The following criteria are applicable to all the equipment furnished under
this contract whether referenced specifically elsewhere in the Terms of
Reference and Technical Specification Document or not:
Bidder shall guarantee that the operating equipment will not produce a
sound pressure level greater than 85 dBA when measured one meter from
any point on any item of equipment or enclosure including valves. This
requirement applies to the running plant taking into account the noise
effect from all the equipment within this contract.
The maximum noise level measured at the outside boundary of the power
plant fence shall be 70 dBA maximum between 6 a.m and 10 p.m and 60
dBA maximum between 10 p.m and 6 a.m. To meet this requirement, the
Bidder shall estimate the noise level at 100 m and 150 m away from the
noisiest Power Plant Building.