Professional Documents
Culture Documents
Amca 99 PDF
Amca 99 PDF
AMCA Publication 99
All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections
107 and 108 of the 1976 United States Copyright Act without the permission of the copyright owner is
unlawful. Requests for permission or further information should be addressed to the Executive Director,
Air Movement and Control Association International, Inc.
AMCA 99 – Standards Handbook
AMCA 99
STANDARDS HANDBOOK
CONTENTS
AMCA Standards are adopted in the public interest. They are intended to eliminate
misunderstanding between the manufacturer and the purchaser and to assist in selecting,
specifying, and obtaining the proper product for the particular need.
Existence of an AMCA Standard does not in any respect preclude any member or non-member
from manufacturing or selling products not conforming to the standard.
Approval of Standards
Proposed standards are reviewed by the appropriate Standards Committees and by the Board of
Directors before submittal to the membership for approval. An affirmation vote of two-thirds of the
members affected is required for adoption or revision.
Review of Standards
AMCA Standards are regularly reviewed, but may also be reviewed at any time at the request of
the membership or by direction of the Board of Directors.
AMCA PUBLICATION 99
STANDARDS HANDBOOK
CONTENTS
Fan impellers differ from one another in many respects, even among those of the same type. One
characteristic that all share is that each individual impeller design can be uniquely related to the overall
diameter of the impeller. Because of this unique relationship, all impellers that share the same geometric
design but differ only in size are said to have similarity. Fan casings share in this unique relationship, with the
casing being optimized with respect to an impeller design so that aerodynamic performance goals are
achieved. A fan design, then, is a geometrically unique combination of fan impeller and fan casing. All sizes
of fans produced according to this unique geometry have similarity based on their respective diameters.
Similarity is useful in that it enables the prediction of aerodynamic performance: given the performance of a
fan of a given diameter at a certain rotational speed and a certain air density, the performance of that same
unique geometry at another impeller diameter, or rotational speed or air density can be determined.
Note that the variables that affect a fan's aerodynamic performance are: impeller diameter, rotational speed
and air density. Since these variables are expressed as ratios, they are dimensionless and are independent
of the system of units used, as long as the units are used consistently for each ratio.
The mathematical statements which describe the effects of these factors on aerodynamic performance for
any known performance point are known collectively as the FAN LAWS.
As with all laws, some similarity requirements must be met if the FAN LAWS are to be effective:
A. DESIGN GEOMETRY
Geometric similarity must exist between any two fan sizes; i.e., dimensions must be proportional and
angularity must be constant for all essential air passages of the impeller and the casing.
B. GAS DENSITY
As air moves through the fan, it is acted upon by the rotating impeller and there results a pressure rise. With
a pressure rise, one would expect that the gas undergoes compression. Compression, in turn, means a
change in gas density.
The compressibility coefficient (Kp) must be calculated for the condition. The supporting formulas for Kp
originate in Appendix C, ANSI/AMCA Standard 210-99.
C. REYNOLDS NUMBER
Reynolds number is one of many descriptors of fan performance, and further information is available in most
textbooks on fluid mechanics. For our purposes here, it is necessary to know that for a given fan design
geometry, there are many possible Reynolds numbers, and that there is a threshold value on either side of
which fluids behave differently. The similarity requirement here is that both sets of operating parameters
result in Reynolds numbers such that the effect of any difference between them is negligible. The implied
requirement is that both of the Reynolds numbers must be on the same side of the threshold value. For
additional information on Reynolds number, see Handbook of Fan Engineering, latest edition.
D. MACH NUMBER
Mach number relates to the velocity of a gas (air) as it passes into or through a fan. Similarity requires that
the Mach numbers for the two sets of parameters must be reasonably close. Just as was the case with
Reynolds number, there is a threshold value and a difference in performance on either side of the threshold.
Since almost all fans operate well below the threshold value for Mach number, no procedure for determining
the threshold value is given in this document.
Then for any given point on a fan performance curve, the relationship between a known performance point
and desired performance point c (converted) is given by the FAN LAWS.
1ST LAW:
3
Qc Dc Nc K p
Q = D N K
pc
2ND LAW:
2 2
Ptc Dc Nc K p ρc
=
Pt D N K pc ρ
3RD LAW:
2 2
Pvc Dc Nc ρc
P = D N ρ
AMCA 99-0021-01
2 2
Pvc Dc Nc ρ c
P =D N ρ
v
[The denominator of the first term should have the subscript “v”.]
Air Movement and
Control Association BSR AMCA
International, Inc. THE FAN LAWS STANDARD
Arlington Heights, IL 99-0021-01
60004-1893 U.S.A. PAGE 3 OF 10
4TH LAW:
5 3
Hc Dc Nc K p ρc
H = D N
K pc ρ
5TH LAW:
Where Ptc and Pvc are established per the 2ND and 3RD FAN LAWS.
6TH LAW:
Psc
ηsc = ηtc
Ptc
Where Psc is established using the 5TH FAN LAW and Ptc is established using the 2ND FAN LAW.
D = Impeller diameter
Dc = Impeller diameter, converted
N = Impeller rotational speed
Nc = Impeller rotational speed, converted
Q = Volume airflow rate
Qc = Volume airflow rate, converted
Pt = Pressure, total
Ptc = Pressure, total, converted
Pv = Pressure, velocity
Pvc = Pressure, velocity, converted
H = Power
Hc = Power, converted
Ps = Pressure, static
Psc = Pressure, static, converted
ηsc = Efficiency, static, converted
ηtc = Efficiency, total, converted
ln (1 + x ) z
Kp =
x ln (1 + z )
Pt
x=
Pt1 + (Cb p b )
γ −1 Ch H
z=
γ Q(Pt1 + (Cb p b ))
2 2
zc Pt1 + Cb p b ρc Nc Dc γ γ c − 1
=
z Pt1c + Cb p bc ρ N D γ − 1 γ c
−1
η γ z η γ η γ z 2
K pc = 1 + t c − 1 c + t c − 1 c c − 2 c ,
γ c − 1 2 γ c − 1 γ c − 1 6
an approximation derived from a series expansion, sufficiently accurate for Kp >= 0.9, and fan mechanical
efficiency ηt is given by:
QPt K p
ηt =
Ch H
Note: For all fans, ηt=ηtc (for incompressible flow only)
Where:
Kp = Compressibility coefficient
Kpc = Compressibility coefficient, converted
x = A coefficient of convenience in the equation
z = A coefficient of convenience in the equation
Pt1 = Total pressure at fan inlet
Cb = Barometer constant: SI = 1 (I-P = 13.63)
Ch = Power constant: SI = 1 (I-P = 6362)
pb = Barometer pressure, Pa (in. Hg)
γ = Ratio of specific heats = 1.4
EXAMPLE:
The following example shows how the FAN LAWS, including compressibility, are applied in aerodynamic
performance predictions for a given fan design.
KNOWN PARAMETERS:
SI I-P
CONVERSION PARAMETERS:
SI I-P
To determine the flow rate Qc and pressure Ptc, FAN LAWS 1 and 2 must be used. The GIVEN and
CONVERTED conditions provide all the information required for the calculations except Kp and Kpc.
Determine Kp:
ln (1 + x ) z
KP =
x ln (1 + z )
Pt
x=
Pt1 + (Cb Pb )
953.7
=
0 + ((1)(97359))
953.7
=
97359
x = 0.0097957
γ −1 Ch H
z=
γ Q(Pt1 + (Cb Pb ))
1.4 − 1
=
(1)(9299)
1.4 7.952 (0 + (1)(97359 ))
z = 0.0034317
ln (1 + x ) z
Kp =
x ln (1 + z )
ln (1 + 0.0097957 ) 0.0034317
=
0.0097957 ln (1 + 0.0034317 )
K p = 0.99684
QPt K p
ηt =
Ch H
ηt = 0.813, or 81.3%
zc Pt1 = (Cb p b ) ρc Nc Dc
2 2
=
z Pt1c = (Cb p bc ) ρ N D
zc / z = 1.81905
Then:
zc
• z = (1.81905 )(0.0034317 ) = (0.006242 )
z
And:
1
K pc =
0.006242 0.006242 2
1 + (2.8455 − 1) + (2.8455 − 1)(2.8455 − 2 )
2 6
Then:
K pc = 0.994235
And to obtain the values for the unknowns at the converted conditions:
3
1524 820 0.99684
Qc = 7.952
927 1000 0.994235
= 29.05 m 3 / s
2 2
1524 820 1.2 0.99684
Ptc = 953.7
927 1000 1.152 0.994235
= 1810.2Pa
5 3
1524 820 1.2 0.99684
H c = 9.299
927 1000 1.152 0.994235
= 64.31kW
EXAMPLE CALCULATIONS IN I-P UNITS:
Pt
x=
Pt1 = (Cb p b )
3.84
=
0 + (13.63 )(28.75 )
3.84
=
391.86
x = 0.0097994
γ −1 Ch H
z=
γ Q(Pt1 + (Cb p b ))
1.4 − 1
=
(6362 )(12.47 )
1.4 16850 (0 + (13.63 )(28.75 ))
0.4 79334.14
=
1.4 16850 (0 + 391.86 )
(0.2857 )(79334.14 )
=
(16850 )(391.86 )
(0.2857 )(79334.14 )
=
(6602841)
[
= (0.2857 )(0.0120151) ]
z = 0.0034327
Then:
zc Pt1 + (Cb p b ) rc Nc Dc
2 2
=
z Pt1c + (Cb p bc ) r N D
= 1.818652
And:
1
K pc =
0.006243 0.006243 2
1 + (2.8455 − 1) + (2.8455 − 1)(2.8455 − 2 )
2 6
Then:
K pc = 0.994262
And to obtain the values for the unknowns at the converted condition:
3 2
60.0 820 0.075 0.99684
Qc = 16850
36.5 1000 0.072 0.99426
= 61534 cfm
2 2
60.0 820 0.075 0.99684
Ptc = 3.84
36.5 1000 0.072 0.99426
= 7.2867 in.wg
5 3
60.0 820 0.075 0.99684
H c = 12.47
36.5 1000 0.072 0.99426
= 86.189 hp
ABSOLUTE PRESSURE – Pressure above a perfect vacuum; the sum of gauge pressure and atmospheric
pressure.
