You are on page 1of 6

System Analysis with the MVA Method for

Symmetrical Three-Phase Faults


Adnan Kakilli1
1
Marmara University Technical Education Faculty, Istanbul, Turkey

Abstract – Electric energy is one of the fundamental The short-circuit current levels can be very high.
resources of modern industrial society. Electric power The level depends on fault types. There are two
is available to the user instantly, at the correct voltage effects of the magnitude of the short circuit current.
and frequency, and exactly in the amount that is One of them is thermal and the other one is dynamic.
needed. This remarkable performance is achieved
No substation equipment, motor control centers,
through careful planning, design, installation and
operation of a very complex network of generators,
breaker panels, etc.., are supposed to be selected
transformers, and transmission and distribution lines. without the knowledge of the complete short circuit
We must examine all possible types of fault or information of the entire power distribution system
abnormal conditions which may occur in the power [4].
system. The analysis of power systems under faulted
condition provides information regarding circuit There are various methods to determine short
breaker selection, relay setting, and the stability of the circuit current values but only one of them is
systems operation. discussed and presented in this paper. Some brief
In this study, a balanced three phase fault current at information is given about the other short circuit
a given bus of the system is calculated by using
calculation methods.
different methods. Especially emphasis on the MVA
method and compared other conventional methods.

Keywords – Fault Calculation, MVA Method, Ohmic 2. Methods of Symmerrical Three-Phase Faults
Method, Per-Unit Method Calculations

The normal mode of operation of an AC power


1. Introduction system is balanced, there-phase. However, there are
undesirable but unavoidable incidents that may
Electrical energy consumption increases more temporarily disrupt normal conditions, such as when
and more on a daily basis. Technological the insulation of the power system fails at any point
development is the reason for the use of electrical or when a conducting material comes in contact with
energy. Therefore, every year many more power a bare conductor. In such cases a shunt fault has
stations, transmission lines and substations are occurred. A fault may be caused by lightning, trees
constructed. This situation increases the fault current falling on the electric wires, vehicular collision with
levels in power systems. the poles or towers and so forth.

The analysis of power systems under faulted Shunt faults may be classified under four types.
conditions provides information regarding circuit The different types of faults are listed here in order of
breaker selection, relay setting and the stability of the frequency of their occurrence.
system operation [1]. It is important to determine the
values of system voltages and currents during faulted 1-Single line-to-ground fault (SLG)
conditions, so that protective devices may be set to 2-Line-to-line fault (L-L)
minimize the harmful effects of such contingencies 3-Double line-to-ground fault (2LG)
[2]. The proper coordination of protective relays and 4-Balanced three-phase fault.
the correct specification of circuit breaker rating are
based on the result of calculations. The performance 2.1. Comparision of Short Circuit Calculation Methods
of the power system is simulated in what is called
transient stability analysis under a variety of Fault calculations provide information on
disturbances, such as short circuits, sudden large load currents and voltages of a power system during fault
changes, and switching operations [3]. Sometimes conditions. Short-circuit currents are computed for
short circuits present a possibility of damage to the each relay and circuit breaker location and for
equipment, and loss of synchronous machines. It is various system contingency conditions, such as lines
an unwanted situation. or generating units out of service, in order to

TEM Journal – Volume 2 / Number 1/ 2013. 51


www.temjournal.com
determine maximum and minimum fault currents.
This information is useful to the design engineer is System U 2 (kV) 13,8 2
x = = = 0,380Ω
selecting circuit breakers for fault interruption, S (MVA) 500
selecting relays for fault detection, and determining
x = 0,151Ω
the relay settings, which is referred to as relay Feeder
coordination. The proper selection and setting of
U 2 (kV) 2,4 2
protective devices ensure minimum disruption of the x = x pu = 0,055 = 0,063Ω
Trans. S(MVA) 500
electrical service, and limits possible damage to the
faulted equipment.
U 2 (kV) 2,4 2
x = x pu = 0,016 = 0,369Ω
Motor S(MVA) 500
Sufficient accuracy in fault studies can be
obtained with certain simplifications in the model of
the power system. These assumptions include the Table 1. Ohmic Conversion
following;

1-Shunt elements of the transformer model are


neglected, that is, magnetizing currents and core BASE (MVA) 500
System x pu = = = 1,00 pu
loses are ignored. MVA (SC) 500

BASE (MVA) 500


2-Shunt capacitances in the transmission line x pu = x = 0,151 = 0,396 pu
U2 13,8 2
model are neglected. Feeder

3-Transformers are assumed to have nominal tap BASE (MVA) 500


x pu = x pu = 0,055 = 5,5 pu
positions. Trans. MVA t 5

4-All internal voltage sources are set equal x pu = x pu


BASE (MVA)
= 0,16
500
= 32,0 pu
to1,0+j0 p.u. terminal voltage. Motor MVA m 2,5

This set of assumptions is equivalent to neglecting Table 2. Per-Unit Conversion


prefault load current [3].

