Temporary Jacking
Bearing Schedule Point
from Contractor
Design for Pier E4
project no: HK077 sheet no.
project title: Cross Bay Link
section: date
calcs for: by

Calculation of Anti-Bursting
Reinforcement of Jacking Point
project no: HK077 (91558) sheet no.
project title: Cross Bay Link 1
section: Precast V-piers and Crossbeam date 15/01/2019
calcs for: Temporary Jacking Point Reinforcement by rw

Temporary Jacking Point Reinforcement


This section presents the calculations on additional reinforcement requirements for the
temporary jacking points on the Portal Beam at Pier E4. The layout of the temporary jack
locations on top of the V-pier of the Cross Beam is shown in below figures.

The temporary jacking points (No. 1 and 2) are checked for bearing stress and anti-busrting
reinforcement against vertical loads (SLS and ULS).

There are two sets of temporary jacking points to cater for different loading scenarios:
- Temporary jacking points No.1 - For supporting the box girder deck during erecton (for adjustment)
- Temporary jacking points No.2 - For supporting the box girder deck during erection (e.g.
temporary supports during the deck erection)
- Both temporary jacking points No.1 and 2 will act simultaneously to support for future bearing replacement

The temporary jacking point sizes are provided to us by the Engineer and the Contractor.
- Temporary jacking points No.1 - 800mm x 800mm plan area
- Temporary jacking points No.2 - 800mm x 800mm plan area

Legend
Permanent Bearings
Jacking Point No.1
Jacking Point No.2

Plan View of Cross Beam

Jacking point No.2 -


Jacking point No.1 - Temporary
Temporary support for box
Support for erection
girder during deck erection

Temporary jack locations


800 800

800 800

Permanent
Jacking point No.1 & 2 - bearing plinth
Temporary support for (designed under
future bearing replacement separate
submission by
others)

V-Pier and Cross Beam Plan View on Bearings and Temporary Jacking
points on V-Pier and Cross Beam

1. During Deck Erection 2. Future Bearing Replacement

Deck

Temporary Deck
jacking point No.2
(sand jack) Bearing Plinth

Temporary
jacking point No.1
(hydralic jack for
adjustment) Temporary jacking
point No.1 & 2
project no: HK077 (91558) sheet no.
project title: Cross Bay Link 2
section: Precast V-piers and Crossbeam date 15/01/2019
calcs for: Temporary Jacking Point Reinforcement by rw

Design Loads
The design loads on the temporary jacking points are provided to us by the Engineer and
the Contractor, the design loads are as follow:
- Temporary jacking points 1 8740 kN per jacking point (during erection) *
11799 kN per jacking point (ULS: 1.35 x Deck dead load)
- Temporary jacking points 2 8740 kN per jacking point (during erection) *
11799 kN per jacking point (ULS: 1.35 x Deck dead load)
- Temporary jacking points 1 & 2 23175 kN per 2 jacking points (during future bearing replacement, SLS)
30685 kN per 2 jacking points (during future bearing replacement, ULS)
(conservatively taken as max. ULS and SLS bearing load)

*Design load during erection is taken as the maximum deck load among all jacking points provided by
Meinhardt. (see table in appendix)

Material and Stress Limits


fck = 45 MPa (C45/55) fcd = 25.5 MPa (Expr 3.15)
fyk 500 MPa

Stress limitation for reinforcement σs = 250 MPa (at SLS Crack Width)
σs = 375 MPa (at SLS Stress Check)
σyd = 435 MPa (at ULS)
project no: HK077 (91558) sheet no.
project title: Cross Bay Link 3
section: Precast V-piers and Crossbeam date 15/01/2019
calcs for: Temporary Jacking Point Reinforcement by rw

1) Bearing Vertical Load Check


The bearing pressure below the jacking is checked against the maximum allowable
stresses at SLS and ULS. A stress limit of 0.6*fck, as per J.102 of BS EN 1992-2-2005, is
checked against SLS and ULS applied load in accordance with BS EN1992-1-1:2005 7.2(2).

Anti-bursting reinforcement is checked to ensure the bursting force can be


resisted by the reinforcement. The bursting force and the reinforcement requirement is
calculated based on expression J.102 in BS EN1992-2:2005 Annex J.