ABSOLUTE ROUGHNESS – A measure of surface unevenness; the distance between high and low points
on a surface.
ACFM (ACTUAL CUBIC FEET PER MINUTE) – Actual volume airflow rate through a plane of measurement,
at the existing air density, expressed in ft3/min.
ACMS (ACTUAL CUBIC METERS PER SECOND) - Actual volume airflow rate through a plane of
measurement, at the existing air density, expressed in m3/s.
ACTUATOR (OPERATOR) – A mechanism attached to a damper or adjustable louver to move its blades, or
attached to a vaneaxial fan to change impeller blade pitch. An actuator may be manually, electrically,
pneumatically or hydraulically powered.
ACOUSTIC ATTENUATION DEVICE – Any component having sound absorption as its primary function.
ADJUSTABLE PITCH – The ability to mechanically alter the angle (pitch) of an impeller blade with the
impeller at rest.
AIR CURTAIN (AIRSTREAM) – A directionally-controlled stream of air, moving across the entire height and
width of an opening, which reduces the infiltration or transfer of air from one side of the opening to the other
and/or inhibits the passage of insects, dust, or debris.
AIR CURTAIN AVERAGE CORE VELOCITY – The average of several air curtain core velocities measured
along the width of the air curtain.
AIR CURTAIN CORE VELOCITY – The peak air velocity of the air curtain as measured across the air curtain
depth at a specified distance from the discharge nozzle.
AIR CURTAIN DEPTH – The airstream dimension perpendicular to both the height and width of the opening
being protected.
AIR CURTAIN UNIT EFFICIENCY – The ratio of the air curtain output air power to the power input to the
motor, expressed as a percentage.
AIR CURTAIN UNIT RATED THROW – The distance away from an air curtain unit discharge nozzle to a
point where a specified minimum air velocity is achieved.
AIR CURTAIN UNIT VELOCITY PROJECTION – The average air curtain core velocity at specified distances
from the air curtain unit discharge nozzle.
AIR CURTAIN WIDTH – The airstream dimension perpendicular to the direction of airflow and parallel to the
width of the opening being protected.
AIR (GAS) DENSITY – The mass per unit volume of air or gas.
AIRFOIL – (1) A shape such that, when it is moved through air, has greater lift than drag. (2) A blade or vane
having a streamlined shape.
AIR SYSTEM – An assembly of connected ducts, filters, conditioning devices, dampers, louvers and fans for
the purpose of moving air from one place to another in a controlled fashion.
AIR THROW – The horizontal or vertical axis distance an air stream travels after leaving an air outlet before
the air velocity is reduced to a specific terminal value.
AMCA TESTING LABORATORY – The association’s testing laboratory, currently located in Arlington
Heights, Illinois, or an independent laboratory licensed by AMCA to perform pre-certification performance
tests and performance check tests.
AMCA ACCREDITED LABORATORY – A laboratory equipped and staffed to conduct tests according to the
appropriate AMCA-accepted test method, and which has been inspected by an AMCA staff engineer and duly
approved for such testing.
ANECHOIC TERMINATION – A device placed at the end of a test duct to prevent excessive reflection of
sound waves back into the duct, thus reducing interference with the sound waves being measured.
ATTENUATION – The amount by which sound amplitude is decreased as it travels from a sound source to a
receiver located at a given point.
AVERAGE OUTLET VELOCITY – (1) The airflow rate of a fan per unit area of the fan discharge, calculated
by dividing the airflow rate by the area of the fan discharge. (2) The free-delivery airflow rate of an air curtain
unit divided by the face area of the discharge nozzle.
BACKPLATE – A circular plate, a component of a centrifugal fan impeller, which is attached to the fan hub
and serves as the major attachment for the impeller blades and as the means of transmitting torque to them.
BACKPLATE / CENTERPLATE LINER – A narrow strip of steel, ceramic or synthetic material, installed in
sets, each attached to the backplate / centerplate of an impeller, adjacent to an impeller blade, for the
purpose of protection against erosion.
BALANCING – The process of adding or removing mass on a rotor to move the center of gravity toward the
axis of rotation so as to reduce the unbalanced forces.
BEARING LOSS – The power loss resulting from friction in the main bearings of a fan or motor.
BLADE – (1) The flow element of an impeller, which, by its shape and motion, generates airflow inside a fan,
transforming impeller rotational energy to kinetic energy of airflow. (2) A movable surface in a damper or
louver that can be rotated to control airflow. (3) A stationary louver surface intended to restrict the passage of
water, sound or other airborne materials, or to limit visual see-through.
BLADE ENTRY SEAL – The sealing arrangement through which a damper blade passes in a guillotine
damper.
BLADE LINER – A steel, ceramic or synthetic material piece having the same size and shape as the fan
blade, which covers the fan blade face in part or completely for the purpose of protection against erosion.
BLADE PASSAGE FREQUENCY – The tone generated by the fan’s blades passing a fixed object and
having a frequency given by: F(Hz) = (number of blades x fan revolutions per minute) / 60.
BLADE SUPPORT – (1) A structural member, located inside the duct section of a guillotine damper frame,
which supports the blade load when the damper is in the closed position; (2) A bracket that connects a
stationary louver blade to a rear-mounted structural support.
BLAST AREA – The outlet area of a centrifugal fan less the projected area of its cut-off.
BONNET – The portion of a guillotine damper that supports the damper blade when the damper is in the open
position. (1) OPEN TYPE: The damper blade is exposed to the atmosphere when blade is withdrawn from the
duct. (2) FULLY ENCLOSED (SEALED) TYPE: The entire bonnet encloses the damper blade when the
damper is in the open position.
CENTERLINE SUPPORT – A method of supporting a fan housing at its centerline when necessary to control
differential thermal growth of the housing.
CERTIFIED RATING – A published performance rating of a product which AMCA has licensed to bear the
AMCA Certified Performance Rating Seal. The seller of the product certifies that the rating is in accordance
with the appropriate AMCA-approved test method and that the requirements of the AMCA Certified Ratings
Program have been met.
CERTIFIED RATINGS PROGRAM – The testing and licensing program established by AMCA International to
verify the published performance ratings of a product produced by a seller.
CHAMBER – (1) A test enclosure having a means for settling airflow, a cross sectional area larger than the
inlet/outlet of test equipment connected to it, and the capability for measuring airflow rate and pressure. (2)
An enclosure used to regulate airflow and to absorb sound.
CLASS STANDARD – An established minimum performance level of fan aerodynamic performance in terms
of pressure and airflow rate.
COMPRESSIBILITY – The characteristic of air or a gas whereby its density is a function of pressure.
COMPRESSIBILITY COEFFICIENT – A thermodynamic coefficient used to correct the perfect gas equation
when applied to air or gas.
CONTINUOUS LINE (CONTINUOUS BLADE) – A term describing a louver constructed with blades that
present an uninterrupted horizontal or vertical line to complement or enhance architectural features.
CONTROLLABLE PITCH IMPELLER – An axial impeller having a mechanism by which the pitch angle of all
the impeller blades can be changed while the impeller is rotating.
CORE AREA – The front cross-sectional area (product of minimum width and minimum height) of the front
opening of a louver assembly with the blades removed.
CORE AREA VELOCITY – The airflow rate through a louver divided by its core area.
CORROSION RESISTANT – A term descriptive of materials or surface treatments that reduce corrosive
attack.
COUNTERBALANCE – Weights or springs that offset the unbalanced weight of an eccentrically pivoted
damper blade.
CRITICAL SPEED, FIRST – The rotational speed of a fan corresponding to the lowest natural frequency of
the rotating fan impeller and shaft assembly when mounted on rigid supports without benefit of damping.
CUT-OFF – A baffle or plate at the narrowest radial distance between the impeller and the housing near the
outlet of a centrifugal fan, and which directs air away from the impeller and minimizes recirculation of air.
CURB – A roof penetration with a raised perimeter to seal against the weather and to facilitate installation of
roof mounted ventilation equipment such as a fan or hood.
DECIBEL – A dimensionless number expressing, in logarithmic terms, a level of sound pressure or power.
DETERMINATION – The complete set of measurements for a particular point of operation for a product under
test. The measurements must be sufficient to determine all performance variables.
DIFFUSER – (1) A duct discharge termination through a ceiling for the control and discharge of air. (2) A
gradual transition of a duct, located at a fan outlet, which increases in cross sectional area and permits a
portion of velocity pressure to be regained as static pressure; also known as an evasé.
DISCHARGE ANGLE – (1) The angle formed by the plane of an opening and the direction of an air curtain.
(2) The angle of air or other gas flow exiting an impeller.
DISCHARGE NOZZLE – An air curtain unit component that directs and controls the airstream.
DISCHARGE NOZZLE DEPTH – The inside nozzle dimension perpendicular to both the direction of airflow
and the width of the airstream.
DISCHARGE NOZZLE WIDTH - The inside nozzle dimension perpendicular to the direction of airflow and
parallel to the width of the airstream.