A simple power system are given below in figure


1. Types or formulas are given for each component
System
for various fault calculation methods. 500 MVA
kV 2 13,8 2
MVA = = = 1260
Feeder x (Ohms) 0,151

MVA t 5
MVA = = = 91
Trans. x pu 0,055

MVA m 2,5
MVA = = = 15,6
Motor x pu 0,16

Table 3. MVA Conversion

Figure 1. One line diagram for the comparison of various


methods

52 TEM Journal – Volume 2 / Number 1/ 2013.


www.temjournal.com
Figure 2. a) Ohmic Method Reactance Diagram b) Per-Unit Reactance Diagram c) MVA Diagram

Methods Fault Ohmic Per-Unit MVA


Condition Method Method Method
Fault @ 2,4 kV Bus 77,8 MVA 72,6 MVA 72,6 MVA
Witout Motor Cont.
Fault @ 2,4 kV Bus 88 MVA 88MVA 88 MVA
With Motor Cont.
Table 4. Result of the Comparison of Methods

3. Analysis and Solution of Power Plant All data related to the system connections, generator,
Symmetrical Three-Phase Faults on MVA main and auxiliary transformers, etc.., are available.
Line-to-line rms voltage levels of the plant are: 138
To design a real power system which consists of kV, 34,5 kV, 13,8 kV, 4,16 kV. All loads are
generators, transformers, transmission lines, ignored. The resistive components of all impedances
distribution transformers, switches, circuit breakers, are also ignored. Power plant and data values are
reading and measurement devices. Usually the given in Fig.3.
length of he transmission lines is rather long. The
fault risk ratio increases depending on transmission Cumpute the three-phase fault MVA’s and fault
lines length and number of lines. currents (in ampares, rms) for the following three-
phase locations:
The objective is to find how much short circuit
current flows from the sources to the fault, when a 138 kV bus of the plant.
symmetrical three-phase short circuit occurs at any 34,5kV bus of the plant.
location (buses or lines) in a power system. As a
result of the process, the calculations slow us how to Determine the individual generator and system
select circuit breakers, what should be their MVA fault contributions is MVA during faults 1,2 and
values and current rating (steady state and transient determine all transformer and line MVA flows as
state), and voltage ratings as well [5]. well.

As an example, an industrial power plant is


analyzed. The plant has two generators. It is
connected to the 138 kV system of the power plant.

TEM Journal – Volume 2 / Number 1/ 2013. 53


www.temjournal.com
Figure 3. An Industrial Power Plant

3.1. Analysis And Solution Fault at 138 kV Bus


component is supplied by the system directly, and it
Fault at 138 kV bus, all breakers open. Assume is short circuited at its terminals. It is equal to its own
no load at any of the buses and all “boxed” values are MVA base divided by its own per-unit impedance for
in MVA. A “boxed” value of a component is given transformers, generators, motors, etc.
as a short circuit MVA flow from the system if the

Figure 4. Fault at 138 kV Bus

We must transform the “delta to a wye figure above will be used in a delta-wye transform.
configuration. The a,b,c notations taken from the

54 TEM Journal – Volume 2 / Number 1/ 2013.


www.temjournal.com
Figure 5. a) MVA Contributions, Fault at 138 kV Bus
b) MVA Contributions, Fault at 34,5 kV Bus

4. Conclusion

The MVA method is easier than the other The conversion formulas as used for both the
methods. There are many reasons why the MVA ohmic and the per-unit methods are complex and not
method is recommended for industrial power system easy to memorize.
short circuit calculations
Both the ohmic and the per-unit methods usually
It does not require a common MVA base as end up with small decimals resulting from converting
required by the per-unit method. It is not necessary to impedances from one voltage level to another one or
convert impedances from one voltage level to from converting impedances to the same common
another as repuired by the ohmic method. base. Therefore, one can make mistakes easily [6].

TEM Journal – Volume 2 / Number 1/ 2013. 55


www.temjournal.com
References
[5]. Fink, D. G., Beaty, H. W., Standard Handbook
[1]. Gungor, B., R., Power Systems, Harcout Brace For Electrical Engineers, McGraw-Hill, New
Jovanovich, New York, 1988, pp.323 York, 1993.
[2]. Kasibama, H., W., Electrical Power Engineering, [6]. Yuen, M., H., “Short Circuit ABC-Learn It In an
McGraw-Hill, New York, 1993, pp.227 Hour, Use It Anywhere, Memorize No Formula”,
[3]. Yamayee, Z., A., Bala, J.,R., J.,L., IEEE Transactions on Industry Applications,
Electromechanical Energy devices and Power Vol. IA-10 No.2, March/April 1974, pp.265-266
Systems, John Wiley & Sons, New York, 1994,
pp.384-386
[4]. Sarma, M., Glover, D., J., Power System analysis Corresponding author: Adnan Kakilli
& Design, PWS, Boston, 1994. Institution: Marmara University, Technical Education
Faculty, Istanbul, Turkey
E-mail: kakilli@marmara.edu.tr

56 TEM Journal – Volume 2 / Number 1/ 2013.


www.temjournal.com

You might also like