HVAC Sizing IES VIRTUAL ENVIRONMENT

Project and Climate


VE 2019
Model Data Cooling Calculation Data
Project file HVAC Sizing.mit Results file Load run.clg
Source HVAC file Proposed.asp Calculated 2020/04/11 11:57
HVAC file snapshot Vista\Load run.asp Profile Month Jan - Dec
Model floor area 13,782.1 m² Max outdoor temp. dry bulb 35.2 °C
Building conditioned floor area 13,782.1 m² Max outdoor temp. wet bulb 22.4 °C
Building conditioned volume 48,237.3 m³
Heating Calculation Data
Number of conditioned rooms 4
Results file Load run.htg
Load analysis methodology ASHRAE Heat Balance Method
Calculated 2020/04/11 11:56
Calculated 2020/04/11 20:36
Profile Month Jan
Version No. 2019.1.0.0
Outdoor winter design temp 15.3 °C

Location Data Project Loads Summary


Location Bangaluru , India Cooling loads: kW W/m²
Latitude 12.97 N Coincident peak space load 755.21 54.80
Longitude 77.58 E Heating loads:
Altitude 921.0 m Coincident peak space load 102.30 7.42
Time Zone 5.5 hours ahead of GMT

Design Weather Data


Source ASHRAE design weather database
Monthly percentile:
For heating loads design weather 99.60 %
For cooling loads design weather 0.40 %
Barometric pressure 90,757.6 Pa
Air density 1.200 kg/m³
Air specific heat 1.019 kJ/kg·K
Density-specific heat product 1.223 kJ/m³·K
Summer ground reflectance 0.2
Winter ground reflectance 0.2
Carbon dioxide (ambient) 400.00 ppm