DRY-BULB THERMOMETER – An ordinary thermometer, especially one with an un-moistened bulb; not
influenced by atmospheric humidity.
DUCT – A passageway used primarily for conveying air or other gas at low pressure.
DUCTED FAN – A fan having ductwork connected to the fan inlet, the fan outlet, or both.
DYNAMIC SIMILARITY – A comparison that uses ratios of forces due to elasticity, viscosity, gravity, surface
tension, inertia and pressure to show equivalence between two similar fans. The variables compared are fan
Reynolds number, point of operation, compressibility, gas specific heat ratio, and tip speed Mach parameter.
EFFICIENCY – A ratio of the useful energy provided by a dynamic application to the energy supplied to the
system at a specific point of operation.
END REFLECTION – A phenomenon that occurs whenever sound is transmitted across an abrupt change in
area, such as from the end of a duct into a room. When end reflection occurs, some of the sound is reflected
back into the smaller area of the duct and does not escape into the room.
ENERGY FACTOR – The ratio of the total kinetic energy of airflow to the kinetic energy corresponding to the
average air velocity.
EQUIVALENT DIAMETER – The diameter of a circle having the same area as another geometric shape. For
a rectangular cross-section having width (a) and height (b), the equivalent diameter is given by: De =
(4ab/π)0.5
EXPANSION JOINT (FLEXIBLE CONNECTOR) – A flexible member used to attach a fan inlet and/or outlet
to a connecting duct.
FACE AREA – The total cross-sectional area of an air curtain unit discharge, a damper, louver, or duct.
FAN – (1) A device that uses a power-driven rotating impeller to move air or gas. The internal energy
increase imparted by a fan to air or a gas is limited to 25 kJ/kg (10.75 BTU/lbm). (2) A device having a power-
driven rotating impeller, without a housing, for circulating air in a room.
FAN AIR (GAS) DENSITY – The density of air or gas corresponding to the total pressure, total temperature,
and composition of the air or gas at a fan inlet.
FAN AIRFLOW RATE – The volume airflow rate at a fan inlet at fan air density.
FAN APPURTENANCES – Accessories added to a fan for the purpose of control, isolation, safety, static
pressure regain, erosion protection, etc. Common appurtenances include inlet box(es), inlet box damper,
variable inlet vane, outlet damper, vibration isolation base, inlet screen, belt guard, evasé or diffuser, sound
attenuator, erosion protection, and turning gear.
FAN BOUNDARIES – Limits defining the interfaces between the fan and the remainder of the air system and
delineated as the planes perpendicular to the airstream as it enters and leaves a fan. Various appurtenances,
such as an inlet box, inlet vane, inlet cone, silencer, screen, rain hood, damper, evasé or diffuser, may be
included as part of a fan between the inlet and outlet boundaries.
FAN EQUIPMENT – An assembly of a fan and its various appurtenances, as defined by the fan boundaries.
FAN IMPELLER POWER – The power delivered to a fan impeller, specifically, the fan shaft power minus the
bearing loss.
FAN INLET – The plane perpendicular to an airstream where the airflow first meets the inlet cone or the inlet
box furnished by the fan manufacturer.
FAN INLET AREA – The gross inside area measured at the plane(s) of the inlet connection(s). For
converging inlets, the inlet area is considered to be a plane perpendicular to the airstream where it first meets
the inlet cone.
FAN OUTLET – The plane perpendicular to the airstream at the outlet opening of the fan or the manufacturer-
supplied evasé or diffuser.
FAN OUTLET AREA – The gross inside area measured at the plane of the outlet opening. For a roof
ventilator, it is the gross impeller outlet area for centrifugal types or the gross housing area at the impeller for
axial types.
FAN PERFORMANCE CHARACTERISTICS – The pressure rise (total or static) and the volume airflow rate
generated by a fan, and its power consumption at any given point of operation.
FAN POWER INPUT – The power required to drive a fan and any elements in the drive train.
FAN POWER OUTPUT – The useful power delivered to the air or a gas, and which is proportional to the
product of the fan airflow rate, the fan total pressure, and the compressibility coefficient.
FAN REYNOLDS NUMBER – A dimensionless parameter for judging dynamic similarity of flow in
geometrically similar fans, relating inertia to viscous forces, and given by:
Re = πND2ρ / 60µ
where: Re = fan Reynolds number, dimensionless
π = 3.14159…
N = fan rotational speed, rpm
D = tip diameter of impeller, m (ft)
ρ = inlet air density, kg/m3 (lbm/ft3)
µ = absolute viscosity, Pa•s (lbm/ft•s)
FAN SHAFT – The spindle on which a fan impeller is mounted, and upon which it rotates.
FAN SHAFT POWER – The power delivered to the input end of a fan shaft, exclusive of drive losses other
than that due to the fan or motor bearings, and fan shaft seal friction.
FAN SOUND POWER – The ratio of sound power, radiated into a standard test duct, to a reference value of
1.0x10-12 watts.
FAN ROTATIONAL SPEED – The rotating speed of a fan impeller, in revolutions per minute.
FAN STATIC EFFICIENCY – A parameter consisting of fan total efficiency multiplied by the ratio of static
pressure to total pressure, at a given point of operation.
FAN STATIC PRESSURE – At a given point of fan operation, the difference between fan total pressure and
fan velocity pressure; the difference between static pressure at fan outlet and total pressure at fan inlet.
FAN STATIC PRESSURE RISE – At a given point of fan operation, the increase in static pressure between
fan inlet and fan outlet.
FAN TOTAL EFFICIENCY – At a given point of fan operation, a ratio equal to the fan power output divided by
the power input to the fan.
FAN TOTAL PRESSURE – At a given point of fan operation, the difference between total pressure at fan
outlet and fan inlet.
FAN VELOCITY PRESSURE – The pressure corresponding to the average air velocity at a specified fan
outlet.
FIXED PITCH – A term descriptive of an axial impeller having all blades permanently secured at a given pitch
angle.
FLASHING – A sheet metal strip placed at the junction of intersecting building surfaces to resist the entrance
of water.
FLOW RATE – The volume flow rate of a gas at a specific gas density.
FOUNDATION STIFFNESS – The lateral spring constant of the foundation as referenced to the fan bearing
centerline. Factors to be considered include the foundation block, the sub-soil, piles, if any, the concrete pier
supporting the steel fan supports, and the interface between the steel supports and the concrete pier.
FREE AREA – The minimum louver or damper area through which air can pass.
FREE AREA VELOCITY – The airflow rate through a damper or louver divided by its free area.
FREE AIR DELIVERY – That point of operation where a fan or an air curtain unit operates against zero static
pressure.
FREQUENCY – The number of complete cycles in a unit of time. When applied to sound, it is the number of
complete pressure wave fluctuations which pass a given point each second. For a time period of seconds,
the unit of measure is the Hertz (Hz).
GAUGE PRESSURE – The value of a pressure when the reference pressure is the barometric pressure at
the point of measurement.
GEOMETRIC SIMILARITY – A comparison of the ratio of corresponding dimensions of two fans, including
angles, each dimension proportioned to impeller diameter. The proportional dimensions include material
thickness, clearances, and roughness, as well as airflow passages
GUIDE VANES – Curved stationary vanes (stator vanes) located at the impeller inlet or discharge to reduce
swirl and to enhance static pressure regain from the airflow.
HEAD – (1) The upper or highest frame member of a damper or louver. (2) Fluid pressure expressed in
terms of height of water column.
HOUSING – A stationary enclosure for an impeller, having an inlet and an outlet, and designed to direct the
flow of air through the impeller and towards the outlet. The housing may also affect the energy transformation
of the airstream.
HOUSING SIDEPLATE LINER – A narrow strip of steel, ceramic or synthetic material fastened to the
sideplate of a centrifugal fan housing at the intersection of the sideplate and the scroll, for the purpose of
erosion protection.
HUB – The center portion of an impeller, by which the impeller is connected to its shaft, and through which
the shaft transmits torque to the impeller.
HYDRAULIC DIAMETER – A characteristic dimension in Reynolds number calculations, taken normal to the
fluid flow and equal to four times the cross-sectional area divided by the wetted perimeter.
IDENTICAL MODULES – A standard for performance comparison wherein two fans have identical
aerodynamic designs, including fan impeller diameter, impeller tip width, number of blades, blade pitch, blade
arc, blade size, scroll configuration and angle of expansion, rotational speed, distance to the next adjacent fan
or barrier, and essentially the same inlet and outlet conditions. Motor frame size and drive are be the same if
these are within the airstream.
IMPELLER – The assembled rotating component of a fan, designed to increase the energy level of the
airstream.
INLET BOX – A component, similar to a duct elbow, which can be added to the inlet of an axial or centrifugal
fan for the purpose of directing airflow into the fan inlet in line with the axis of the fan shaft.
INLET FLOW PROFILE – The shape of the air velocity profile just upstream of a fan inlet and which indicates
variation in airflow through a plane extending across the airflow passage.
INTERFERENCE FIT – A mating condition of two components wherein the limits of size are so specified that
an interference always results when the mating components are assembled; either a press fit or a shrink fit.
JACKSHAFT – (1) A separate shaft used to operate multiple louver or damper sections. (2) An intermediate
shaft between motor and fan impeller.
JOURNAL – The part of a rotor that is in contact with or supported by a bearing in which it revolves.
KINEMATIC SIMILARITY – A relationship between airflow systems requiring that the ratios of all
corresponding velocities be similar for two fans to be considered similar. This includes corresponding
velocities of the air or gas and corresponding peripheral velocities of the impellers. The directions and points
of application of all corresponding vectors must be identical.
