DelCEN 2500 HV
MODBUS Protocol Sheet
Introduction:
The Master Card, Control Board and Micro PC used in DelCEN 2500 HV will be connected to Ethernet switch. CAN and
SMBus will be looped from board to board. For external SCADA system, connection is provided using MODBUS over
TCP/IP communication.
Networking:
Inverter acts as MODBUS server. Any SCADA system can query and get the data from the Inverter. IP address for the
system will be configured during commissioning. And same should be communicated to the SCADA vendor. TCP port
for the Modbus TCP will be 502.
Note: Number of Devices vary as per the zone monitor module variants