At Temporary Jacking Locations


The location of the temporary jacking is unchanged from the conforming design
drawings of the substructure. The design loads at these temporary jacking location are as per
described earlier.
b1
h
b2 Additonal
reinforcemnt at
jacking point

Bearing Type Unit Jacking point 1 Jacking point 2 Jacking point 1&2
Jacking Width, b1 (see note 4) (mm) 800 800 1600 A = bearing plan
Point
Dimension Length, b2 (see note 4) (mm) 800 800 800 area = b1 x b2
Bearing SLS Max (kN) 8740 8740 23175
Vertical
Loads ULS Max (kN) 11799 11799 30685
No of Jacking Points (-) 1 1 2
Bearing pressure, P / A (SLS) MPa 13.7 13.7 9.1
Bearing
Allowable = 0.6*fck (J.102) MPa 27.0 27.0 27.0 7.2(2)
stress
check at Bearing OK at SLS? (-) OK OK OK Bearing at SLS is ok
contact Bearing pressure, P / A (ULS) MPa 18.4 18.4 12.0
point
Allowable = 0.6*fck (J.102) MPa 27.0 27.0 27.0
Bearing OK at ULS? (-) OK OK OK Bearing at ULS is ok
Bursting At SLS (kN) 1311 1311 1738
Force At ULS (kN) 1770 1770 2301
Reinf' At SLS (mm2) 5244 5244 6953
required,
As,req At ULS (mm2) 4071 4071 5293
Reinf' BM95c (closed link) (-) 4 B 25 4 B 25 8 B 25
Check BM95b (single leg bars) (-) 12 B 25 12 B 25 24 B 25
Reinf' 95 (U bar) (-) 4 B 25 4 B 25 8 B 25
provided (-) B B B
(mm2) 9817 9817 19635 Anti-bursting
As,prov reinforcement provided
(-) OK OK OK is ok

The depth of the anti-bursting rebars, h, will be the same as b2 (e.g. 800mm for jacking
points 1 and 2).
project no: HK077 sheet no.
project title: Cross Bay Link
section: date
calcs for: by

Calculation of Anti-Edge Sliding


Reinforcement of Jacking Point
(provided by the Contractor)
E4 Cross Beam - Edge Sliding Check for Bearing Replacement Stage
Case 1) Edge Sliding Check at Inner Bearing (for Bearing Replacement Scenario)
ULS Permanent Load (Conforming Bearing Schedule) 31000 kN (From 60329339/C1/SK0007 Rev-)

ULS Total Load per inner Bearing 31000 kN

The above loading will be shared by 2 jacking points


Frdu, Jacking Load at Each Point (kN) 15500 kN
Fyd 435 MPa
According to BS EN 1992-2:2005 Annex J
Ar,req 17816.1 mm2

Assumptions for Effective Reinforcement for Provisions of Edge Sliding Resistance


1) Only the Transverse Horizontal Reinforcement of Cross Beam are considered effective
2) Resistance from Antibursting Reinforcement is neglected INNER

a) Steel Area from Cross Beam Transverse Reinforcement: Accordingly to Information from AECOM's Designer:
Rebar Size 25 mm Both Jacking Point 1 and 2 will be used simultaneously for
Spacing 150 mm Bearing Replacement Jacking Operation
Effective Width 3785 mm
No. of Effective Rebars 26 nos.
Steel Area Provided 12762.7 mm2

b) Steel Area from Cross Beam Spacer Bar


Rebar Size 0 mm (Spacer Bar Neglected)
Spacing 1500 mm
Effective Width 3785 mm
No. of Effective Rebars 3 nos.
Steel Area Provided 0 mm2

c) Steel Area from Cross Beam Additional Anti-edge sliding rebar


Rebar Size 25 mm (Additional Anti-edge sliding rebar)
Spacing 300 mm
Effective Width 3785 mm
No. of Effective Rebars 13 nos.
Steel Area Provided 6381.36 mm2

Total Steel Area Provided a) + b)+ c) : 19144.1 mm2 > 17816.1 mm2 OK!

Case 2) Edge Sliding Check at Outer Bearing (for Bearing Replacement Scenario)
ULS Permanent Load (Conforming) 31000 kN From 60329339/C1/SK0007 Rev.-)

ULS Total Load per inner Bearing 31000 kN

The above loading will be shared by 2 jacking points


Frdu, Jacking Load at Each Point (kN) 15500 kN
Fyd 435 MPa
According to BS EN 1992-2:2005 Annex J
Ar,req 17816.1 mm2

Assumptions for Effective Reinforcement for Provisions of Edge Sliding Resistance