LINKAGE – A system of bar links, pivots, and rotating members for the transfer of force and motion to louver
and damper blades.
MACH NUMBER – A ratio of fluid velocity to the speed of sound in the same fluid.
MAKE-UP AIR – Outside air that is brought into a building to replace exhaust air and building leakage
(exfiltration), or process exfiltration.
MASS AIRFLOW RATE – The mass of air that passes through a given area in unit time and is obtained by
multiplying the volumetric airflow rate by the air density.
MAXIMUM CONTINUOUS RATING – The maximum continuous airflow, pressure and temperature values at
which the fan is specified to operate.
MEASUREMENT PLANE – The radial plane in the test duct, generally perpendicular to the airflow, at which
measurement(s) is(are) obtained.
MECHANICAL RUN-OUT – The total actual variation in the location of a shaft surface during a complete
revolution as determined by a stationary measuring device such as a dial indicator.
MOTOR POWER – The power delivered from the output shaft of the motor.
NATURAL FREQUENCY – The frequency at which a system oscillates in the absence of external forces and
exhibits a maximum response to an external input.
NON-DUCTED FAN – A fan without ductwork connected to either its inlet or its outlet.
NOSE PIECE (REPLACEABLE) – A sacrificial metal, ceramic or synthetic material piece added to the
leading edge of an airfoil blade for the purpose of erosion protection.
NOZZLE – A flow-measuring device having a streamlined entrance and a sharp-edged outlet perpendicular to
its longitudinal axis. Airflow rate through a nozzle is proportional to the square root of the differential pressure
across the nozzle and the throat area of the nozzle.
OCTAVE BAND – A range of frequencies between two end frequencies selected such that the center
frequency is twice the center frequency of the next lowest band.
ONE-THIRD OCTAVE BAND – A band of frequencies resulting from the division of an octave band into three
smaller bands.
OPPOSED BLADE DAMPER – A damper constructed such that adjacent blades rotate in opposite directions.
OUTLET VELOCITY – The average velocity of air emerging from an outlet, measured in the plane of the
outlet.
OUTLET VELOCITY UNIFORMITY – A measure of test velocity variation equal to the standard deviation of
measured test velocities divided by the average of those test values, the ratio being subtracted from one
(1.0).
PACKING – Sealing material used to minimize or eliminate leakage at the shaft penetration of a housing or
frame.
PARALLEL BLADE DAMPER – A damper in which the blades rotate in the same direction.
PARTIAL BLADE LINER – A narrow piece of metal, ceramic or synthetic material located at the intersection
of the impeller blade and backplate or centerplate for erosion protection.
PEAK DESIGN TEMPERATURE – The maximum temperature at which a piece of equipment can operate for
a specific duration.
POINT OF OPERATION – The relative position on a fan or air curtain unit performance curve corresponding
to a particular airflow rate, pressure, power consumption, and efficiency.
POINT OF RATING – The specified fan operating point on its characteristic curve.
POWER RATING - The amount of power consumed by the drive motor(s) of the air curtain unit.
PRESSURE – (1) Force per unit area; (2) Stress per unit volume of a fluid, corresponding to the energy per
unit volume of a fluid.
PRESSURE DIFFERENTIAL – Commonly, the change in static pressure across a device. The term is
seldom if ever associated with velocity pressure or total pressure.
PRESSURE DROP – Commonly, (1) The static pressure difference between two points in an airflow system,
due to frictional resistance along system walls, or in passing over or through an obstruction; (2) A measure of
the resistance to airflow across a device, which is expressed as the difference in static pressure across the
device at a specific rate of airflow. The term is seldom if ever associated with velocity pressure or total
pressure.
PRESSURE LOSS – The change in total pressure due to friction and turbulence.
PRODUCT LINE – A product or series of product sizes with a common design purpose and generally similar
aerodynamic features, but not necessarily homologous, cataloged under the same product description or
name and/or identifying references.
PROPELLER – A bladed device (impeller) that rotates on a shaft to produce a useful thrust of air or gas in a
direction parallel with the shaft axis.
RATE OF TEMPERATURE CHANGE – The increase or decrease in temperature per unit time.
RELATIVE ROUGHNESS FACTOR – The measurement of surface unevenness, from peaks to valleys,
divided by a dimension such as pipe diameter.
RESONANCE – A condition of high vibration response that occurs when the frequency of an external driving
force approaches the natural frequency of the system.
RESONANT SPEED, DESIGN – The calculated fan rotational speed corresponding to the lowest natural
frequency of the combined fan shaft in bending, considering the fan rotor, oil film, bearing housing, and
bearing supports, but excluding the effect of foundation stiffness.
RESONANT SPEED, INSTALLED – The calculated fan rotational speed corresponding to the lowest natural
frequency of the combined fan shaft in bending, considering the fan rotor, oil film, bearing housing, and
bearing supports, and including the effect of foundation stiffness.
REYNOLDS NUMBER – A dimensionless number representing the ratio of internal forces to viscous forces at
a particular point of a fluid in motion. Its value is calculated as: the fluid’s density times the flow velocity at the
point of interest, multiplied by a characteristic length, and the product divided by the fluid’s viscosity.
Re = ρ (VD / µ) = (VD / ν )
where: Re = Reynolds number, dimensionless
ρ = inlet air density, kg/m3 (lbm/ft3)
V = Velocity of air, m/s (ft/s)
D = Diameter, m (ft)
µ = absolute viscosity, Pa•s (lbm/ft•s)
ν = kinematic viscosity, m2/s (ft2/s)
ROTOR – An assembly consisting of a fan impeller mounted on its shaft.
SAMPLING TUBE – A windscreen tube designed for minimum sensitivity to airflow noise, and designed to be
attached to a standard 13 mm (0.5 in.) microphone.
SCROLL LINER – A metal, ceramic or synthetic material piece attached to a fan scroll for the purpose of
erosion protection.
SEAL AIR – (1) Air introduced into the air chamber of an isolation damper at a pressure higher than that of
gases either upstream or downstream, to prevent passage of duct gas across the enclosed damper space. (2)
Pressurized air introduced into a shaft seal chamber to function as a leakage barrier to process gas. (3)
Pressurized air introduced into a housing around a furnace to prevent the escape of products of combustion.
SEATING TORQUE - The amount of torque required to compress the seals or hold the louver or damper
blades in the closed position.
SEISMIC QUALIFICATION – Documentation supplied with an item of equipment that substantiates the ability
of the equipment to withstand the effects of an earthquake of specified magnitude.
SHAFT – A cylindrical piece of metal, usually solid, that is used to support a rotating part such as a fan
impeller, and transmit torque to the supported component.
SHAFT SEAL – A device that creates a barrier over the circumference of a fan shaft or damper axle for the
purpose of limiting or preventing the passage of air or gas across the barrier.
SHALL and SHOULD – In this and other AMCA standards, the word shall is understood to be mandatory,
and the word should as advisory.
SHUT-OFF – That point of fan operation where the airflow rate is zero.
SIMILARITY – A ratio used to compare a given characteristic of two fans; when equated to unity, similarity is
said to exist for that characteristic. The ratios considered may be for dynamic, geometric, and/or kinematic
characteristics
SONE – (1) A unit of loudness corresponding to the loudness of a sound at a frequency of 1000 Hz and a
sound pressure of 0.02 microbar (40 dB); (2) A linear unit of sound loudness based on the perception of the
average human ear.
SOUND – An auditory sensation produced by the vibration of matter that results in propagation by variation of
pressure, particle displacement or density through an elastic medium.
SOUND POWER LEVEL – The acoustic power rating of a sound source measured in decibels and equal to
ten times the logarithm (base 10) of the acoustic power in watts with reference to 1x10-12 watts.
SOUND PRESSURE LEVEL – The acoustic pressure at a point in space where a microphone or a listener’s
ear is situated. One decibel (dB) of sound pressure is defined as 20 times the logarithm (base 10) of the
sound pressure fluctuation with reference to 0.0002 microbars (20 micropascals).
SPECIFIC HEAT – The ratio of the amount of heat required to raise the temperature of a given mass of any
substance one degree to that amount of heat required to raise the temperature of an equal mass of a
standard substance one degree (usually water at 15°C (59°F)).
SPECIFIC HEAT AT CONSTANT PRESSURE – The quantity of heat required to raise the temperature of a
unit mass of a substance one degree at constant pressure.
SPECIFIC HEAT AT CONSTANT VOLUME - The quantity of heat required to raise the temperature of a unit
mass of a substance one degree at constant volume.
SPECIFIC HEAT RATIO – The numeric ratio of the specific heat of a gas at constant pressure to that of the
same gas at constant volume.
STALL LIMIT – That point near the peak of an axial fan’s pressure curve (for a particular blade angle) that
corresponds to the minimum airflow at which the fan can be operated without instability.
STANDARD AIR – Air having a density of 1.2 kg/m3 (0.075 lbm/ft3), a specific heat ratio of 1.4, a viscosity of
1.819E-05 Pa•s (1.222E-05 lbm/ft-s) and an absolute pressure of 101.325 kPa (406.78 in. wg). Air at 20°C
(68°F), 50% relative humidity, and 101.325 kPa (29.92 in. Hg) has these properties, approximately.
STANDARD AIR DENSITY – A density of 1.2 kg/m3 (0.075 lbm/ft3), corresponding approximately to air at
20°C (68°F), 50% relative humidity, and 101.325 kPa (29.92 in. Hg).
SCFM (STANDARD CUBIC FEET PER MINUTE) – The volume airflow rate through a plane of
measurement, corrected to standard air density of 0.075 lbm/ft3.
