CHECK LIST PREVENTIVE MAINTENANCE

MECHANICAL ELECTRICAL Base Service

Protelindo Site ID : JAW-CJV-0004-D-P

Protlindo Site Name : TEMBALANG (SEMARANG)

Date : 06/03/2012

Time : 10:18:00 AM WIB / WITA / WIT

GROUNDING

Grounding Measurement : ………………………. Ohm ( < 1 Ohm )

Grounding Well : ………………………. Ohm ( < 1 Ohm )

Tower Leg : 0,33 Ohm ( < 1 Ohm )

Fence : 0,36 Ohm ( < 1 Ohm )

Genset Tank : N/A Ohm ( < 1 Ohm )

Grounding Status :

Lightening Rod : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), …… ...

BAR grounding tower : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ………

BAR grounding well : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ………

Down conductor Cable : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ………

Bolt Connection : OK NOK Remark : ( uncompleted condition / stolen / broken / worse connection ), ………

TOWER

Tower Type : SST Monopole Triangle Pole Mini Tower

Painting Condition : OK NOK Remark : ( tower loosen paint 70 % ), GALVANIS

Construction Condition : OK NOK Remark : ( paving down/ tower leg cracked ), ………….

Tower Cleaning : OK NOK Remark : ( cleaning from spider nest / bee / etc ), ………….

Tower Lamp / OBL : OK NOK N/A Remark : ( broken, cracked, unshielded), ………….

Photo Sensor : OK NOK N/A Remark : ( broken, cracked, unshielded), ………….

LIGHTING

Tower Lamp (OBL) Amount : 4 Unit

Yard Lamp Amount (Mercury & TL) : 1 Unit

Tower Lamp (OBL) Condition : OK NOK N/A Remark : ( broken, cracked, unshielded), ………….

Yard Lamp Condition : OK NOK N/A Remark : ( broken, cracked, unshielded), ………….

Site Photo Sensor : OK NOK N/A Remark : ( sensor respon checking ), ………….

Yard Lamp Shield : OK NOK N/A Remark : ( lamp shield checking broken / no ), …….

FENCE

Fence Condition : OK NOK N/A Remark : ( collapsed, broken ), ………….

Site Cleaning : OK NOK Remark : ( cleaning for grass / garbage )……………………

Flume Cleaning : OK NOK Remark : ……………………

Paving Block or Gravel : OK NOK Remark : ……………………

Barbared Wire : OK NOK Remark : ……………………

Fence Door (Swing/Sliding) : OK NOK Remark : ……………………

ENVA STATUS

ENVA Check Respons

Lightening Alarm : OK NOK N/A Remark : ( uninstalled, undetected ), ………….

Obstruction Light Failure : OK NOK N/A Remark : ( uninstalled, undetected ), ………….

Grounding System : OK NOK N/A Remark : ( uninstalled, undetected ), ………….

Fence Break : OK NOK N/A Remark : ( uninstalled, undetected ), ………….

PT NOKIA SIEMENS NETWORK

INSPECTION BY

( HARI )
CHECK LIST PREVENTIVE MAINTENANCE
MECHANICAL ELECTRICAL Tenant

Protelindo Site ID : JAW-CJV-0004-D-P Date : 06/03/2012

Protlindo Site Name : TEMBALANG (SEMARANG) Time : 10:18:00 AM WIB / WITA / WIT

Operator : FLEXI
AIR CONDITIONER

Equipment Type : Indoor Outdoor AC Amount : 2 unit


AC Mark : Daikin National Others / PANASONIC 1,5 PK
Measurement Remark AC # 1 AC # 2 AC # 3 AC # 4
Broken AC AC Status YES NO YES NO YES NO YES NO
Power PK 1,5 1,5
Pressure Psi 70 70
According with data signed at
Current Max
AC Outdoor
Current Measurement Ampere 6,72 8,28
AC Indoor Condition Leak / Not Leak OK NOK OK NOK OK NOK OK NOK
Pipe Condition Leak / Not Leak OK NOK OK NOK OK NOK OK NOK
Auto Restart Operation OK NOK N/A OK NOK N/A OK NOK N/A OK NOK N/A
Switch Contactor test switch OK NOK OK NOK OK NOK OK NOK
AC Temperature Setting < 24 oC OK NOK OK NOK OK NOK OK NOK
Room Temperature : 20,7
EXHAUST FAN

Exhaust Fan Condition : OK NOK Exhaust Fan Cleaning : OK NOK


SHELTER

Shelter Roof : OK NOK N/A Remark : ( leak, broken ), ………….


