PROJECT NAME Saudi Diyar Consultants

Testing and Commissioning


FIRE FIGHTING PUMPS

Project : ALTITUDE: Ft
Date : AMBIANT TEMPERATURE: °F

Main Electrical Fire Pump


Serial Number :
Model Number : Notes:
Type : VERTICAL SPLIT CASE
Voltage : / /
Amperage : / /
Design Actual
Suction Pressure, psi :
Discharge pressure, psi :
Pump Efficiency:
Head ,ft :
P1
Water flow, gpm :
BHP #DIV/0! #DIV/0!
JOCKEY Fire Pump
Serial Number :
Model Number : Notes:
Type : VERTICAL MULTI STAGE
Voltage : / /
Amperage : / /
Design Actual
Suction Pressure, psi :
Discharge pressure, psi :
Pump Efficiency:
Head ,ft :
P2
Water flow, gpm :
BHP #DIV/0! #DIV/0!
Main Diesel Fire Pump
Serial Number :
Model Number : Notes:
Type : VERTICAL SPLIT CASE
Design Actual
Engine RPM
Pump RPM
Suction Pressure, psi :
Discharge pressure, psi :
Pump Efficiency:
Head ,ft :
P3
Water flow, gpm :
BHP #DIV/0! #DIV/0!
DERATING #DIV/0! #DIV/0!

SDC

11/14/2019 General 1
Khorais Road Project - Riyadh
Saudi Diyar Consultants

b- Check List :

1- MAIN FIRE PUMP


TYPE: HORIZONTAL SPLIT CASE 1500 GPM @ 346.5 Ft
PUMP BREAK HORSEPOWER 175 Hp
SUCTION SIZE 8 in
DISCHARGE SIZE 8 in
THE FOLLOWING FITTINGS FOR THE PUMP SHALL BE PROVIDED BY THE PUMP
MANUFACTURER:
A- AUTOMATIC AIR RELEASE FOUND
B- CASING RELIEF VALVE AT PUMP DISCHARGE FOUND
C- INSTRUMENTATION (Gauges, Tachometer, Thermometer, etc..) FOUND
THE FOLLOWING FITTINGS SHALL BE PROVIDED:
A- ECCENTRIC TAPERED REDUCER AT SUCTION INLET FOUND
B- HOSE VALVE MANIFOLD WITH HOSE VALVES NOT APPLICABLE
NUMBER AND SIZE OF HOSE VALVES 6 - 2.5 in NOT APPLICABLE
HOSE VALVE MANIFOLD SIZE 8 in NOT APPLICABLE
C- FLOW MEASURING DEVICES (175% OF RATED CAPACITY) FOUND
FLOW METER SIZE 8 in FOUND
D- DISCHARGE CONE FOUND
E- RELIEF VALVE (FOR DIESEL SYSTEM) FOUND
RELIEF VALVE SIZE MUST BE 6 in FOUND
RELIEF VALVE DISCHARGE 8 in FOUND
CHECK AND GATE VALVES INSTALLATION ON DISCHARGE SIDE FOUND
DIESEL FUEL TANK
VOLUME MUST BE 193 Gallons or 732 L
ACTUAL VOLUME AS PER SITE Gallons or L
DUAL BATTERIES FOUND
EXHAUST CONNECTION AND SILENCER FOUND
COOLING WATER LINE (from pumps' discharge pipe to the engine
heat exchanger cooling water line) FOUND
ENGINE JACKET WATER HEATER (engine coolant temperature
not less than 120°F) FOUND
GOVERNOR (capable of regulating the engine speed within 10% of the
rated speed across the entire flow range of the pump curve) FOUND
OVERSPEED SHUT DOWN DEVICE (must active if the engine
operating speed is 20% higher than the rated speed of engine) FOUND
MANUAL CRANKING DEVICE
WATER TO COOLANT HEAT EXCHANGER FOUND
TWO STARTERS (diesel engine must be capable of being started using
one of the two provided batteries FOUND

Notes:

11/14/2019
Checklist-fire pump 2
04:57:56
Khorais Road Project - Riyadh
Saudi Diyar Consultants

11/14/2019
Checklist-fire pump 3
04:57:56
Khorais Road Project - Riyadh
Saudi Diyar Consultants

b- Check List :

2- FIRE PUMPS CONTROLLER


TYPE: HORIZONTAL SPLIT CASE 1500 GPM @ 288.75 Ft
PUMP BREAK HORSEPOWER 146 Hp
SUCTION SIZE 8 in
DISCHARGE SIZE 8 in

A- Must be supplied with at least one reliable source of power FOUND


B- All current carrying components of an electric fire pump controller
must be located 12 inches above the floor, and housed in NEMA2
or higher enclosure. FOUND
C- STARTING METHOD STAR DELTA (Y - Δ)
D- SURGE ARRESTOR: is required for each phase.
This device protects the motor from high voltage surges such as
those caused by lightening. FOUND
E- ISOLATING SWITCH: to ensure power is disconnected from the
controller for servicing. The switch must be interlocked with the
circuit breaker so that the switch cannot be operated while the
circuit breaker is closed. FOUND
F- MOTOR PROTECTION CIRCUIT BREAKER: an externally
operable circuit breaker required for protection of the motor from
instantaneous operation of the fire pump when the isolating switch FOUND
is engaged.
G- LOCKED ROTOR OVER CURRENT PROTECTION: must be
set to trip between 8 and 20 seconds of exposure to a locked rotor
condition (600% the full load amps of the motor) FOUND
H- MOTOR CONTACTORS: rated for the motor horse power FOUND
I- POWER AVAILABLE VISIBLE INDICATOR
J- PHASE REVERSAL VISIBLE INDICATOR: should the phase of the
incoming power reverse, the controller must be capable of indicating
this condition using a pilot lamp on the controller enclosure and
energize alarm contact. FOUND
K- MANUAL START HANDLE: operator to mechanically engage the fire FOUND
pump should the controller failed to automatically start the pump.
L- TESTING MEANS: the controller must have provisions so that FOUND
the fire pump canbe tested.

Notes:

11/14/2019
Electrical&Control 4
04:57:56
Khorais Road Project - Riyadh
Saudi Diyar Consultants

11/14/2019
Electrical&Control 5
04:57:56
Khorais Road Project - Riyadh
Saudi Diyar Consultants

i- Fire Fighting Pumps Readings :

DESIGN Main Jockey


VOLTAGE Diesel
AMPS.
Suction, psi 0
Discharge, psi 150
Head, Ft 346.5 0 0 0
GPM 1500

Main
VOLTAGE Diesel
AMPS.
Suction, psi
Discharge, psi
Head, Ft 0 0
GPM 2250
Head must not be less than 65% of the original head

NOTES :

Name Signature Date

11/14/2019
Readings 6