SCMS (STANDARD CUBIC METERS PER SECOND) - The volume airflow rate through a plane of
measurement, corrected to standard air density of 1.2 kg/m3.
START-OPEN PRESSURE – The differential pressure across a backdraft or pressure relief damper at which
the blades begin to rotate towards the open position.
STATIC PRESSURE – That portion of air pressure that exists by degree of compression only.
STATIC REGAIN – (1) The conversion of velocity pressure at a small area into static pressure at a larger
area by slowing the gas or air velocity by means of a diffuser or an evasé; (2) The amount of static pressure
gained by conversion of velocity pressure to static pressure.
STATIC TEMPERATURE – The temperature that exists by virtue of the internal energy of the air alone. If a
portion of the energy is converted to kinetic energy, the static temperature is decreased accordingly.
STOP – An angle or rigid strip used to close the gap between a blade edge and frame at the top and bottom
of a damper or a louver.
SUB-FRAME (BUCKFRAME) – A frame installed in a wall opening to facilitate the mounting or removal of a
louver.
SUB-SILL (EXTENDED SILL) – A shaped metal flashing installed at the bottom of a wall opening to facilitate
water drainage.
SURGE LIMIT – A point near the peak of a centrifugal fan’s performance pressure curve that defines the
minimum airflow rate at which a fan can be operated without instability.
SYSTEM EFFECT FACTOR – A decrease in fan performance capability, observed as a pressure loss that
results from the effect of fan inlet restrictions / obstructions, fan outlet restrictions or other conditions
influencing the performance of the fan when it is installed in a system.
SYSTEM PRESSURE LOSSES – The sum of the static pressure losses due to friction, shock, dissipation of
velocity pressure at the system discharge and the static pressure differences between the entry and
discharge openings of an air system. System pressure losses are total pressure losses.
TEMPERATURE, DESIGN – The minimum or maximum temperature at which a fan or damper can be
continuously operated.
TEMPERATURE, DESIGN AIR – (1) That air temperature at which a heating, ventilating or air conditioning
system or apparatus is designed to maintain (indoor design) or to operate against (outdoor design). Outdoor
design temperature is usually give for both minimum and maximum conditions. (2) The maximum and/or
minimum gas temperature for specification of process control equipment.
TEMPERATURE, OPERATING – The air temperature in the fan under actual normal operating conditions.
TERMINATING DUCT – Where a fan under test for sound and equipped with both inlet and outlet ducts, one
duct contains the sound pressure measurement device. The duct on the opposite side may be equipped with
an anechoic termination and is known as the terminating duct.
TEST – A series of determinations for various points of operation of a fan, damper, louver, airflow
measurement station or air curtain unit.
TEST BLOCK – The operating test point above and beyond the Maximum Continuous Rating that
demonstrates the fan margin to the customer.
TEST DUCT – (1) A duct section of prescribed length that is defined originally in ANSI/AMCA 210 (and
subsequently in AMCA standards 500D and 500L), and which is used to control and measure airflow rate and
pressure. (2) A duct that functions as the sound measurement section and has an anechoic termination.
TIP SPEED MACH PARAMETER – A dimensionless number expressing the ratio of a fan impeller’s
peripheral velocity to the local velocity of sound at the fan inlet.
TOTAL PRESSURE – The air pressure that exists by virtue of the degree of compression and rate of motion
of flowing air. It is equal to the algebraic sum of the velocity pressure and the static pressure at a point.
Thus, if the air is at rest, the total pressure will equal the static pressure.
TOTAL TEMPERATURE – The temperature that exists by virtue of the internal and kinetic energy of the air.
If the air is at rest, the total temperature will equal the static temperature.
TORSIONAL CRITICAL SPEED – The fan rotational speed that corresponds to the natural frequency in
torsion of its power transmission system, including driver, drive train components, and the fan rotor.
TURNING GEAR – An intermittent fan drive arrangement consisting of a motor, a speed reducer, and a
unidirectional engagement clutch fastened to the outboard end of a fan shaft or motor shaft through a flexible
coupling. The turning gear rotates the complete rotating assembly at a low speed to prevent distortion in the
rotor assembly due to uneven cooling. The turning gear may be sized to have the capability of starting the
main rotor. Axial fans generally do not require a turning gear.
VANE – (1) A stationary curved surface used to straighten or direct airflow, (2) A flat or curved surface that
can be rotated about an axis to direct airflow.
VARIABLE PITCH IMPELLER – An axial impeller having a mechanism or mechanisms by which the pitch
angle of each impeller blade can be changed while the impeller is at rest.
VELOCITY DISTORTION PARAMETER – AXIAL – A parameter characterizing air velocity distortion within a
measuring plane at a constant radius in a circular duct, and in a direction parallel to the fan shaft centerline in
a rectangular duct. It is expressed as a percentage of the mean velocity of the air at the fan inlet
VELOCITY DISTORTION PARAMETER – INLET FLOW – An indicator of the variation in the airflow field at
the inlet plane of a fan. It is calculated by applying the principle of standard deviation, using velocity
measurements taken in a matrix form in a transverse plane across the flow field and expressed as a
percentage of the mean velocity of the air at the fan inlet.
VELOCITY PRESSURE – That portion of air pressure that exists by virtue of rate of motion only.
VELOCITY PROFILE – A graphic presentation of the distribution of velocities, shown parallel to the general
direction of flow, in a moving fluid.
VELOCITY PROJECTION – The average core velocity at several distances from a discharge nozzle of an air
curtain unit.
VIBRATION – The continuing periodic motion of an elastic system having properties of amplitude, frequency,
and phase, with values generally reported as displacement, velocity, or acceleration.
VISCOSITY – A proportionality factor relating the shearing stress to a unit rate of change in the velocity of the
flowing gas or liquid. Also known as ABSOLUTE VISCOSITY or DYNAMIC VISCOSITY, depending on
whether the value is defined in terms of force or terms of mass.
VOLUME AIRFLOW RATE – The volume of air that passes through a given area in unit time.
WAVELENGTH – In a wave, the distance between two adjacent points that have the same phase. For sound
waves, wavelength is determined by dividing the speed of sound in the medium through which the wave
propagates by the frequency of the sound.
WET-BULB DEPRESSION – The difference between the dry-bulb and wet-bulb temperatures at the same
location.
WET-BULB THERMOMETER – A thermometer having a sensing bulb covered with cloth, usually muslin or
cambric, and saturated with water.
WIND-MILLING – The reverse-direction rotation of a fan rotor due to a flow of natural air into the fan housing
when the fan driver is not energized.
ABRASION RESISTANT FAN (or DAMPER) - A fan or damper designed to minimize abrasion, having parts
subject to wear constructed of materials that are abrasion resistant and/or are easily replaceable.
ACOUSTICAL DUCT SILENCER – An air duct section containing sound absorbing materials that reduce the
transmission of sound through the air passage.
ACOUSTICAL LOUVER - A louver incorporating sound absorbing material to reduce sound transmission
across an opening.
ADJUSTABLE LOUVER - A louver in which the blades may be rotated either manually or mechanically.
AIR CURTAIN UNIT – An air moving device that produces a curtain of air.
AIR DIFFUSER - A duct discharge termination located in a ceiling and arranged to direct airflow, or to promote
air mixing.
AIRFLOW MEASUREMENT STATION - A multiple-point sensing device used to measure the airflow in a duct
and which consists of a single or multiple array of sensors in permanent position across the duct system.
1. DIFFERENTIAL (VELOCITY) PRESSURE OUTPUT TYPE - Converts air velocity into a differential
(velocity) pressure signal which correlates to the velocity or volume of air flowing through a duct.
2. ELECTRONIC OUTPUT TYPE - Converts air velocity into an electronic signal that correlates directly and
proportionally to the velocity of the air volume flowing through a duct.
AIR-HANDLING UNIT - A packaged assembly of air-conditioning components (coils, filters, fan, humidifier, and
so forth) that provides for treatment of air before it is distributed.
1. BLOW-THROUGH – Fan is mounted upstream of a heat exchanger.
2. CENTRAL STATION – Does not include a source of heating or cooling.
3. COOLING – Includes a means for cooling air.
4. COOLING – HEATING – Includes the means for both heating and cooling air.
5. DRAW-THROUGH – Heat exchanger(s) are mounted upstream of the fan.
6. HEATING – Includes a means for heating air.
AXIAL FAN - A fan in which the airflow is predominately parallel to the impeller’s axis of rotation.
BACKDRAFT DAMPER - A damper which, when mounted in a duct or opening, permits airflow in one direction
only.
BAROMETRIC DAMPER - A backdraft damper having an adjustable start-open pressure and used for gravity
ventilation or other low velocity applications.
BATH FAN – A fan used to exhaust air from a bathing / toilet area for the primary purpose of moisture and/or
odor removal.
BIFURCATED FAN - A direct-driven fan having the airstream-mounted drive motor separated from the
airstream by means of a compartment or tunnel.
BLAST DAMPER – A damper that reacts to sudden pressure changes in an air system, to either relieve the air
pressure, or to isolate a space from the rapid pressure rise.
BLOWER – A fan that operates against air system resistance downstream of the fan; a Forced Draft Fan.
BOX FAN – A fan used in an office or residential application and having the motor and impeller enclosed in an
approximately square box having a handle.
CEILING DAMPER - A device intended to protect an air duct opening in a fire-rated ceiling assembly and which
operates to interrupt airflow automatically in the event of fire to restrict the passage of flame and heat.
CEILING EXHAUST FAN - A fan mounted in a ceiling and which serves to exhaust air from a room.
CEILING FAN - A propeller fan supported from a ceiling and which serves to circulate air within a given space;
also known as an air circulation fan.
