Project Cooling and Heating loads are coincident peak value for all conditioned spaces without oversizing. Load run | 2020/04/11 20:36 | Project and climate - Page 1 of 1
HVAC Sizing IES VIRTUAL ENVIRONMENT
Room Loads Report
Zone: None First Floor VE 2019
System: 03 c AHU FF HVAC Methodology: ApacheHVAC
COOLING ROOM PEAK HEATING ROOM PEAK AREAS & THERMAL TRANSMITTANCE
Time of Peak (Mo/Hr:Mn) 5 / 8:30 Time of Peak (Mo/Hr:Mn) Heating Design Total Area Glazing Glazing U-value1
Outside Air (DB/WB/RH) 28.2 °C / 19.0 °C / 42.7 % Outside Air (DB/WB/RH) 15.3 °C / 9.7 °C / 49.7 % m² m² % W/m²·K
External
Room Room Net Per Floor Percent Room Net Per Floor Percent Wall (above grade) 822.5 297.0 36.1 2.73
Sensible Latent Value Area of Total Value Area of Total Below Grade Walls - - - -
Envelope Gains/Losses W W W W/m² % Envelope Gains/Losses W W W/m² % Windows2 297.0 297.0 100.0 6.32
External Walls 1,770 - 1,770 0.5 0.8 External Walls -2,632 -2,632 -0.8 17.8 Doors - - - -
Roofs 0 - 0 0.0 0.0 Roofs 0 0 0.0 0.0 Floors - - - -
3
Ground/Exposed Floors 0 - 0 0.0 0.0 Ground/Exposed Floors 0 0 0.0 0.0 Roofs - - - -
External Doors 0 - 0 0.0 0.0 External Doors 0 0 0.0 0.0 COMBINED 822.5 297.0 36.1 2.73
Windows Conduction 3,613 - 3,613 1.0 1.7 Windows Conduction -6,663 -6,663 -1.9 44.9 Internal
Skylights Conduction 0 - 0 0.0 0.0 Skylights Conduction 0 0 0.0 0.0 Ceilings 3,445.5 - - 1.07
Solar 12,789 - 12,789 3.7 6.0 Solar 0 0 0.0 0.0 Floors 3,445.5 - - 1.07
Infiltration 2,029 -4,024 -1,995 -0.6 -0.9 Infiltration -3,975 -3,975 -1.2 26.8 Partitions4 - - - -
Nat/Aux Vent 0 0 0 0.0 0.0 Nat/Aux Vent 0 0 0.0 0.0 1
Area-weighted U-value; 2 Windows/glazing include glass and frames;
3
Internal Building Gains/Losses Internal Building Gains/Losses Roofs incl. skylights; 4 Partitions incl. internal windows and doors.
Internal Walls/Openings 0 - 0 0.0 0.0 Internal Walls/Openings 0 0 0.0 0.0
Internal Floors 7,789 - 7,789 2.3 3.7 Internal Floors -1,581 -1,581 -0.5 10.7 TEMPERATURES & SETPOINTS
Internal Air & Furniture 17,543 - 17,543 5.1 8.3 Internal Air & Furniture 0 0 0.0 0.0 Cooling Heating
Ceilings 1,774 - 1,774 0.5 0.8 Ceilings 27 27 0.0 -0.2 °C °C
Supply Air (design) 12.8 32.2
Sub Total 47,307 -4,024 43,283 12.6 Sub Total -14,825 -14,825 -4.3 Room Setpoint (design) 23.9 21.1
Room (actual) 24.6 21.1
Internal Gains Internal Gains Mean Radiant Temperature 26.4 21.1
Lights 40,796 - 40,796 11.8 19.2 Lights 0 0 0.0 0.0 Dry Resultant Temperature 25.5 21.1
People 50,489 40,391 90,880 26.4 42.9 People 0 0 0.0 0.0 RH (Design Max Setpoint) (%) 70.0 70.0
Misc, Computers, Equip 37,087 0 37,087 10.8 17.5 Misc, Computers, Equip 0 0 0.0 0.0
Sub Total 128,373 40,391 168,764 49.0 Sub Total 0 0 0.0 AIRFLOW
Cooling Heating
TOTAL 175,679 36,367 212,047 61.5 100 TOTAL -14,825 -14,825 -4.3 100 l/s l/s
Supply (design) 12,930 3,879
COOLING SUMMARY HEATING SUMMARY Reheat Minimum (design) 3,879 3,879
Leakage at Design Flow 0 0
Sensible cooling load (W): 175,679 Sensible heating load (W): 14,825
Ventilation (requirement) 3,446 3,446
Latent cooling load (W): 36,367 Design zone air temp for Supply Airflow calculation (°C): 21.1
Exhaust (requirement) - -
Sensible heat ratio: 0.83
Infiltration 559 559
Design Supply Airflow calculated per: Sensible Loads
Design zone air temp for Supply Airflow calculation (°C): 23.9
CHECKS
Data in this report is firstly from the Room Loads (.clg and .htg) results files and the VE model. When there is an associated ApacheHVAC file, additional data from Load run | 2020/04/11 20:36 | Room Loads - Page 1 of 4
that file is included; however, the reported values for loads and calculated design airflows in these Room Loads reports are not influenced by system operation.