Project Cooling and Heating loads are coincident peak value for all conditioned spaces without oversizing. Load run | 2020/04/11 20:36 | Project and climate - Page 1 of 1
HVAC Sizing IES VIRTUAL ENVIRONMENT
Room Loads Report
Zone: None First Floor VE 2019
System: 03 c AHU FF HVAC Methodology: ApacheHVAC
COOLING ROOM PEAK HEATING ROOM PEAK AREAS & THERMAL TRANSMITTANCE
Time of Peak (Mo/Hr:Mn) 5 / 8:30 Time of Peak (Mo/Hr:Mn) Heating Design Total Area Glazing Glazing U-value1
Outside Air (DB/WB/RH) 28.2 °C / 19.0 °C / 42.7 % Outside Air (DB/WB/RH) 15.3 °C / 9.7 °C / 49.7 % m² m² % W/m²·K
External
Room Room Net Per Floor Percent Room Net Per Floor Percent Wall (above grade) 822.5 297.0 36.1 2.73
Sensible Latent Value Area of Total Value Area of Total Below Grade Walls - - - -
Envelope Gains/Losses W W W W/m² % Envelope Gains/Losses W W W/m² % Windows2 297.0 297.0 100.0 6.32
External Walls 1,770 - 1,770 0.5 0.8 External Walls -2,632 -2,632 -0.8 17.8 Doors - - - -
Roofs 0 - 0 0.0 0.0 Roofs 0 0 0.0 0.0 Floors - - - -
3
Ground/Exposed Floors 0 - 0 0.0 0.0 Ground/Exposed Floors 0 0 0.0 0.0 Roofs - - - -
External Doors 0 - 0 0.0 0.0 External Doors 0 0 0.0 0.0 COMBINED 822.5 297.0 36.1 2.73
Windows Conduction 3,613 - 3,613 1.0 1.7 Windows Conduction -6,663 -6,663 -1.9 44.9 Internal
Skylights Conduction 0 - 0 0.0 0.0 Skylights Conduction 0 0 0.0 0.0 Ceilings 3,445.5 - - 1.07
Solar 12,789 - 12,789 3.7 6.0 Solar 0 0 0.0 0.0 Floors 3,445.5 - - 1.07
Infiltration 2,029 -4,024 -1,995 -0.6 -0.9 Infiltration -3,975 -3,975 -1.2 26.8 Partitions4 - - - -
Nat/Aux Vent 0 0 0 0.0 0.0 Nat/Aux Vent 0 0 0.0 0.0 1
Area-weighted U-value; 2 Windows/glazing include glass and frames;
3
Internal Building Gains/Losses Internal Building Gains/Losses Roofs incl. skylights; 4 Partitions incl. internal windows and doors.
Internal Walls/Openings 0 - 0 0.0 0.0 Internal Walls/Openings 0 0 0.0 0.0
Internal Floors 7,789 - 7,789 2.3 3.7 Internal Floors -1,581 -1,581 -0.5 10.7 TEMPERATURES & SETPOINTS
Internal Air & Furniture 17,543 - 17,543 5.1 8.3 Internal Air & Furniture 0 0 0.0 0.0 Cooling Heating
Ceilings 1,774 - 1,774 0.5 0.8 Ceilings 27 27 0.0 -0.2 °C °C
Supply Air (design) 12.8 32.2
Sub Total 47,307 -4,024 43,283 12.6 Sub Total -14,825 -14,825 -4.3 Room Setpoint (design) 23.9 21.1
Room (actual) 24.6 21.1
Internal Gains Internal Gains Mean Radiant Temperature 26.4 21.1
Lights 40,796 - 40,796 11.8 19.2 Lights 0 0 0.0 0.0 Dry Resultant Temperature 25.5 21.1
People 50,489 40,391 90,880 26.4 42.9 People 0 0 0.0 0.0 RH (Design Max Setpoint) (%) 70.0 70.0
Misc, Computers, Equip 37,087 0 37,087 10.8 17.5 Misc, Computers, Equip 0 0 0.0 0.0
Sub Total 128,373 40,391 168,764 49.0 Sub Total 0 0 0.0 AIRFLOW
Cooling Heating
TOTAL 175,679 36,367 212,047 61.5 100 TOTAL -14,825 -14,825 -4.3 100 l/s l/s
Supply (design) 12,930 3,879
COOLING SUMMARY HEATING SUMMARY Reheat Minimum (design) 3,879 3,879
Leakage at Design Flow 0 0
Sensible cooling load (W): 175,679 Sensible heating load (W): 14,825
Ventilation (requirement) 3,446 3,446
Latent cooling load (W): 36,367 Design zone air temp for Supply Airflow calculation (°C): 21.1
Exhaust (requirement) - -
Sensible heat ratio: 0.83
Infiltration 559 559
Design Supply Airflow calculated per: Sensible Loads
Design zone air temp for Supply Airflow calculation (°C): 23.9
CHECKS

Number of People 689.10


m²/Person 5.00
Average Ceiling Height (m) 3.50
W/m² - Cooling (sensible) 50.99
W/m² - Heating 4.30
m²/kW - Cooling (sensible) 19.61
m²/kW - Heating 232.41
l/s/m² - Cooling 3.75
l/s/m² - Heating 1.13
% Outside Air - Cooling 26.65
% Outside Air - Heating 88.83
Outdoor Air l/s/m² 1.00
Outdoor Air l/s/person 5.00

