Professional Documents
Culture Documents
Reference No:
Fire and Jockey Pump Installation
SITEVER
INSTRUCTION SIP-FP-0001
PROCESS Page of 10 SIP-FP-0001
001
1.0 Introduction
2.0 Purpose
3.0 Scope
4.0 Application
5.0 Materials/ Equipment
6.0 Procedure
7.0 Points to Note
8.0 References
1.0 INTRODUCTION
A fire pump is designed to increase water pressure. The pump intake and discharge piping must be
capable of flowing the required volume to which the pump will add the needed pressure for fire
protection. The pump can be started manually, but is usually arranged to start automatically upon a
drop in system pressure or the activation of a fire suppression system.
A Jockey pump is a small pump connected to a fire sprinkler system and is intended to maintain
pressure in a fire protection piping system to an artificially high level so that the operation of a single
fire sprinkler will cause a pressure drop which will be sensed by the fire pump automatic controller,
causing the fire pump to start. The jockey pump is essentially a portion of the fire pump's control
system. A jockey pump is sized for a flow less than the flow to one sprinkler in order to ensure a system
pressure drop. Jockey pumps are typically small multistage centrifugal pumps, and do not have to be
listed or certified for fire system application. The control equipment for jockey pumps may however
carry approvals. Jockey pumps should be sized for 3% of the flow of the main fire pump and to provide
10psi more pressure than the main fire pump.
2.0 PURPOSE
Fire pumps are needed for main reason; to protect lives & properties against fire by supplying adequate
water supply to automatic sprinklers or standpipe systems. To meet building codes & insurance
requirements.
3.0 SCOPE
Provide a complete fire pumps system as defined by the latest edition of NFPA20.
4.0 APPLICATION
Fire pumps are powered by an electric motor or diesel engine. The sprinkler system pressure drops
significantly when one or more fire sprinklers are activated or alternatively when other firefighting
connections are opened, causing a pressure drop.
2. Storage Warehouse:
Large expanses of space have higher water pressure demands if a fire begins to spread. Warehouse
is a prime example because they don’t have walls or doors to slow the fire as its spread.
Listing Authorities;
1. Underwriters Laboratories (UL)
2. Factory Mutual Research Corporation (FM)
6. PROCEDURE
A. Site planning
Receiving: Upon receiving the pump, it should be inspected for damage or shortages. If damage
has occurred, file a claim immediately with the company that delivered the pump. If the manual
is removed from the crating, do not lose or misplace.
B. Preparation
2. Foundation
3. Mounting
4. Field Alignment
5. Grouting
6. Piping:
7. POINTS TO NOTE
8. REFERENCES
Installation and operation manual centrifugal Pumps by Weinman.
Installation and operating manual for fire pumps by Armstrong.
NFPA-20 Standard for the installation of stationary Pumps for Fire Protection.
Fire Pump System in NFPA 20 Standard - ETNA
https://maker.pro/custom/tutorial/the-basic-mechanical-tools-you-need-for-your-workshop
https://interestingengineering.com/25-tools-every-engineer-should-have-to-fix-everything