Dinding Shelter : OK NOK N/A Remark : ( cracked, leak, broken ), ………….
Fence Condition : OK NOK N/A Remark : ( collapsed, broken ), ………….
Room Cleaning : OK NOK Leak Remark : ……………………
Roof Cleaning : OK NOK Leak Remark : ……………………
Benzoic Spreading : OK NOK Remark : ( cleaning for grass / garbage )……………………
Door Hinge Lubrication : OK NOK Remark : ……………………
Shelter Foundation : OK NOK Remark : ……………………
Alarm System

Heat Detector : OK NOK N/A Remark : ( uninstalled, undetected ), ………….


Smoke Detector : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Ring Bell : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
GROUNDING

Grounding Status : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), …… ...

Control Box : 0,39 Ohm ( < 1 Ohm )

Measurement External Grounding Bar : 0,37 Ohm ( < 1 Ohm )

Internal Grounding Bar : 0,53 Ohm ( < 1 Ohm )

OUTDOOR TYPE
Base Frame Condition : OK NOK N/A Remark : ...............................
Dynabolt Condition : OK NOK N/A Remark : ...............................
Base Frame Foundation : OK NOK N/A Remark : ...............................
KWH ELECTRICAL MEASUREMENT
Phase Voltage R - N (200V - 240V) : 217 V 220 V +/- 5% max 10 V Phase Voltage S - T (350V - 400V) : 371 V 380 V +/- 5% max 10 V
Phase Voltage S - N (200V - 240V) : 216 V 220 V +/- 5% max 10 V Phase Voltage T - R (350V - 400V) : 373 V 380 V +/- 5% max 10 V
Phase Voltage T - N (200V - 240V) : 211 V 220 V +/- 5% max 10 V Phase Voltage G - N (< 5 V) : 0 V
Phase Voltage R - S (350V - 400V) : 378 V 380 V +/- 5% max 10 V KWH Meter Record : 35037
ELECTRICAL VISUAL CHECK
AC-PDB : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ………
KWH Box Including Pole KWH : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection / pole Condition )
COS : OK NOK N/A Remark : ( clean, neat, broken )
PLN VISUAL CHECK
PLN Power Supplied : 23 kVA
MCB input :
MCB Condition : OK NOK NA
1 Phase : ……………… A ……………… pcs
3 Phases : 35 A 3 pcs
COS : 40 A
PLN ID : 52-3040397908
Seal
KWH Record : OK NOK NA ( Good Sealed ), ………..……
Terminal / OKA : OK NOK NA ( Good Sealed ), ………..……
MCB : OK NOK NA ( Good Sealed ), ………..……
PLN FUNCTION TEST
MCB in the KWH 'ON' Position
A. Current flows to the MCCB for Devices : OK NOK NA ( Current Measurement result = Visual check ), ………..……
B. R, S & T Indicator Lamps are lit : OK NOK NA
MCB for Devices to 'ON' Position : OK NOK NA ( MCB In position ), ………..……
KWH Meter Spin Normally : OK NOK NA ( Spin Normally ), ………..……

PT NOKIA SIEMENS NETWORK

INSPECTION BY

( HARI )
CHECK LIST PREVENTIVE MAINTENANCE
MECHANICAL ELECTRICAL Tenant

Protelindo Site ID : JAW-CJV-0004-D-P Date : 06/03/2012

Protlindo Site Name : TEMBALANG (SEMARANG) Time : 10:18:00 AM WIB / WITA / WIT

Operator : ISAT
AIR CONDITIONER

Equipment Type : Indoor Outdoor AC Amount : …………. unit


AC Mark : Daikin National Others / ……………..
Measurement Remark AC # 1 AC # 2 AC # 3 AC # 4
Broken AC AC Status YES NO YES NO YES NO YES NO
Power PK

Pressure Psi
According with data signed at
Current Max
AC Outdoor
Current Measurement Ampere

AC Indoor Condition Leak / Not Leak OK NOK OK NOK OK NOK OK NOK


Pipe Condition Leak / Not Leak OK NOK OK NOK OK NOK OK NOK
Auto Restart Operation OK NOK N/A OK NOK N/A OK NOK N/A OK NOK N/A
Switch Contactor test switch OK NOK OK NOK OK NOK OK NOK
AC Temperature Setting < 24 oC OK NOK OK NOK OK NOK OK NOK
Room Temperature :
EXHAUST FAN

Exhaust Fan Condition : OK NOK Exhaust Fan Cleaning : OK NOK


SHELTER

Shelter Roof : OK NOK N/A Remark : ( leak, broken ), ………….