Data in this report is firstly from the Room Loads (.clg and .htg) results files and the VE model. When there is an associated ApacheHVAC file, additional data from Load run | 2020/04/11 20:36 | Room Loads - Page 1 of 4
that file is included; however, the reported values for loads and calculated design airflows in these Room Loads reports are not influenced by system operation.
HVAC Sizing IES VIRTUAL ENVIRONMENT
Room Loads Report
Zone: None Ground Floor VE 2019
System: 03 c AHU GF HVAC Methodology: ApacheHVAC
COOLING ROOM PEAK HEATING ROOM PEAK AREAS & THERMAL TRANSMITTANCE
Time of Peak (Mo/Hr:Mn) 5 / 16:30 Time of Peak (Mo/Hr:Mn) Heating Design Total Area Glazing Glazing U-value1
Outside Air (DB/WB/RH) 34.1 °C / 20.7 °C / 30.5 % Outside Air (DB/WB/RH) 15.3 °C / 9.7 °C / 49.7 % m² m² % W/m²·K
External
Room Room Net Per Floor Percent Room Net Per Floor Percent Wall (above grade) 822.5 297.0 36.1 2.73
Sensible Latent Value Area of Total Value Area of Total Below Grade Walls - - - -
Envelope Gains/Losses W W W W/m² % Envelope Gains/Losses W W W/m² % Windows2 297.0 297.0 100.0 6.32
External Walls 6,449 - 6,449 1.9 2.6 External Walls -2,471 -2,471 -0.7 4.9 Doors - - - -
Roofs 0 - 0 0.0 0.0 Roofs 0 0 0.0 0.0 Floors 3,445.5 - - 1.99
3
Ground/Exposed Floors 43,990 - 43,990 12.8 17.9 Ground/Exposed Floors -39,342 -39,342 -11.4 77.5 Roofs - - - -
External Doors 0 - 0 0.0 0.0 External Doors 0 0 0.0 0.0 COMBINED 4,268.0 297.0 7.0 2.13
Windows Conduction 9,744 - 9,744 2.8 4.0 Windows Conduction -6,554 -6,554 -1.9 12.9 Internal
Skylights Conduction 0 - 0 0.0 0.0 Skylights Conduction 0 0 0.0 0.0 Ceilings 3,445.5 - - 1.07
Solar 12,031 - 12,031 3.5 4.9 Solar 0 0 0.0 0.0 Floors - - - -
Infiltration 7,162 -5,572 1,590 0.5 0.6 Infiltration -3,975 -3,975 -1.2 7.8 Partitions4 - - - -
Nat/Aux Vent 0 0 0 0.0 0.0 Nat/Aux Vent 0 0 0.0 0.0 1
Area-weighted U-value; 2 Windows/glazing include glass and frames;
3
Internal Building Gains/Losses Internal Building Gains/Losses Roofs incl. skylights; 4 Partitions incl. internal windows and doors.
Internal Walls/Openings 0 - 0 0.0 0.0 Internal Walls/Openings 0 0 0.0 0.0
Internal Floors 0 - 0 0.0 0.0 Internal Floors 0 0 0.0 0.0 TEMPERATURES & SETPOINTS
Internal Air & Furniture 0 - 0 0.0 0.0 Internal Air & Furniture 0 0 0.0 0.0 Cooling Heating
Ceilings 2,907 - 2,907 0.8 1.2 Ceilings 1,547 1,547 0.4 -3.0 °C °C
Supply Air (design) 12.8 32.2
Sub Total 82,283 -5,572 76,711 22.3 Sub Total -50,795 -50,795 -14.7 Room Setpoint (design) 23.9 21.1
Room (actual) 24.0 21.1
Internal Gains Internal Gains Mean Radiant Temperature 26.8 20.4
Lights 40,796 - 40,796 11.8 16.6 Lights 0 0 0.0 0.0 Dry Resultant Temperature 25.4 20.8
People 50,489 40,391 90,880 26.4 37.0 People 0 0 0.0 0.0 RH (Design Max Setpoint) (%) 70.0 70.0
Misc, Computers, Equip 37,087 0 37,087 10.8 15.1 Misc, Computers, Equip 0 0 0.0 0.0
Sub Total 128,373 40,391 168,764 49.0 Sub Total 0 0 0.0 AIRFLOW
Cooling Heating
TOTAL 210,655 34,819 245,474 71.2 100 TOTAL -50,795 -50,795 -14.7 100 l/s l/s
Supply (design) 15,504 4,651
COOLING SUMMARY HEATING SUMMARY Reheat Minimum (design) 4,651 4,651
Leakage at Design Flow 0 0
Sensible cooling load (W): 210,655 Sensible heating load (W): 50,795
Ventilation (requirement) 3,446 3,446
Latent cooling load (W): 34,819 Design zone air temp for Supply Airflow calculation (°C): 21.1
Exhaust (requirement) - -
Sensible heat ratio: 0.86
Infiltration 559 559
Design Supply Airflow calculated per: Sensible Loads
Design zone air temp for Supply Airflow calculation (°C): 23.9
CHECKS