CENTRIFUGAL FAN - A fan in which a gas, such as air, is moving in a primarily axial direction upon entering
the impeller and has its direction changed by the impeller blades to an essentially radial flow at the impeller
discharge. The impeller is generally contained in a volute housing
CIRCULATING FAN - A fan used for moving air within a space, and which is unconnected to any ducting, and is
usually without a housing.
COMBINATION LOUVER-DAMPER - A louver having both stationary and eccentrically pivoted movable blades
that can be opened and closed.
COMBUSTION AIR BLOWER – A centrifugal fan that serves to supply pressurized air to a burner system
combusting gas, oil, or other fuel.
CONTRA-ROTATING FAN - An axial flow fan having two impellers arranged in series and rotating in opposite
directions.
CONVEYING FAN - A fan suitable for conveying solids (e.g., wood chips, textile waste, pulverized material, or
dust).
CORROSION RESISTANT FAN – A fan having an impeller and housing constructed of materials that resist
corrosion, or having airstream or exterior components surface-treated to minimize the corrosive effect of certain
chemicals or compounds.
CROSS-FLOW FAN - A fan in which the fluid path though the impeller is in a direction substantially at right
angles to its axis with air both entering and leaving radially at its periphery.
DAMPER – A device used to vary the volume of air passing through an opening, duct or confined cross-section
by varying the cross-sectional area.
DESTRATIFICATION FAN - An air circulation fan located in a room to move warm air from the ceiling
downward or to mix air in a given space.
DOWNDRAFT FAN – An exhaust fan that serves to remove heated air and moisture by inducing air to flow
down to a fan inlet located below a cooking surface.
ELECTRIC AIR HEATER – A space heater having electric resistance elements as the heat source and a fan for
the circulation of heated air.
EVAPORATIVE COOLER – An assembly consisting of a fan or fans and other necessary equipment to cool by
evaporation the airflow created by the fan(s).
FACE-AND-BYPASS DAMPER – A pair of dampers that operate together but with opposite motion, to direct an
airstream either through or around a heat transfer device.
FIRE DAMPER - A device arranged to interrupt airflow automatically through part of an air system so as to
restrict the passage of flame, and installed in a fire-related wall or floor to close automatically in the event of a
fire in order to maintain the integrity of the fire-rated separation.
FLUE GAS DESULFURIZATION FAN - An additional induced draft fan placed in series with and downstream of
an induced draft fan to overcome losses of retrofit air pollution control devices.
FORCED DRAFT FAN – A high pressure / high volume fan used to supply primary and secondary combustion
air to a furnace / boiler and its exhaust system. See also: COMBUSTION AIR BLOWER and BLOWER.
GAS RECIRCULATION FAN – An induced draft fan used to redirect boiler gases through the furnace,
superheaters, economizers and to overcome losses in connecting ductwork
GAS TIGHT FAN (DAMPER) – A fan or damper constructed with seals and gaskets at all housing penetrations
to minimize gas leakage through the housing and appurtenances.
GENERAL PURPOSE FAN - A fan suitable for handling clean air that does not exceed a temperature of 80°C
(176°F), or 40°C (104°F) if the motor or the fan bearings are in the airstream.
GOGGLE DAMPER – A damper having a single sliding blade that has a cut-out opening matching the inside
dimension of the duct to which it is attached. The blade slides in tracks and may be positioned to either allow or
restrict the passage of air or gas.
GRAVITY ROOF VENTILATOR - A roof mounted hood or louvered penthouse that uses the difference in air
density or internal building pressurization to vent air into or out of a building.
GUILLOTINE DAMPER - A damper used for isolation purposes and having a blade or blades that are
withdrawn from the duct area when the damper is fully open.
GUILLOTINE DAMPER, DOUBLE-BLADE - A guillotine damper having two parallel blades, the space between
them capable of being pressurized to prevent duct gas leakage across the space between the blades when the
damper is in the closed position.
HAZARDOUS LOCATION FAN (DAMPER) - A fan or damper equipped with electrical equipment having
enclosures tested as suitable to contain internal combustion without ignition of atmospheres external to the
enclosures. The fan or damper itself is of spark resistant construction.
HEAT RECOVERY VENTILATOR – A fan-powered assembly utilizing a heat exchanger or heat recovery
material(s) to transfer energy from exhaust air to replacement air.
HEAVY DUTY DAMPER – A channel frame air control device intended to be fastened between flanged duct
sections and constructed to withstand the elevated temperatures, pressures and contaminated gas flows of
industrial processes.
HIGH PRESSURE FAN – A fan serving to supply air to an industrial process at relatively low airflow and
relatively high pressure.
HOT GAS FAN - A fan constructed of materials capable of operating continuously at elevated temperature
INDUCED DRAFT FAN – A high pressure fan located downstream of a boiler/furnace which draws air or
induces products of combustion from the boiler and discharges them through the exhaust system; any fan which
induces airflow into the fan inlet.
INDUSTRIAL FAN – A fan constructed of materials capable of withstanding the elevated temperatures,
pressures and contaminated gas flows of industrial processes.
INLET VANE (RADIAL) DAMPER – A round damper intended for installation at or in a fan inlet and which
controls and/or pre-swirls air entering the fan impeller. The damper blades are mounted radially and operate in
parallel. The cylindrical (external) type has a sleeve or channel frame that allows mounting directly to the
exterior of a fan inlet. The cone (nested) type has blades supported by the centrifugal fan inlet cone. Either
type may be constructed such that the blades are cantilevered from the outer attachment or are in addition
supported by a center hub that may itself contain the operating mechanism.
IN-LINE FAN – A fan designed to be mounted between duct sections with air inlet and outlet being in an axial
direction.
ISOLATION DAMPER - A low leakage damper intended to regulate or stop the airflow in branches of a duct
system.
ISOLATION DAMPER, MAN-SAFE – A damper containing an isolating system to seal off flue gases so that
men without breathing apparatus or other special equipment may safely enter the isolated section.
JET FAN - A fan mounted at the ceiling of a vehicular tunnel and which induces airflow by entrainment of air
with that streaming from the fan outlet.
KITCHEN FAN – A centrifugal or axial fan located in a kitchen area and which serves to exhaust heat and
moisture.
LOUVER - A device comprising multiple blades which, when mounted in an opening, permits airflow but inhibits
the entrance of water or other elements.
MAKE-UP AIR UNITS - A packaged assembly consisting of a heat source and fan(s) serving to supply fresh,
tempered, replacement air for that exhausted from a building.
MECHANICAL DRAFT FAN – A generic term of classification applying to any of the fans used in a furnace or
boiler system, including Forced Draft, Induced Draft, Primary Air, Overfire Air, Gas Recirculation, Seal Air, and
Flue Gas Desulfurization fans.
MIXED FLOW FAN - A fan in which the airflow through the impeller is intermediate between the centrifugal and
axial flow types, the air moving both axially and radially.
MULTI-STAGE FAN - A fan having two or more impellers that work in series, with guide (stator) vanes between
the impellers.
NON-CLOGGING FAN - A fan having an impeller designed to minimize clogging by virtue of its shape or by use
of special materials. The fan may also incorporate other features to allow use of cleaning sprays and to facilitate
the removal of any resulting materials.
OVERFIRE AIR FAN – A fan that serves to deliver additional (excess) air downstream of the fuel burners in a
boiler for the purpose of improving combustion.
PARTITION FAN - A fan installed in or on a partition and used for moving air from one air space to another.
PASSIVE THROUGH-THE-WALL INLET – A device mounted in an outside wall of a building and which serves
to allow the entrance of ambient air to replace that which has been exhausted.
PEDESTAL FAN – A propeller fan intended for mounting on a stand having a base and column.
PENTHOUSE - A roofed structure incorporating louvers or louver blades in all or part of the walls and usually
located on the roof of a building.
PLENUM FAN - A fan having an un-housed centrifugal impeller that draws air into the impeller through an inlet
located in a barrier wall, and having a driver located on the same side of the barrier as the impeller.
PLUG FAN – A fan having an un-housed impeller arranged such that the system into which it is inserted may
act as a housing, allowing air to be drawn into impeller inlet, and constructed such that the driver is located
outside the duct system
PORTABLE PERSONNEL COOLER – A type of air circulator fan having the impeller and motor enclosed in a
common safety-guarded housing that is mounted on wheels or casters and which serves primarily to provide
cooling for personnel.
POSITIVE PRESSURE VENTILATOR – A portable fan that can be positioned relative to an opening of a
confined space and cause it to be positively pressurized by discharge air velocity. It is principally used by
firefighters to mitigate the effect of smoke and is also used to assist in inflating hot air balloons.
POWER ROOF/WALL VENTILATOR (PRV) - A fan consisting of a centrifugal or axial impeller with an integral
driver in a weather-resistant housing and with a base designed to fit, usually by means of a curb, over a wall or
roof opening.
PRESSURE RELIEF DAMPER – A type of backdraft damper having an adjustable start-to-open pressure and
which is capable of maintaining a relatively constant pressure at various airflows and which closes upon a
decrease in differential pressure.
PROPELLER FAN - An axial fan having an impeller comprised of symmetrical and equally spaced blades
extending radially from a central hub and which is mounted in an orifice plate or ring.
RANGE HOOD – A hood located above a range, stove, grill, or oven and which serves to exhaust hot air, fumes
or moisture directly to a building’s exterior or through filtering media for discharge back into the room.
REVERSIBLE AXIAL-FLOW FAN - An axial fan capable of changing impeller rotation so that air may be moved
in either direction along the fan’s axis of rotation.