HVAC Sizing IES VIRTUAL ENVIRONMENT
Room Loads Report
Zone: None Ground Floor VE 2019
System: 03 c AHU GF HVAC Methodology: ApacheHVAC
COOLING ROOM PEAK HEATING ROOM PEAK AREAS & THERMAL TRANSMITTANCE
Time of Peak (Mo/Hr:Mn) 5 / 16:30 Time of Peak (Mo/Hr:Mn) Heating Design Total Area Glazing Glazing U-value1
Outside Air (DB/WB/RH) 34.1 °C / 20.7 °C / 30.5 % Outside Air (DB/WB/RH) 15.3 °C / 9.7 °C / 49.7 % m² m² % W/m²·K
External
Room Room Net Per Floor Percent Room Net Per Floor Percent Wall (above grade) 822.5 297.0 36.1 2.73
Sensible Latent Value Area of Total Value Area of Total Below Grade Walls - - - -
Envelope Gains/Losses W W W W/m² % Envelope Gains/Losses W W W/m² % Windows2 297.0 297.0 100.0 6.32
External Walls 6,449 - 6,449 1.9 2.6 External Walls -2,471 -2,471 -0.7 4.9 Doors - - - -
Roofs 0 - 0 0.0 0.0 Roofs 0 0 0.0 0.0 Floors 3,445.5 - - 1.99
3
Ground/Exposed Floors 43,990 - 43,990 12.8 17.9 Ground/Exposed Floors -39,342 -39,342 -11.4 77.5 Roofs - - - -
External Doors 0 - 0 0.0 0.0 External Doors 0 0 0.0 0.0 COMBINED 4,268.0 297.0 7.0 2.13
Windows Conduction 9,744 - 9,744 2.8 4.0 Windows Conduction -6,554 -6,554 -1.9 12.9 Internal
Skylights Conduction 0 - 0 0.0 0.0 Skylights Conduction 0 0 0.0 0.0 Ceilings 3,445.5 - - 1.07
Solar 12,031 - 12,031 3.5 4.9 Solar 0 0 0.0 0.0 Floors - - - -
Infiltration 7,162 -5,572 1,590 0.5 0.6 Infiltration -3,975 -3,975 -1.2 7.8 Partitions4 - - - -
Nat/Aux Vent 0 0 0 0.0 0.0 Nat/Aux Vent 0 0 0.0 0.0 1
Area-weighted U-value; 2 Windows/glazing include glass and frames;
3
Internal Building Gains/Losses Internal Building Gains/Losses Roofs incl. skylights; 4 Partitions incl. internal windows and doors.
