Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-E-6018
Project Name: Date: 01 Apr 2011
Contract Number: Page 4 of 8
Revision 1
1.0 GENERAL
1.1 Summary
A. Scope of Specification
This specification describes the general requirements for multi conductor 300 volt to
1000 volt power and control cables.
B. Related Documents
3. See the Request for Quotation (RFQ) or Purchase Order (PO) for additional
requirements.
1.2 References
The latest issues, amendments, and supplements to these documents shall apply unless otherwise
indicated.
2.0 PRODUCTS
2.1 General
2.2 Equipment
A. Conductors
Conductors shall be annealed uncoated copper with class B stranding and shall be sized
as indicated on the datasheets.
B. Insulation
Single conductors shall have ethylene propylene rubber (EPR) flame retardant insulation.
C. Ground Wires
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-E-6018
Project Name: Date: 01 Apr 2011
Contract Number: Page 6 of 8
Revision 1
A bare copper ground wire shall be provided for all cables where the power conductor is
larger than number 10 AWG (4mm2).
D. Fillers
Fillers shall be used as necessary to give the completed cable a substantially circular
cross-section. Filler shall be of an inert, non-hygroscopic material.
E. Metallic Sheath
F. Jacket
A PVC jacket of moisture resistant flame retardant material shall be applied over the
entire cable assembly
A. Inspection
2. Material and workmanship shall be subject to Marafiq’s inspection and testing after
delivery to the site. In case any cables are found to be defective in material or
workmanship, or otherwise not in conformance with the requirements of this
specification, Manufacturer shall replace or repair cable at Manufacturer’s cost.
B. Testing
4. Any special tests shown in the datasheet shall be performed on the completed cables
in accordance with the applicable procedure.
5. Marafiq reserves the right to witness all tests. Manufacturer shall provide written
notification to Marafiq at least two (2) weeks in advance of the test date. The notice
shall include an outline of the procedures used in performance of the tests.
6. Manufacturer shall not proceed with witness tests in the absence of Marafiq and/or
Marafiq’s Representative unless he has received written notification waiving witness
of testing.
A. Power Conductors
Power conductors shall conform to ICEA Method 1,color sequence Table E-2 or Method
4 (printed numbers).
B. Control Conductors
C. Jacket
The following minimum information shall be printed on the surface of the jacket at
regular intervals:
Conductor size
Number of conductors
Voltage class
Type of insulation
Manufacturer's name
Marking to indicate UL listing
D. Reels
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-E-6018
Project Name: Date: 01 Apr 2011
Contract Number: Page 8 of 8
Revision 1
A metal weatherproof tag shall be affixed to each side of the reel indicating the following
information:
3.0 EXECUTION
Not applicable.
ATTACHMENTS
Not Applicable
End of Specification