1) the Transverse Reinforcement of Cross Beam are considered effective
2) Side Bar of Cross Beam along the Free End are considered effective Outer
3)) Effect of Resistance from Antibursting Reinforcement is neglected
a) Steel Area from Cross Beam Transverse Reinforcement: Accordingly to Information from AECOM's Designer:
Rebar Size 25 mm Both Jacking Point 1 and 2 will be used simultaneously for
Spacing 150 mm Bearing Replacement Jacking Operation
Effective Width 2942 mm
No. of Effective Rebars 20 nos.
Steel Area Provided 9817.48 mm2

b) Steel Area from Cross Beam Spacer Bar


Rebar Size 0 mm (Spacer Bar Neglected)
Spacing 1500 mm
Effective Width 2942 mm
No. of Effective Rebars 2 nos.
Steel Area Provided 0 mm2

c) Steel Area from Cross Beam Edge Side Bar On Free End (Ony Consider the top 3 bars to be effective)
Rebar Size 40 mm
Spacing 0 mm
Effective Width 0 mm
No. of Effective Rebars per layer 1 nos.
No. of Layers 3 layers
Total No. of Rebars 3 nos.
Steel Area Provided (Effective) 3769.91 mm2

d) Steel Area from Cross Beam Additional Anti-edge sliding rebar


Rebar Size 25 mm
Spacing 300 mm
Effective Width 2942 mm
No. of Effective Rebars per layer 10 nos.
No. of Layers 1 layers
Total No. of Rebars 10 nos.
Steel Area Provided (Effective) 4908.74 mm2

Total Steel Area Provided: 18496.1 mm2 > 17816.1 mm2 OK!
E4 Cross Beam - Edge Sliding Check for Box Girder Erection Stage
Box Girder Self-Weight 25070 kN
Max. Support Reaction 8740 kN
ULS Load Factor (Jacking) 1.4

Case 1a) Edge Sliding Check at Inner Bearing Using Jacking Point 1 / Point 2 (Box Girder Erection Stage)

Frdu, Jacking Load at Each Point (kN) 12236 kN


fyd 435 MPa
According to BS EN 1992-2:2005 Annex J
Ar,req 14064.4 mm2

Assumptions for Effective Reinforcement for Provisions of Edge Sliding Resistance


1) Only the Transverse Horizontal Reinforcement of Cross Beam are considered effective
2) Resistance from Antibursting Reinforcement is neglected

a) Steel Area from Cross Beam Transverse Reinforcement: INNER


Rebar Size 25 mm
Spacing 150
Effective Width 2985 mm
No. of Effective Rebars 20 nos.
Steel Area Provided 9817.48 mm2

b) Steel Area from Cross Beam Transverse Reinforcement (Spacer Bar)


Rebar Size 0 mm (Spacer Bar Neglected)
Spacing 1500
Effective Width 2985 mm
No. of Effective Rebars 2 nos.
Steel Area Provided 0 mm2

c) Steel Area from Cross Beam Additional Anti-edge sliding rebar


Rebar Size 25 mm
Spacing 300 mm
Effective Width 2985 mm
No. of Effective Rebars per layer 10 nos.
No. of Layers 1 layers
Total No. of Rebars 10 nos.
Steel Area Provided (Effective) 4908.74 mm2

Total Steel Area Provided: 14726.2 mm2 > 14064.4 mm2 OK!
Case 2a) Edge Sliding Check at Outer Bearing Using Jacking Point 1 (Box Girder Erection Stage)

Frdu, Jacking Load at Each Point (kN) 12236 kN


fyd 435 MPa
According to BS EN 1992-2:2005 Annex J
Ar,req 14064.4 mm2

Assumptions for Effective Reinforcement for Provisions of Edge Sliding Resistance


1) the Transverse Reinforcement of Cross Beam are considered effective
2) Effect of Resistance from Antibursting Reinforcement is neglected

a) Steel Area from Cross Beam Transverse Reinforcement:


Rebar Size 25 mm
Spacing 150
Effective Width 2942 mm OUTER BEARING
No. of Effective Rebars 20 nos.
Steel Area Provided 9817.48 mm2

b) Steel Area from Cross Beam Transverse Reinforcement (Spacer Bar)


Rebar Size 0 mm (Spacer Bar Neglected)
Spacing 1500
Effective Width 2942 mm
No. of Effective Rebars 2 nos.
Steel Area Provided 0 mm2

c) Steel Area from Cross Beam Edge Side Bar On Free End (Ony Consider the top 3 bars to be effective)
Rebar Size 40 mm
Spacing 0 mm
Effective Width 0 mm
No. of Effective Rebars per layer 1 nos.
No. of Layers 3 layers
Total No. of Rebars 3 nos.
Steel Area Provided (Effective) 3769.91 mm2

d) Steel Area from Cross Beam Additional Anti-edge sliding rebar


Rebar Size 25 mm
Spacing 300 mm
Effective Width 2942 mm
No. of Effective Rebars per layer 10 nos.
No. of Layers 1 layers
Total No. of Rebars 10 nos.
Steel Area Provided (Effective) 4908.74 mm2

Total Steel Area Provided: 18496.1 mm2 > 14064.4 mm2 OK!

