Protection Application Example

380 kV OHL

blocking of the distance protection during power swings. At 380 kV it is common


practice to Enable the power swing detection.

121 Teleprotection for Distance Prot.: To achieve fast tripping for all faults on the circuit
a teleprotection scheme must be applied.

Parameter PUTT POTT Blocking Unblocking


Short line Not suitable as Suitable as the Suitable as Suitable as the
the Zone 1 Z1b setting reverse reach Z1b setting
operation is may be setting is may be
essential and substantially independent of substantially
Zone 1 setting larger than the line length larger than the
in X and R line impedance line impedance
direction must so that signal so that signal
be small on transmission is transmission is
short lines secure for all secure for all
faults on the faults on the
line. line.
Weak Infeed Not suitable as Suitable as the Partially Suitable as the
the Zone 1 strong end Suitable as the strong end
operation is detects all line reverse fault is detects all line
essential at faults with also detected at faults with
both ends for overreaching the weak infeed overreaching
100% line Z1b. The weak end but no trip Z1b. The weak
coverage infeed end then at weak infeed infeed end then
echos the end echos the
received signal. received signal.
Amplitude Not suitable as Not suitable as Suitable as the Not suitable as
modulated the signal must the signal must signal is only the signal must
power line be transmitted be transmitted sent when the be transmitted
carrier through the through the line is not through the
fault location fault location faulted fault location
which which which
attenuates the attenuates the attenuates the
signal signal signal
Frequency or Suitable as the Suitable as the Suitable as the Suitable as the
phase signal can be signal can be signal can be signal can be
modulated transmitted transmitted transmitted transmitted
power line through the through the under all through the
carrier fault location fault location conditions fault location
Communication Suitable Suitable Suitable Suitable
independent of
power line
Table 3: Selection of teleprotection scheme

In this case the selection is POTT

122 DTT Direct Transfer Trip: If external inputs, also CFC, must be connected to initiate
tripping via binary input, this function should be activated. The trip will then
automatically be accompanied by the minimum trip command duration (trip circuit

7SA522/7SA6 Application Example Page 8 of 82