You are on page 1of 5

Maruthi Ispat & Energy Pvt Ltd

Power Plant
Electrical & Instrumentation
Breakdown Analysis Report-E&I
Department:Ele

Equipment Name

Equipment ID

Breakdown opening date & time

Breakdown closing date & time

Sl.No Failure

1 Hotwell Level Transmitter

2 Why Display card with CPU burnt?

Root Cause of Breakdown identified

Corrective Action

Preventive Action

Result after Implementation


Prepared By
hi Ispat & Energy Pvt Ltd
Power Plant
rical & Instrumentation
own Analysis Report-E&I
Department:Electrical/Instrumentation

Hotwell Level Transmtter

90_LT_001

2/3/2019

8/5/2019

Causes of Failure

Level Transmitter Display card with CPU burnt

Heat transfer internal to Transmitter occured from process Exhaust steam


leading to damage Display card & CPU.

Heat transfer internal to Transmitter occured from process Exhaust steam


leading to damage Display card & CPU.

Replacement of Transmitter with the new one.

Kept under regular observation with proper covering.

Now Hotwell level tripping shifted back to Level Transmitter and working
normal.
Doc No : MIEPL/FM/PP/E&I/15
Rev No : 00
Date :04/03/2019
Page No: 01 of 01

Hotwell Level Transmtter

90_LT_001

2/3/2019

8/5/2019

Action Taken/Remarks

Hotwell level tripping shifted to Level Switches instead of Transmitter


temporarily.

Since Display with CPU card is an electronic part which is out of warranty.Hence
decided to replace the transmitter after discussion with Vendor.
Approved By