SEAL AIR FAN – (1) A fan that serves to pressurize an enclosure around a furnace or boiler to prevent the
escape of burned gases into ambient air. (2) A fan supplying air to a shaft seal chamber as a leakage barrier to
process gas. (3) A fan supplying air to the chamber of an isolation damper to prevent the passage of duct gases
across the enclosed space.
SIGHT-PROOF LOUVER - A louver that cannot be seen through from any direction.
SMOKE (LEAKAGE RATED) DAMPER - A damper intended to: (1) restrict the spread of smoke in HVAC
systems that are designed to be automatically shut down in the event of a fire or (2) control the movement of
smoke when the HVAC system is operational in a building having a smoke management system.
SMOKE MANAGEMENT FAN (SMOKE VENTILATION FAN) – A fan that serves to exhaust smoke and heated
air from a building and which may be certified to remain operable after exposure to a given temperature for a
given duration.
SPARK RESISTANT FAN (or DAMPER) - A fan or damper constructed to reduce the potential for spark
generation when the airstream is potentially explosive.
STATIC VENTILATING DEVICE – A device that passively exhausts air from a building by venting.
TABLE FAN – An air circulator fan intended for use on a desk, table or counter top; it may also be provided with
the means for being mounted to a wall.
TEMPERATURE CONTROL DAMPERS – A pair of dampers intended to be operated together to provide a total
airflow at a given temperature. Two different airflows are regulated by simultaneous damper adjustments.
TUBE AXIAL FAN - An axial flow fan with the impeller in a cylindrical housing and without guide vanes to
straighten the discharged air.
TUBULAR CENTRIFUGAL FAN - A fan having a centrifugal impeller within a cylindrical housing discharging
the air in an axial direction.
UTILITY SET - A centrifugal fan designed as a packaged unit, ready to run, either belt-driven or directly
connected to an electric motor.
VANE AXIAL FAN - A fan comprised of an axial impeller in a cylindrical housing having guide vanes located
upstream or downstream of the impeller, or both.
VENTILATOR - A device that serves to supply air into or exhaust air from a building.
VOLUME CONTROL DAMPER - A device which, when mounted in a duct or opening, is used to vary the
volume of air flowing through the duct or opening and which can be operated manually or mechanically, and can
have one or more blades.
WET GAS FAN - A fan that serves to move air that contains particles of water.
WHOLE-HOUSE FAN – A fan mounted in the ceiling or attic wall of a house and from which it serves to exhaust
air and which incorporates a backdraft damper.
©2003 Air Movement and Control Association International, Inc.
Air Movement and THE AMCA VOCABULARY:
Control Association BSR AMCA
International, Inc. SYMBOLS STANDARD
Arlington Heights, IL 99-0070-01
60004-1893 U.S.A. PAGE 1 OF 11
SYMBOL OR
ABBREVIATION DESCRIPTION SI I-P
A duct width m ft
B duct height m ft
BW band width Hz Hz
SYMBOL OR
ABBREVIATION DESCRIPTION SI I-P
c speed of sound m/s ft/s
De equivalent diameter m ft
De/y ratio of straightener cell size (dia. to thickness of cell) --- ---
Dh hydraulic diameter m ft
d orifice diameter m ft
f frequency Hz Hz
SYMBOL OR
ABBREVIATION DESCRIPTION SI I-P
fc cut-off frequency Hz Hz
SYMBOL OR
ABBREVIATION DESCRIPTION SI I-P
L length m ft
SYMBOL OR
ABBREVIATION DESCRIPTION SI I-P
LwA sound power level of fan (A-weighted; for dB dB
each band or summarized)
SYMBOL OR
ABBREVIATION DESCRIPTION SI I-P
M Mach number --- ---
M chamber dimension m ft
P pressure Pa in. wg
SYMBOL OR
ABBREVIATION DESCRIPTION SI I-P
Pv velocity pressure or fan velocity pressure Pa in. wg
r radius m ft
SYMBOL OR
ABBREVIATION DESCRIPTION SI I-P
rh relative humidity % %
t temperature ºC ºF
td dry-bulb temperature ºC ºF
tw wet-bulb temperature ºC ºF
SYMBOL OR
ABBREVIATION DESCRIPTION SI I-P
Va velocity profile distortion in axial direction % %
(parallel to the fan impeller shaft)
∧
Vt velocity profile distortion in transverse direction % %
(perpendicular to the fan impeller shaft)
Z altitude m ft
SYMBOL OR
ABBREVIATION DESCRIPTION SI I-P
γ ratio of specific heats --- ---
η motor efficiency % %
λ wavelength m ft
SUBSCRIPT
a atmospheric conditions
b barometric pressure
d dry-bulb temperature
g static pressure
r reading
w wet-bulb depression
SYMBOL OR
ABBREVIATION DESCRIPTION SI I-P
0 plane 0 (general test area)
Percentage
Basic Series Theoretical values differences
SERIAL between
NUMBER basic series
Base 10 and
Mantissa Calculated calculated
R5 R 10 R 20 R 40
of values values (%)
logarithms
Percentage
Basic Series Theoretical values differences
SERIAL between
NUMBER basic series
Base 10 and
Mantissa Calculated calculated
R5 R 10 R 20 R 40
of values values (%)
logarithms
U.S.
AMCA Standard (1) Conversion (4)
Customary
Metric (SI) Unit Factor
Units
cubic meter per second
VOLUME FLOW cfm 0.00047195
m3/s
pascal
PRESSURE in. wg 248.36
Pa or N/m2
watt
POWER hp 745.70
W or J/s
newton meter
TORQUE lbf-in 0.11298
NCm
millimeter
DIMENSIONS in. 25.400
mm
pascal
STRESS lbf/in2 6894.8
Pa or N/m2
kelvin
TEMPERATURE (3) °F (°F + 459.67)/1.8
Notes:
1) The choice of the appropriate multiple or sub multiple of an SI unit is governed by convenience. The
multiple chosen for a particular application should be the one which will lead to numerical values
within a practical range (i.e. kilopascal for pressure, kilowatts for power, megapascal for stress, and
liters/second for volume flow.)
2) The second is the SI base unit of time. Although outside SI, the minute has been recognized by
CIPM as necessary to retain for use because of its practical importance.
3) The kelvin is the SI base unit of thermodynamic temperature and is preferred for most scientific and
technological purposes. The degree celcius (°C) is acceptable for practical applications.
4) Multiply “Customary” unit by this factor to obtain AMCA Standard except for kelvin temperature.
©1976 Air Movement and Control Association International, Inc.
Air Movement and
Control Association BSR AMCA
International, Inc. CHARTS & TABLES STANDARD
Arlington Heights, IL 99-0200-00
60004-1893 U.S.A. PAGE 1 OF 8
Z t p D : v c
Altitude Temperature Atmospheric Air Dynamic Kinematic Speed of
Pressure Density Viscosity Viscosity Sound
Z t p D : v c
Altitude Temperature Atmospheric Air Dynamic Kinematic Speed of
Pressure Density Viscosity Viscosity Sound
Fan applications may involve the handling of potentially explosive or flammable particles, fumes, or vapors.
Such applications require careful consideration of all system components to insure the safe handling of such
gas streams. This AMCA Standard deals only with the fan unit installed in that system. The Standard
contains guidelines which are to be used by both the manufacturer and user as a means of establishing
general methods of construction. The exact method of construction and choice of alloys is the responsibility
of the manufacturer; however, the customer must accept both the type and design with full recognition of the
potential hazard and the degree of protection required.
TYPE CONSTRUCTION
A All parts of the fan in contact with the air or gas being handled shall be made of nonferrous
material. Steps must also be taken to assure that the impeller, bearings, and shaft are
adequately attached and/or restrained to prevent a lateral or axial shift in these components.
B The fan shall have a nonferrous impeller and nonferrous ring about the opening through which
the shaft passes. Ferrous hubs, shafts, and hardware are allowed provided construction is such
that a shift of impeller or shaft will not permit two ferrous parts of the fan to rub or strike. Steps
must also be taken to assure that the impeller, bearings, damper blades and shaft are adequately
attached and/or restrained to prevent a lateral or axial shift in these components.
C The fan shall be so constructed that a shift of the impeller or shaft will not permit two ferrous parts
of the fan to rub or strike.
NOTES:
1. No bearings, drive components or electrical devices shall be placed in the air or gas stream unless they
are constructed or enclosed in such a manner that failure of that component cannot ignite the surrounding
gas stream.
3. For this Standard, nonferrous material shall be any material with less than 5% iron or any other material
with demonstrated ability to be spark resistant.
4. The use of aluminum or aluminum alloys in the presence of steel which has been allowed to rust requires
special consideration. Research by the U.S. Bureau of Mines and others has shown that aluminum
impellers rubbing on rusty steel may cause high intensity sparking.
The use of the above Standard in no way implies a guarantee of safety for any level of spark resistance.
“Spark resistant construction also does not protect against ignition of explosive gases caused by catastrophic
failure or from any airstream material that may be present in a system.”
This Standard applies to ferrous and nonferrous metals. The potential questions which may be
associated with fans constructed of FRP, PVC, or any other plastic compound were not addressed.
©1986 Air Movement and Control Association International, Inc.
Air Movement and Adopted
Control Association
OPERATING LIMITS FOR AMCA 11-30-66
International, Inc. CENTRAL-STATION UNITS STANDARD
Arlington Heights, IL 99-1401-66
60004-1893 U.S.A. PAGE 1 OF 1 Reviewed
1983
ISO 13349
AMCA Drive Fan Alternative Fan
Drive Description
Arrangement Configuration Configuration
Arrangement
1 SWSI 1 or For belt or direct drive.
12 (Arr. 1 with
sub-base) Impeller overhung on shaft, two
bearings mounted on pedestal
base.