Dinding Shelter : OK NOK N/A Remark : ( cracked, leak, broken ), ………….
Fence Condition : OK NOK N/A Remark : ( collapsed, broken ), ………….
Room Cleaning : OK NOK Leak Remark : ……………………
Roof Cleaning : OK NOK Leak Remark : ……………………
Benzoic Spreading : OK NOK Remark : ( cleaning for grass / garbage )……………………
Door Hinge Lubrication : OK NOK Remark : ……………………
Shelter Foundation : OK NOK Remark : ……………………
Alarm System

Heat Detector : OK NOK N/A Remark : ( uninstalled, undetected ), ………….


Smoke Detector : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Ring Bell : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
GROUNDING

Grounding Status : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), …… ...

Control Box : 0,37 Ohm ( < 1 Ohm )

Measurement External Grounding Bar : - Ohm ( < 1 Ohm )

Internal Grounding Bar : N/A Ohm ( < 1 Ohm )

OUTDOOR TYPE
Base Frame Condition : OK NOK N/A Remark : ...............................
Dynabolt Condition : OK NOK N/A Remark : ...............................
Base Frame Foundation : OK NOK N/A Remark : ...............................
KWH ELECTRICAL MEASUREMENT
Phase Voltage R - N (200V - 240V) : 212 V 220 V +/- 5% max 10 V Phase Voltage S - T (350V - 400V) : 0 V 380 V +/- 5% max 10 V
Phase Voltage S - N (200V - 240V) : 212 V 220 V +/- 5% max 10 V Phase Voltage T - R (350V - 400V) : 0 V 380 V +/- 5% max 10 V
Phase Voltage T - N (200V - 240V) : 212 V 220 V +/- 5% max 10 V Phase Voltage G - N (< 5 V) : 0 V
Phase Voltage R - S (350V - 400V) : 0 V 380 V +/- 5% max 10 V KWH Meter Record : 2472
ELECTRICAL VISUAL CHECK
AC-PDB : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ………
KWH Box Including Pole KWH : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection / pole Condition )
COS : OK NOK N/A Remark : ( clean, neat, broken )
PLN VISUAL CHECK
PLN Power Supplied : 7,7 kVA
MCB input :
MCB Condition : OK NOK NA
1 Phase : 35 A 1 pcs
3 Phases : …………… A ………….. pcs
COS : 40 A
PLN ID : N/A
Seal
KWH Record : OK NOK NA ( Good Sealed ), ………..……
Terminal / OKA : OK NOK NA ( Good Sealed ), ………..……
MCB : OK NOK NA ( Good Sealed ), ………..……
PLN FUNCTION TEST
MCB in the KWH 'ON' Position
A. Current flows to the MCCB for Devices : OK NOK NA ( Current Measurement result = Visual check ), ………..……
B. R, S & T Indicator Lamps are lit : OK NOK NA
MCB for Devices to 'ON' Position : OK NOK NA ( MCB In position ), ………..……
KWH Meter Spin Normally : OK NOK NA ( Spin Normally ), ………..……

PT NOKIA SIEMENS NETWORK

INSPECTION BY

( HARI )
CHECK LIST PREVENTIVE MAINTENANCE
MECHANICAL ELECTRICAL Tenant

Protelindo Site ID : JAW-CJV-0004-D-P Date : 06/03/2012

Protlindo Site Name : TEMBALANG (SEMARANG) Time : 10:18:00 AM WIB / WITA / WIT

Operator : TSEL
AIR CONDITIONER

Equipment Type : Indoor Outdoor AC Amount : …………. unit


AC Mark : Daikin National Others / ……………..
Measurement Remark AC # 1 AC # 2 AC # 3 AC # 4
Broken AC AC Status YES NO YES NO YES NO YES NO
Power PK

Pressure Psi
According with data signed at
Current Max
AC Outdoor
Current Measurement Ampere

AC Indoor Condition Leak / Not Leak OK NOK OK NOK OK NOK OK NOK


Pipe Condition Leak / Not Leak OK NOK OK NOK OK NOK OK NOK
Auto Restart Operation OK NOK N/A OK NOK N/A OK NOK N/A OK NOK N/A
Switch Contactor test switch OK NOK OK NOK OK NOK OK NOK
AC Temperature Setting < 24 oC OK NOK OK NOK OK NOK OK NOK
Room Temperature :
EXHAUST FAN

Exhaust Fan Condition : OK NOK Exhaust Fan Cleaning : OK NOK


SHELTER

Shelter Roof : OK NOK N/A Remark : ( leak, broken ), ………….