Number of People 689.10


m²/Person 5.00
Average Ceiling Height (m) 3.50
W/m² - Cooling (sensible) 61.14
W/m² - Heating 14.74
m²/kW - Cooling (sensible) 16.36
m²/kW - Heating 67.83
l/s/m² - Cooling 4.50
l/s/m² - Heating 1.35
% Outside Air - Cooling 22.22
% Outside Air - Heating 74.08
Outdoor Air l/s/m² 1.00
Outdoor Air l/s/person 5.00

Data in this report is firstly from the Room Loads (.clg and .htg) results files and the VE model. When there is an associated ApacheHVAC file, additional data from Load run | 2020/04/11 20:36 | Room Loads - Page 2 of 4
that file is included; however, the reported values for loads and calculated design airflows in these Room Loads reports are not influenced by system operation.
HVAC Sizing IES VIRTUAL ENVIRONMENT
Room Loads Report
Zone: None Third Floor VE 2019
System: 03 c AHU TF HVAC Methodology: ApacheHVAC
COOLING ROOM PEAK HEATING ROOM PEAK AREAS & THERMAL TRANSMITTANCE
Time of Peak (Mo/Hr:Mn) 5 / 14:30 Time of Peak (Mo/Hr:Mn) Heating Design Total Area Glazing Glazing U-value1
Outside Air (DB/WB/RH) 35.1 °C / 21.0 °C / 28.9 % Outside Air (DB/WB/RH) 15.3 °C / 9.7 °C / 49.7 % m² m² % W/m²·K
External
Room Room Net Per Floor Percent Room Net Per Floor Percent Wall (above grade) 822.5 297.0 36.1 2.73
Sensible Latent Value Area of Total Value Area of Total Below Grade Walls - - - -
Envelope Gains/Losses W W W W/m² % Envelope Gains/Losses W W W/m² % Windows2 297.0 297.0 100.0 6.32
External Walls 5,846 - 5,846 1.7 2.5 External Walls -2,596 -2,596 -0.8 11.3 Doors - - - -
Roofs 39,315 - 39,315 11.4 16.5 Roofs -10,060 -10,060 -2.9 44.0 Floors - - - -
3
Ground/Exposed Floors 0 - 0 0.0 0.0 Ground/Exposed Floors 0 0 0.0 0.0 Roofs 3,445.5 - - 0.36
External Doors 0 - 0 0.0 0.0 External Doors 0 0 0.0 0.0 COMBINED 4,268.0 297.0 7.0 0.82
Windows Conduction 11,885 - 11,885 3.4 5.0 Windows Conduction -6,639 -6,639 -1.9 29.0 Internal
Skylights Conduction 0 - 0 0.0 0.0 Skylights Conduction 0 0 0.0 0.0 Ceilings - - - -
Solar 11,730 - 11,730 3.4 4.9 Solar 0 0 0.0 0.0 Floors 3,445.5 - - 1.07
Infiltration 7,494 -5,572 1,922 0.6 0.8 Infiltration -3,975 -3,975 -1.2 17.4 Partitions4 - - - -
Nat/Aux Vent 0 0 0 0.0 0.0 Nat/Aux Vent 0 0 0.0 0.0 1
Area-weighted U-value; 2 Windows/glazing include glass and frames;
3
Internal Building Gains/Losses Internal Building Gains/Losses Roofs incl. skylights; 4 Partitions incl. internal windows and doors.
Internal Walls/Openings 0 - 0 0.0 0.0 Internal Walls/Openings 0 0 0.0 0.0
Internal Floors -1,732 - -1,732 -0.5 -0.7 Internal Floors 382 382 0.1 -1.7 TEMPERATURES & SETPOINTS
Internal Air & Furniture 0 - 0 0.0 0.0 Internal Air & Furniture 0 0 0.0 0.0 Cooling Heating
Ceilings 0 - 0 0.0 0.0 Ceilings 0 0 0.0 0.0 °C °C
Supply Air (design) 12.8 32.2
Sub Total 74,537 -5,572 68,965 20.0 Sub Total -22,887 -22,887 -6.6 Room Setpoint (design) 23.9 21.1
Room (actual) 24.0 21.1
Internal Gains Internal Gains Mean Radiant Temperature 26.6 20.9
Lights 40,796 - 40,796 11.8 17.2 Lights 0 0 0.0 0.0 Dry Resultant Temperature 25.3 21.0
People 50,489 40,391 90,880 26.4 38.2 People 0 0 0.0 0.0 RH (Design Max Setpoint) (%) 70.0 70.0
Misc, Computers, Equip 37,087 0 37,087 10.8 15.6 Misc, Computers, Equip 0 0 0.0 0.0
Sub Total 128,373 40,391 168,764 49.0 Sub Total 0 0 0.0 AIRFLOW
Cooling Heating
TOTAL 202,910 34,819 237,729 69.0 100 TOTAL -22,887 -22,887 -6.6 100 l/s l/s
Supply (design) 14,934 4,480
COOLING SUMMARY HEATING SUMMARY Reheat Minimum (design) 4,480 4,480
Leakage at Design Flow 0 0
Sensible cooling load (W): 202,910 Sensible heating load (W): 22,887
Ventilation (requirement) 3,446 3,446
Latent cooling load (W): 34,819 Design zone air temp for Supply Airflow calculation (°C): 21.1
Exhaust (requirement) - -
Sensible heat ratio: 0.85
Infiltration 559 559
Design Supply Airflow calculated per: Sensible Loads
Design zone air temp for Supply Airflow calculation (°C): 23.9
CHECKS

