Professional Documents
Culture Documents
Company Name
Address
City, State Zip
Phone Number
Item ID = 1
Item Description = Teste
System Application = Pipe - Horizontal
Dimensional Standard = ASTM C 585 Rigid
Calculation Type = Condensation Control Report
Process Temperature = 5
Ambient Temperature = 35
Wind Speed = 1
Relative Humidity = 65
Dew Point = 27.4
Condensation Control Thickness = 15
Nominal Pipe Size = 200
Bare Metal = Steel
Bare Surface Emittance = 0.8
Insulation Layer 1 = Elastomeric SHT+TUBE, Gr 1, C534-14
Variable Insulation Thickness Surface Temp (°C) Heat Gain (W/m) Efficiency (%)
Bare 5.0 259.80
15.0 29.1 60.26 76.80
25.0 32.1 32.34 87.55
40.0 33.0 23.57 90.92
50.0 33.5 18.87 92.74
65.0 33.9 15.36 94.09
80.0 34.1 13.50 94.80
90.0 34.2 12.13 95.33
100.0 34.3 11.07 95.74
115.0 34.4 10.23 96.06
125.0 34.5 9.54 96.33
140.0 34.5 8.97 96.55
150.0 34.6 8.49 96.73
165.0 34.6 8.07 96.89
175.0 34.6 7.71 97.03
190.0 34.6 7.39 97.15
200.0 34.7 7.11 97.26
215.0 34.7 6.86 97.36
225.0 34.7 6.64 97.44
240.0 34.7 6.44 97.52
250.0 34.7 6.25 97.59
file:///C:/Users/alencar.campos/Documents/3EPlus/PrintReport.htm 3/28/2020