Dinding Shelter : OK NOK N/A Remark : ( cracked, leak, broken ), ………….
Fence Condition : OK NOK N/A Remark : ( collapsed, broken ), ………….
Room Cleaning : OK NOK Leak Remark : ……………………
Roof Cleaning : OK NOK Leak Remark : ……………………
Benzoic Spreading : OK NOK Remark : ( cleaning for grass / garbage )……………………
Door Hinge Lubrication : OK NOK Remark : ……………………
Shelter Foundation : OK NOK Remark : ……………………
Alarm System

Heat Detector : OK NOK N/A Remark : ( uninstalled, undetected ), ………….


Smoke Detector : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Ring Bell : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
GROUNDING

Grounding Status : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), …… ...

Control Box : 0,33 Ohm ( < 1 Ohm )

Measurement External Grounding Bar : 0,42 Ohm ( < 1 Ohm )

Internal Grounding Bar : N/A Ohm ( < 1 Ohm )

OUTDOOR TYPE
Base Frame Condition : OK NOK N/A Remark : ...............................
Dynabolt Condition : OK NOK N/A Remark : ...............................
Base Frame Foundation : OK NOK N/A Remark : ...............................
KWH ELECTRICAL MEASUREMENT
Phase Voltage R - N (200V - 240V) : 212 V 220 V +/- 5% max 10 V Phase Voltage S - T (350V - 400V) : 0 V 380 V +/- 5% max 10 V
Phase Voltage S - N (200V - 240V) : 213 V 220 V +/- 5% max 10 V Phase Voltage T - R (350V - 400V) : 0 V 380 V +/- 5% max 10 V
Phase Voltage T - N (200V - 240V) : 212 V 220 V +/- 5% max 10 V Phase Voltage G - N (< 5 V) : 0 V
Phase Voltage R - S (350V - 400V) : 0 V 380 V +/- 5% max 10 V KWH Meter Record : 1311
ELECTRICAL VISUAL CHECK
AC-PDB : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ………
KWH Box Including Pole KWH : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection / pole Condition )
COS : OK NOK N/A Remark : ( clean, neat, broken )
PLN VISUAL CHECK
PLN Power Supplied : 7,7 kVA
MCB input :
MCB Condition : OK NOK NA
1 Phase : 16 A 2 pcs
3 Phases : …………… A …………… pcs
COS : 40 A
PLN ID : N/A
Seal
KWH Record : OK NOK NA ( Good Sealed ), ………..……
Terminal / OKA : OK NOK NA ( Good Sealed ), ………..……
MCB : OK NOK NA ( Good Sealed ), ………..……
PLN FUNCTION TEST
MCB in the KWH 'ON' Position
A. Current flows to the MCCB for Devices : OK NOK NA ( Current Measurement result = Visual check ), ………..……
B. R, S & T Indicator Lamps are lit : OK NOK NA
MCB for Devices to 'ON' Position : OK NOK NA ( MCB In position ), ………..……
KWH Meter Spin Normally : OK NOK NA ( Spin Normally ), ………..……

PT NOKIA SIEMENS NETWORK

INSPECTION BY

( HARI )
PREVENTIVE MAINTENANCE
Base Service
PHOTO REPORT

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Contractor : NOKIA SIEMENS NETWORK

Foto A - 1 Foto A - 2
Tampak halaman site sebelum dibersihkan Tampak halaman site setelah dibersihkan

Foto A - 3 Foto A - 4
Tampak tower bagian atas (tampak mounting & lampu halaman) Tampak tower bagian bawah (tampak pedestal/kaki tower)

Foto A - 5 Foto A - 6
Tampak pagar / tembok Tampak paving block / gravel
PREVENTIVE MAINTENANCE
Base Service
PHOTO REPORT

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Contractor : NOKIA SIEMENS NETWORK

Foto B - 1 Foto B - 2
Status grounding - Tampak lightning rod (Splitzen) Status grounding - Grounding ke Pagar

Foto B - 3 Foto B - 4
Status grounding - Down Conductor cable Status grounding - Bolt Connection