Number of People 689.10


m²/Person 5.00
Average Ceiling Height (m) 3.50
W/m² - Cooling (sensible) 58.89
W/m² - Heating 6.64
m²/kW - Cooling (sensible) 16.98
m²/kW - Heating 150.54
l/s/m² - Cooling 4.33
l/s/m² - Heating 1.30
% Outside Air - Cooling 23.07
% Outside Air - Heating 76.90
Outdoor Air l/s/m² 1.00
Outdoor Air l/s/person 5.00

Data in this report is firstly from the Room Loads (.clg and .htg) results files and the VE model. When there is an associated ApacheHVAC file, additional data from Load run | 2020/04/11 20:36 | Room Loads - Page 3 of 4
that file is included; however, the reported values for loads and calculated design airflows in these Room Loads reports are not influenced by system operation.
HVAC Sizing IES VIRTUAL ENVIRONMENT
Room Loads Report
Zone: None Second Floor VE 2019
System: 03 c AHU SF HVAC Methodology: ApacheHVAC
COOLING ROOM PEAK HEATING ROOM PEAK AREAS & THERMAL TRANSMITTANCE
Time of Peak (Mo/Hr:Mn) 5 / 15:30 Time of Peak (Mo/Hr:Mn) Heating Design Total Area Glazing Glazing U-value1
Outside Air (DB/WB/RH) 34.8 °C / 20.9 °C / 29.4 % Outside Air (DB/WB/RH) 15.3 °C / 9.7 °C / 49.7 % m² m² % W/m²·K
External
Room Room Net Per Floor Percent Room Net Per Floor Percent Wall (above grade) 822.5 297.0 36.1 2.73
Sensible Latent Value Area of Total Value Area of Total Below Grade Walls - - - -
Envelope Gains/Losses W W W W/m² % Envelope Gains/Losses W W W/m² % Windows2 297.0 297.0 100.0 6.32
External Walls 6,549 - 6,549 1.9 3.2 External Walls -2,637 -2,637 -0.8 19.2 Doors - - - -
Roofs 0 - 0 0.0 0.0 Roofs 0 0 0.0 0.0 Floors - - - -
3
Ground/Exposed Floors 0 - 0 0.0 0.0 Ground/Exposed Floors 0 0 0.0 0.0 Roofs - - - -
External Doors 0 - 0 0.0 0.0 External Doors 0 0 0.0 0.0 COMBINED 822.5 297.0 36.1 2.73
Windows Conduction 11,312 - 11,312 3.3 5.5 Windows Conduction -6,667 -6,667 -1.9 48.5 Internal
Skylights Conduction 0 - 0 0.0 0.0 Skylights Conduction 0 0 0.0 0.0 Ceilings 3,445.5 - - 1.07
Solar 12,954 - 12,954 3.8 6.3 Solar 0 0 0.0 0.0 Floors 3,445.5 - - 1.07
Infiltration 7,494 -5,572 1,922 0.6 0.9 Infiltration -3,975 -3,975 -1.2 28.9 Partitions4 - - - -
Nat/Aux Vent 0 0 0 0.0 0.0 Nat/Aux Vent 0 0 0.0 0.0 1
Area-weighted U-value; 2 Windows/glazing include glass and frames;
3
Internal Building Gains/Losses Internal Building Gains/Losses Roofs incl. skylights; 4 Partitions incl. internal windows and doors.