ISO 13349
AMCA Drive Fan Alternative Fan
Drive Description
Arrangement Configuration Configuration
Arrangement
7 SWSI 7 For coupling drive.
Alternative: Bearings
mounted on
independent pedestals
with or without inlet
box.
7 DWDI 17 For coupling drive.
(Arr. 6 with base
for motor) Generally the same as
Arr. 3 with base for the
prime mover.
Alternative: Bearings
mounted on
independent pedestals
with or without inlet
box.
8 SWSI 8 For direct drive.
Alternative: Bearings
mounted on
independent pedestals
with or without inlet
box.
9 SWSI 9 For belt drive.
Impeller overhung on
shaft, two bearings
mounted on pedestal
base.
Notes:
1. Position of inlet box and air entry to inlet box is determined from the drive side as defined below:
a. On single inlet fans: The drive side is that side which is opposite of the fan inlet.
b. On double inlet fans:
1) With a single driver: That side with the driver is considered as the drive side.
2) With multiple drivers: That side with the higher total power is considered as the drive side. If
the total power on each side is equal, then that side which has the fixed (non-expansion)
bearing is considered as the drive side.
2. Position of inlet box is determined in accordance with diagrams. Angle of air entry to box is referred to the
top vertical axis of fan in degrees as measured in the direction of fan rotation. Angle of air entry to box
may be any intermediate angle as required.
3. Positions 135º to 225º in some cases may interfere with floor structure.
Notes:
1. Direction of rotation and angular reference is determined from the drive side as defined below:
a. On single inlet fans: The drive side is that side opposite the fan inlet.
1) With a single driver: That side with the drive is considered the drive side.
2) With multiple drivers: That side with the higher total power is considered the drive side. If
the total power on each side is equal, then the side that has the fixed (non-expansion)
bearing is considered the drive side.
3. A fan inverted for ceiling suspension or rotated for side wall mounting will have its direction of
rotation and angle of discharge determined when fan is located as if floor mounted.
4. This standard is in harmony with ISO 13349. In ISO 13349, CCW fans are referred to as LG, i.e.,
Left or Gauche, while CW fans are referred to as RD, i.e, Right or Droit-handed rotation.
360 0
360 0
315 0 45 0
45 0 315 0
270 0 270 0
900 900
180 0 180 0
Location of motor is determined by facing the drive side of the fan and designating the
motor position by letters W, X, Y or Z as the case may be.
19
16
15
14
13½" @ 3780
STATIC PRESSURE (SP) inches of water
mi
nim
Typical Class II
um
11 Fan is required to be physically capable
characteristic curve. of performing over this range.
pe
rfo
rm
10
an
ce
9 CL
AS
8½" @ 3000 CLASS III SI
SELECTION ZONE
II
8
m
in
im
um
7
6¾" @ 5260
pe
rfo
rm
6
an
ce
CLASS II
CL
S
in
II
4¼" @ 4175
mi
4
um LA
C
pe SS
rfo I
CLASS I
2½" @ 3200
ce
SELECTION ZONE
2
16
15
14
13½" @ 3970
STATIC PRESSURE (SP) inches of water
13
mi
nim
11
Fan is required to be physically capable
um
of performing over this range.
pe
10
rfo
rm
an
ce
9
CL
8½" @ 3150
AS
8 CLASS III
SI
m
SELECTION ZONE
in
II
im
um
7
pe
rfo
6¾" @ 5520
rm
6
an
ce
CL
SELECTION ZONE
m
S
in
II
4¼" @ 4380
im CL
4
um A
pe S I
rfo
S
2½" @ 3360
ce
CLASS I
2 SELECTION ZONE
19
To be designated as meeting the requirements of a specified Class,
18 as defined in this Standard, a fan must be physically capable of
operating safely at every point of rating on or below the "minimum
performance" limit for the Class.
17
16
15
14
STATIC PRESSURE (SP) inches of water
13
12
11 10¾" @ 4600
10
Ratings may be published
Fan is required to be physically
m
in this UPPER RANGE.
in
capable if performing
im
9
um
over this range.
pe
rfo
8
rm
an
ce
CLASS III
CL
7 SELECTION ZONE
6¾" @ 3640
AS
S
m
III
in
im
6
um
5½" @ 6100
pe
rfo
rm
5
an
ce
CL
4 m SELECTION ZONE
S
in
II
im 3½" @ 4900
um
CL pe
3 AS rfo
S rm
I an
CLASS I ce Ratings may be published
2 SELECTION ZONE 2" @ 3700 in this LOWER RANGE.
19
To be designated as meeting the requirements of a specified Class,
18 as defined in this Standard, a fan must be physically capable of
operating safely at every point of rating on or below the "minimum
performance" limit for that Class.
17
16
15
14
STATIC PRESSURE (SP) inches of water
13
12
11 10¾" @ 4800
Ratings may be published
10
in this UPPER RANGE.
m
Fan is required to be physically
in
capable of performing
im
um
9 over this range.
pe
rfo
rm
8
an
ce
CL
7 6¾" @ 3800 CLASS III
AS
m SELECTION ZONE
in
S
im
III
6 um
pe 5½" @ 6400
rfo
rm
5 an
ce
CL
4" @ 2900 CLASS II AS
4 m S
in SELECTION ZONE II
im
um
3½" @ 5150
CL pe
3 AS rfo
S rm Ratings may be published
I an
CLASS I ce in this LOWER RANGE.
2 SELECTION ZONE 2" @ 3900
19
To be designated as meeting the requirements of a specified Class,
18 as defined in this Standard, a fan must be physically capable of
operating safely at every point of rating on or below the "minimum
17
performance" limit for that Class.
16
15
14
13½" @ 2050
STATIC PRESSURE (SP) inches of water
13
12
Ratings may be published
mi
in this UPPER RANGE. Fan is required to be physically
nim
11 capable of performing
um
over this range.
pe
10
rfo
rm
an
ce
9
CL
8½" @ 1630 CLASS III
AS
SELECTION ZONE
S
8
III
m
in
im
um
7
6¾" @ 2950
pe
rfo
rm
6
an
ce
CL
5" @ 1250
AS
5 CLASS II
m
S
in SELECTION ZONE
II
im
um 4¼" @ 2350
4
CL pe
AS rfo
S rm Ratings may be published
3 I an
CLASS I ce in this LOWER RANGE.
SELECTION ZONE 2½" @ 1800
2
Adopted
Air Movement and AMCA 10-20-69
Control Association OPERATING LIMITS FOR STANDARD
International, Inc. 99-2408-69
Arlington Heights, IL
CENTRIFUGAL FANS – Tubular. PAGE 5 OF 5 Reviewed
60004-1893 U.S.A. Supersedes 2408-69 1983
Air Movement and DRIVE ARRANGEMENTS FOR
Control Association ANSI/AMCA
International, Inc. TUBULAR CENTRIFUGAL FANS 99-2410-03
Arlington Heights, IL An American National Standard PAGE 1 OF 1
60004-1893 U.S.A. Approved by ANSI on May 20, 2003
ARRANGEMENT 1
Motor For belt drive. Impeller overhung on
Left
a shaft supported by bearings
mounted within casing. Motor
mounted independent of casing.
Horizontal discharge.
ARRANGEMENT 4
For direct drive. Impeller overhung
on motor shaft. Motor supported
within casing. For horizontal or
vertical discharge. Duct mounting
shown.
360 ARRANGEMENT 9
315 45 For belt drive. Impeller overhung on
a shaft supported by bearings
mounted within casing. Designed
270 90 for mounting of motor on outside of
casing in one of the standard
locations shown. For horizontal and
225 135
vertical discharge. Duct mounting
180 shown.
Motor Shown in Position 360
View Facing Outlet
Another method of mounting vertical fans is shown in the view on the right.
Specify fan to be furnished with ceiling-mounting brackets, floor mounting
Floor-Mounting Brackets
brackets, or both.
m2 mm inches ft2
0.189 *355
0.218 381 15.00 2.33
0.240 *400
0.375 *500
0.387 508 20.00 4.14
0.470 *560
Notes:
0.479 565 22.25 5.12 1. Precise outlet area=
0.581 622 24.50 6.21
0.595 *630 SI: OA(m2) = 1.5x10-06 (D(mm))2
m2 mm inches ft2
2.344 *1250
2.848 1378 54.25 30.46
2.940 *1400
MOTOR I.D.
FAN SIZE
CUTAWAY VIEW
(Motor Support Not Shown)
Fan Size
Outlet Area
(Casing ID) 2
m
mm
200 0.031
224 0.039
250 0.049
280 0.062
315 0.078
355 0.099
400 0.126
450 0.159
500 0.196
560 0.246 Notes:
630 0.312
710 0.396
1. This standard is not limited
800 0.503 to the range of sizes listed.
900 0.636 Smaller and larger fan sizes
1000 0.785 conforming to the R20 series,
1120 0.985 with the 1000mm size as a
1250 1.23 base, may be included. See
1400 1.54 AMCA 99-0098, Basic Series of
1600 2.01 Preferred Numbers.
1800 2.54
2000 3.14
2240 3.94 2. Fan size is based upon
2500 4.91 casing ID; impeller diameter is
2800 6.16 slightly smaller.
3150 7.79
3550 9.90
ISO 13349
AMCA Drive Fan Alternative Fan
Drive Description
Arrangement Configuration Configuration
Arrangement
For belt or direct drive.
1 1
12 (Arr. 1 with Impeller overhung on shaft,
sub-base) two bearings mounted either
upstream or downstream of
the impeller.