Foto B - 5 Foto B - 6
Pengukuran grounding - Grounding ke Pagar Pengukuran grounding - Grounding ke kaki tower
PREVENTIVE MAINTENANCE
Base Service
PHOTO REPORT

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Contractor : NOKIA SIEMENS NETWORK

N/A

Foto C - 1 Foto C - 2
Pengukuran grounding - Tangki genset (if any) Pengukuran grounding - Box control

Foto C - 3 Foto C - 4
OBL - Berfungsi dengan baik Yard Lamp - Berfungsi dengan baik

Foto C - 5 Foto C - 6
Tampak Access Lease Area Site View - Tampak Atas (Sisi -1)
PREVENTIVE MAINTENANCE
Base Service
PHOTO REPORT

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Contractor : NOKIA SIEMENS NETWORK

Foto D - 1 Foto D - 2
Site View - Tampak Atas (Sisi - 2) Safety Tools (Safety belt, helm, sepatu, sarung tangan)

N/A

Foto D - 3 Foto D - 4
Tampak warning sign board (if any)

Foto D - 5 Foto D - 6
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Indoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI

Foto A-1 Foto A-2


Tampak Bagian Luar Shelter Tampak Bagian Dalam Shelter

Foto A-3 Foto A-4


Tampak Cable Tray Tampak Lampu di dalam shelter

Foto A-6 Foto A-5


Tampak Lampu di luar shelter Tampak frame FEP
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Indoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI

Foto B-1 Foto B-2


Tampak Grounding di dalam shelter Tampak pondasi shelter

Foto B-3 Foto B-4


Tampak Fire Extinguisher Tampak Panel Alarm

Foto B-5 Foto B-6


Tampak DC Fan Tampak Smoke & Heat detector
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Indoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI

Foto C-1 Foto C-2


Tampak AC Indoor Tampak AC Outdoor

Foto C-3 Foto C-4


Pengukuran - Tekanan AC Pengukuran - Temperature Shelter

Foto C-5 Foto C-6


Pengukuran - Tegangan R - N (Panel KWH) Pengukuran - Tegangan S - N (Panel KWH)
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Indoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI

Foto D-1 Foto D-2


Pengukuran - Tegangan T - N (Panel KWH) Pengukuran - Tegangan R - S (Panel KWH)

Foto D-3 Foto D-4


Pengukuran - Tegangan S - T (Panel KWH) Pengukuran - Tegangan R - T (Panel KWH)

Foto D-5 Foto D-6


Pengukuran - Tegangan G- N (Panel KWH) Pengukuran - Tegangan R - N (Panel ACPDB)
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Indoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI

Foto D-1 Foto D-2


Pengukuran - Tegangan S - N (Panel ACPDB) Pengukuran - Tegangan T - N (Panel ACPDB)

Foto D-3 Foto D-4


Pengukuran - Tegangan R - S (Panel ACPDB) Pengukuran - Tegangan S - T (Panel ACPDB)

Foto D-5 Foto D-6


Pengukuran - Tegangan R - T (Panel ACPDB) Pengukuran - Tegangan G - N (Panel ACPDB)
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Indoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI

Foto E-1 Foto E-2


Status grounding - Control Box Status grounding - External Grounding Bar

Foto E-3 Foto E-4


Status grounding - Internal Grounding Bar Pengukuran grounding - Control Box

Foto E-5 Foto E-6


Pengukuran grounding - External Grounding Bar Pengukuran grounding - Internal Grounding Bar
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Indoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI

Foto F-1 Foto F-2


Tampak Pole KWH Box Kondisi KWH Panel (Keadaan tertutup)

Foto F-3 Foto F-4


Kondisi KWH Panel (Keadaan terbuka) Kondisi MCB KWH Meter

Foto F-5 Foto F-6


Kondisi Segel pada Terminal KWH Kondisi Segel pada KWH Meter Record
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Indoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI

Foto G-1 Foto G-2


Kondisi segel pada MCB KWH meter KWH meter record

Foto G-3 Foto G-4


ID Pelanggan

Foto G-5 Foto G-6


PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Outdoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012

Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT

Foto A-1 Foto A-2


Tampak Kondisi Base Frame Tampak Kondisi Dyna Bolt

Foto A-3 Foto A-4


Tampak Pondasi Base Frame Pengukuran - Tegangan R - N (Panel KWH)

Foto A-6 Foto A-5


Pengukuran - Tegangan S - N (Panel KWH) Pengukuran - Tegangan T - N (Panel KWH)
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Outdoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT

Foto B-1 Foto B-2


Pengukuran - Tegangan R - S (Panel KWH) Pengukuran - Tegangan S - T (Panel KWH)

Foto B-3 Foto B-4


Pengukuran - Tegangan R - T (Panel KWH) Pengukuran - Tegangan G- N (Panel KWH)

Foto B-5 Foto B-6


Pengukuran - Tegangan R - N (Panel ACPDB) Pengukuran - Tegangan S - N (Panel ACPDB)
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Outdoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT

Foto C-1 Foto C-2


Pengukuran - Tegangan T - N (Panel ACPDB) Pengukuran - Tegangan R - S (Panel ACPDB)

Foto C-3 Foto C-4


Pengukuran - Tegangan S - T (Panel ACPDB) Pengukuran - Tegangan R - T (Panel ACPDB)

Foto C-5 Foto C-6


Pengukuran - Tegangan G - N (Panel ACPDB) Status grounding - Control Box
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Outdoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT

NA

Foto D-1 Foto D-2


Status grounding - External Grounding Bar Status grounding - Internal Grounding Bar

Foto D-3 Foto D-4


Pengukuran grounding - Control Box Pengukuran grounding - External Grounding Bar

NA

Foto D-5 Foto D-6


Pengukuran grounding - Internal Grounding Bar Tampak Pole KWH Box
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Outdoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT

Foto E-1 Foto E-2


Kondisi KWH Panel (Keadaan tertutup) Kondisi KWH Panel (Keadaan terbuka)

Foto E-3 Foto E-4


Kondisi MCB KWH Meter Kondisi Segel pada Terminal KWH

Foto E-5 Foto E-6


Kondisi Segel pada KWH Meter Record Kondisi segel pada MCB KWH meter
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Outdoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT

N/A

Foto F-1 Foto F-2


KWH meter record ID Pelanggan

Foto F-3 Foto F-4

Foto F-5 Foto F-6


PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Outdoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012

Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL

Foto A-1 Foto A-2


Tampak Kondisi Base Frame Tampak Kondisi Dyna Bolt

Foto A-3 Foto A-4


Tampak Pondasi Base Frame Pengukuran - Tegangan R - N (Panel KWH)

Foto A-6 Foto A-5


Pengukuran - Tegangan S - N (Panel KWH) Pengukuran - Tegangan T - N (Panel KWH)
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Outdoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL

Foto B-1 Foto B-2


Pengukuran - Tegangan R - S (Panel KWH) Pengukuran - Tegangan S - T (Panel KWH)

Foto B-3 Foto B-4


Pengukuran - Tegangan R - T (Panel KWH) Pengukuran - Tegangan G- N (Panel KWH)

Foto B-5 Foto B-6


Pengukuran - Tegangan R - N (Panel ACPDB) Pengukuran - Tegangan S - N (Panel ACPDB)
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Outdoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL

Foto C-1 Foto C-2


Pengukuran - Tegangan T - N (Panel ACPDB) Pengukuran - Tegangan R - S (Panel ACPDB)

Foto C-3 Foto C-4


Pengukuran - Tegangan S - T (Panel ACPDB) Pengukuran - Tegangan R - T (Panel ACPDB)

Foto C-5 Foto C-6


Pengukuran - Tegangan G - N (Panel ACPDB) Status grounding - Control Box
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Outdoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL

NA

Foto D-1 Foto D-2


Status grounding - External Grounding Bar Status grounding - Internal Grounding Bar

Foto D-3 Foto D-4


Pengukuran grounding - Control Box Pengukuran grounding - External Grounding Bar

NA

Foto D-5 Foto D-6


Pengukuran grounding - Internal Grounding Bar Tampak Pole KWH Box
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Outdoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL

Foto E-1 Foto E-2


Kondisi KWH Panel (Keadaan tertutup) Kondisi KWH Panel (Keadaan terbuka)

Foto E-3 Foto E-4


Kondisi MCB KWH Meter Kondisi Segel pada Terminal KWH

Foto E-5 Foto E-6


Kondisi Segel pada KWH Meter Record Kondisi segel pada MCB KWH meter
PREVENTIVE MAINTENANCE Tenant
PHOTO REPORT Outdoor

Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012


Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL

N/A

Foto F-1 Foto F-2


KWH meter record ID Pelanggan

Foto F-3 Foto F-4

Foto F-5 Foto F-6