Internal Walls/Openings 0 - 0 0.0 0.0 Internal Walls/Openings 0 0 0.0 0.0
Internal Floors 1,446 - 1,446 0.4 0.7 Internal Floors -62 -62 0.0 0.5 TEMPERATURES & SETPOINTS
Internal Air & Furniture 0 - 0 0.0 0.0 Internal Air & Furniture 0 0 0.0 0.0 Cooling Heating
Ceilings 3,075 - 3,075 0.9 1.5 Ceilings -418 -418 -0.1 3.0 °C °C
Supply Air (design) 12.8 32.2
Sub Total 42,829 -5,572 37,257 10.8 Sub Total -13,758 -13,758 -4.0 Room Setpoint (design) 23.9 21.1
Room (actual) 24.0 21.1
Internal Gains Internal Gains Mean Radiant Temperature 25.8 21.1
Lights 40,796 - 40,796 11.8 19.8 Lights 0 0 0.0 0.0 Dry Resultant Temperature 24.9 21.1
People 50,489 40,391 90,880 26.4 44.1 People 0 0 0.0 0.0 RH (Design Max Setpoint) (%) 70.0 70.0
Misc, Computers, Equip 37,087 0 37,087 10.8 18.0 Misc, Computers, Equip 0 0 0.0 0.0
Sub Total 128,373 40,391 168,764 49.0 Sub Total 0 0 0.0 AIRFLOW
Cooling Heating
TOTAL 171,201 34,819 206,020 59.8 100 TOTAL -13,758 -13,758 -4.0 100 l/s l/s
Supply (design) 12,600 3,780
COOLING SUMMARY HEATING SUMMARY Reheat Minimum (design) 3,780 3,780
Leakage at Design Flow 0 0
Sensible cooling load (W): 171,201 Sensible heating load (W): 13,758
Ventilation (requirement) 3,446 3,446
Latent cooling load (W): 34,819 Design zone air temp for Supply Airflow calculation (°C): 21.1
Exhaust (requirement) - -
Sensible heat ratio: 0.83
Infiltration 559 559
Design Supply Airflow calculated per: Sensible Loads
Design zone air temp for Supply Airflow calculation (°C): 23.9
CHECKS

Number of People 689.10


m²/Person 5.00
Average Ceiling Height (m) 3.50
W/m² - Cooling (sensible) 49.69
W/m² - Heating 3.99
m²/kW - Cooling (sensible) 20.13
m²/kW - Heating 250.43
l/s/m² - Cooling 3.66
l/s/m² - Heating 1.10
% Outside Air - Cooling 27.34
% Outside Air - Heating 91.15
Outdoor Air l/s/m² 1.00
Outdoor Air l/s/person 5.00

Data in this report is firstly from the Room Loads (.clg and .htg) results files and the VE model. When there is an associated ApacheHVAC file, additional data from Load run | 2020/04/11 20:36 | Room Loads - Page 4 of 4
that file is included; however, the reported values for loads and calculated design airflows in these Room Loads reports are not influenced by system operation.

You might also like