Case 2b) Edge Sliding Check at Outer Bearing Using Jacking Point 2 (Box Girder Erection Stage)

Frdu, Jacking Load at Each Point (kN) 12236 kN


fyd 435 MPa
According to BS EN 1992-2:2005 Annex J
Ar,req 14064.4 mm2

Assumptions for Effective Reinforcement for Provisions of Edge Sliding Resistance


1) the Transverse Reinforcement of Cross Beam are considered effective
2) Side Bar of Cross Beam along the Free End are considered effective
3)) Effect of Resistance from Antibursting Reinforcement is neglected
a) Steel Area from Cross Beam Transverse Reinforcement:
Rebar Size 25 mm
OUTER BEARING
Spacing 150
Effective Width 2142 mm
No. of Effective Rebars 15 nos.
Steel Area Provided 7363.11 mm2

b) Steel Area from Cross Beam Transverse Reinforcement (Spacer Bar)


Rebar Size 0 mm (Spacer Bar Neglected)
Spacing 1500
Effective Width 2142 mm
No. of Effective Rebars 2 nos.
Steel Area Provided 0 mm2

c) Steel Area from Cross Beam Edge Side Bar On Free End (Ony Consider the top 3 bars to be effective)
Rebar Size 40 mm
Spacing 0 mm
Effective Width 0 mm
No. of Effective Rebars per layer 1 nos.
No. of Layers 3 layers
Total No. of Rebars 3 nos.
Steel Area Provided (Effective) 3769.91 mm2

d) Steel Area from Cross Beam Additional Anti-edge sliding rebar


Rebar Size 25 mm
Spacing 300 mm
Effective Width 2142 mm
No. of Effective Rebars per layer 8 nos.
No. of Layers 1 layers
Total No. of Rebars 8 nos.
Steel Area Provided (Effective) 3926.99 mm2

Total Steel Area Provided: 15060 mm2 > 14064.4 mm2 OK!
project no: sheet no.
project title:
section: date
calcs for: by

Bearing Schedule
Bearing Schedule (from
from Contractor
Employer's Design)
project no: sheet no.
project title:
section: date
calcs for: by

Deck Weight
Drawing of Size and(Provided by
Location of Temporary
Meinhardt)
Jacking from Contractor
Simon Li
TW-D-073
ANNEX A - Summary of Support Reactions at Temporary Jacking Points Due to Self-weight of Precast
寄件者:
Box Girder Jason Lu <jasonlu@meinhardt.com.hk>
寄件日期: 2020年1月14日星期二 19:43
收件者: 'Simon Li'; 'Ray Wong'; 'Kenny Yu'; '91558'; 'David Lee'
副本: ronald.lee@crbc.com.hk; 'arnold chan'; 'Chiu Ho Yin'; fortressdev@hotmail.com
主旨: RE: E5 Edge Sliding Reinforcement at Jacking Points

Dear Ray,

As discussed yesterday, please find below the support force of E bridge due to self-weight at installation
stage for your use.

Box girder Weight (tons) Support 1 Support 2 Support 3 Support 4


Box Girder
26kN/m3 (tons) (tons) (tons) (tons)

E2-E3 S 2,572 453 394 855 870


E2-E3 N 2,507 749 611 521 626
E3-E4 S 2,507 453 373 874 807
E3-E4 N 2,471 695 611 614 550
E4-E5 S 2,420 380 378 830 832
E4-E5 N 2,349 625 625 550 550
E5-E6 S 2,422 380 378 831 833
E5-E6 N 2,363 631 598 566 567
E6-E7 S 2,252 409 398 716 727
E6-E7 N 2,234 643 632 474 485
E7-EA S 1,698 307 376 471 543
E7-EA N 1,728 479 552 314 384

Regards
Jason Lu
MIEL

Meinhardt Infrastructure and Environment Limited

1
project no: HK077 sheet no.
project title: Cross Bay Link
section: date
calcs for: by

Sketches of Additional Reinforcement


below Jacking Points
(provided by the Contractor)
SKETCH TITLE: ARRANGEMENT OF ADDITIONAL ANTI-EDGE SLIDING REINFORCEMENT AT TEMPORARY JACKING POINTS FOR E4,E5 & E7 CROSS BEAM

SKETCH NO.: TWD073-SK001 1. ALL DIMENSIONS IN MILLIMETERS UNLESS OTHERWISE STATED.


2. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH ICE CERTIFIED DRAWINGS OF CSD NO.1.
3. REINFORCEMENT REQUIRED TO PREVENT EDGE SLIDING DETEMRINED IN ACCORDANCE WITH j.104.1(104), ANNEX J OF BS EN 1992-2:2005.
4. ONLY THE FOLLOWING REINFORCEMENT WITHIN THE EFFECTIVE WIDTH AS INDICATED ARE CONSIDERED EFFECTIVE FOR RESISTING EDGE SLIDING:
a) TRANSVERSE TOP REINFORCEMENT OF CROSS BEAM (BAR MARK 60);
b) 3 NOS. OF SIDE REINFORCEMENT (BAR MARK 42) (FOR THE JACKING POINTS NEAR BOTH ENDS) ;
c) ADDITIONAL ANTI-EDGE SLIDING REINFORCEMENT;
5. DESIGN JACKING FORCE DURING CONSTRUCTION STAGE (I.E. BOX GIRDER ERECTION) IN ACCORDANCE WITH ANNEX A UNDER TW-D-073 , TO BE
FACTORED BY 1.4 FOR ULS DESIGN.
6. DESIGN JACKING FORCE DURING FUTURE BEARING REPLACEMENT (BY OTHERS) ARE TAKEN FROM THE ULS VERTICAL LOAD (MAX.) FROM CONFORMING
BEARING SCHEDULE ON DRAWING NO. 60329339/C1/SK0007 REV.-, ASSUMING BOTH JACKING POINTS (I.E. JACKING POINT 1 & JACKING POINT 2) WILL ACT
SIMULTANEOUSLY.

A "EFFECTIVE WIDTH"

2942
"EFFECTIVE WIDTH"

3785 3785 2942

2nos. of 2nos. of
800x800 Additional Anti-Edge 800x800 800 800

Jacking Point Sliding Rebars Jacking Point

800
JACKING JACKING JACKING JACKING JACKING JACKING JACKING JACKING
T25-300 (10 nos.) POINT 2 POINT 1 POINT 1 POINT 2 POINT 2 POINT 1 POINT 1 POINT 2 T25-300 (10 nos.)
Additional Anti-Edge T25-300 (13 nos.) T25-300 (13 nos.) Additional Anti-Edge

508
Sliding Rebars Additional Anti-Edge Additional Anti-Edge Sliding Rebars
Sliding Rebars Sliding Rebars
T.A.L. T.A.L.

BEARING PLINTH BEARING PLINTH E4 / E5 BEARING PLINTH BEARING PLINTH

1600
RB GL 1250x1250x286
E3

CROSS BEAM
1800

JACKING JACKING JACKING JACKING JACKING JACKING JACKING JACKING


POINT 2 POINT 1 POINT 1 POINT 2 POINT 2 POINT 1 POINT 1 POINT 2

800
RB GL 1250x1250x286
E3 800 800

SECTION A-A
2942 3785 3785 2942

T.A.L for T25 = 1330mm 1450

ARRANGEMENT OF ADDITIONAL ANTI-EDGE SLIDING REINFORCEMENT FOR E4,E5 CROSS BEAM

B "EFFECTIVE WIDTH"

2942
"EFFECTIVE WIDTH"

3785 3785 2942

2nos. of 2nos. of
800x800 Additional Anti-Edge 800x800 800 800

Jacking Point Sliding Rebars Jacking Point


800

JACKING JACKING JACKING JACKING JACKING JACKING JACKING JACKING


T25-300 (10 nos.) POINT 2 POINT 1 POINT 1 POINT 2 POINT 2 POINT 1 POINT 1 POINT 2
T25-300 (10 nos.)
Additional Anti-Edge T25-300 (13 nos.) T25-300 (13 nos.) Additional Anti-Edge
558

Sliding Rebars Additional Anti-Edge Additional Anti-Edge Sliding Rebars


Sliding Rebars Sliding Rebars
T.A.L. T.A.L.

BEARING PLINTH BEARING PLINTH E7 BEARING PLINTH BEARING PLINTH


1500

RB GL 1250x1250x286
E3

CROSS BEAM
1600
558

JACKING JACKING JACKING JACKING JACKING JACKING JACKING JACKING


POINT 2 POINT 1 POINT 1 POINT 2 POINT 2 POINT 1 POINT 1 POINT 2
800

RB GL 1250x1250x286
E3
800 800

SECTION B-B
2942 3785 3785 2942

T.A.L for T25 = 1330mm 1450

ARRANGEMENT OF ADDITIONAL ANTI-EDGE SLIDING REINFORCEMENT FOR E7 CROSS BEAM