Internal Walls/Openings 0 - 0 0.0 0.0 Internal Walls/Openings 0 0 0.0 0.0
Internal Floors 0 - 0 0.0 0.0 Internal Floors 0 0 0.0 0.0 TEMPERATURES & SETPOINTS
Internal Air & Furniture 0 - 0 0.0 0.0 Internal Air & Furniture 0 0 0.0 0.0 Cooling Heating
Ceilings 2,907 - 2,907 0.8 1.2 Ceilings 1,547 1,547 0.4 -3.0 °C °C
Supply Air (design) 12.8 32.2
Sub Total 82,283 -5,572 76,711 22.3 Sub Total -50,795 -50,795 -14.7 Room Setpoint (design) 23.9 21.1
Room (actual) 24.0 21.1
Internal Gains Internal Gains Mean Radiant Temperature 26.8 20.4
Lights 40,796 - 40,796 11.8 16.6 Lights 0 0 0.0 0.0 Dry Resultant Temperature 25.4 20.8
People 50,489 40,391 90,880 26.4 37.0 People 0 0 0.0 0.0 RH (Design Max Setpoint) (%) 70.0 70.0
Misc, Computers, Equip 37,087 0 37,087 10.8 15.1 Misc, Computers, Equip 0 0 0.0 0.0
Sub Total 128,373 40,391 168,764 49.0 Sub Total 0 0 0.0 AIRFLOW
Cooling Heating
TOTAL 210,655 34,819 245,474 71.2 100 TOTAL -50,795 -50,795 -14.7 100 l/s l/s
Supply (design) 15,504 4,651
COOLING SUMMARY HEATING SUMMARY Reheat Minimum (design) 4,651 4,651
Leakage at Design Flow 0 0
Sensible cooling load (W): 210,655 Sensible heating load (W): 50,795
Ventilation (requirement) 3,446 3,446
Latent cooling load (W): 34,819 Design zone air temp for Supply Airflow calculation (°C): 21.1
Exhaust (requirement) - -
Sensible heat ratio: 0.86
Infiltration 559 559
Design Supply Airflow calculated per: Sensible Loads
Design zone air temp for Supply Airflow calculation (°C): 23.9
CHECKS
Data in this report is firstly from the Room Loads (.clg and .htg) results files and the VE model. When there is an associated ApacheHVAC file, additional data from Load run | 2020/04/11 20:36 | Room Loads - Page 2 of 4
that file is included; however, the reported values for loads and calculated design airflows in these Room Loads reports are not influenced by system operation.
HVAC Sizing IES VIRTUAL ENVIRONMENT
Room Loads Report
Zone: None Third Floor VE 2019
System: 03 c AHU TF HVAC Methodology: ApacheHVAC
COOLING ROOM PEAK HEATING ROOM PEAK AREAS & THERMAL TRANSMITTANCE
Time of Peak (Mo/Hr:Mn) 5 / 14:30 Time of Peak (Mo/Hr:Mn) Heating Design Total Area Glazing Glazing U-value1
Outside Air (DB/WB/RH) 35.1 °C / 21.0 °C / 28.9 % Outside Air (DB/WB/RH) 15.3 °C / 9.7 °C / 49.7 % m² m² % W/m²·K
External
Room Room Net Per Floor Percent Room Net Per Floor Percent Wall (above grade) 822.5 297.0 36.1 2.73
Sensible Latent Value Area of Total Value Area of Total Below Grade Walls - - - -
Envelope Gains/Losses W W W W/m² % Envelope Gains/Losses W W W/m² % Windows2 297.0 297.0 100.0 6.32
External Walls 5,846 - 5,846 1.7 2.5 External Walls -2,596 -2,596 -0.8 11.3 Doors - - - -
Roofs 39,315 - 39,315 11.4 16.5 Roofs -10,060 -10,060 -2.9 44.0 Floors - - - -
3
Ground/Exposed Floors 0 - 0 0.0 0.0 Ground/Exposed Floors 0 0 0.0 0.0 Roofs 3,445.5 - - 0.36
External Doors 0 - 0 0.0 0.0 External Doors 0 0 0.0 0.0 COMBINED 4,268.0 297.0 7.0 0.82
Windows Conduction 11,885 - 11,885 3.4 5.0 Windows Conduction -6,639 -6,639 -1.9 29.0 Internal
Skylights Conduction 0 - 0 0.0 0.0 Skylights Conduction 0 0 0.0 0.0 Ceilings - - - -
Solar 11,730 - 11,730 3.4 4.9 Solar 0 0 0.0 0.0 Floors 3,445.5 - - 1.07
Infiltration 7,494 -5,572 1,922 0.6 0.8 Infiltration -3,975 -3,975 -1.2 17.4 Partitions4 - - - -
Nat/Aux Vent 0 0 0 0.0 0.0 Nat/Aux Vent 0 0 0.0 0.0 1
Area-weighted U-value; 2 Windows/glazing include glass and frames;
3
Internal Building Gains/Losses Internal Building Gains/Losses Roofs incl. skylights; 4 Partitions incl. internal windows and doors.
Internal Walls/Openings 0 - 0 0.0 0.0 Internal Walls/Openings 0 0 0.0 0.0
Internal Floors -1,732 - -1,732 -0.5 -0.7 Internal Floors 382 382 0.1 -1.7 TEMPERATURES & SETPOINTS
Internal Air & Furniture 0 - 0 0.0 0.0 Internal Air & Furniture 0 0 0.0 0.0 Cooling Heating
Ceilings 0 - 0 0.0 0.0 Ceilings 0 0 0.0 0.0 °C °C
Supply Air (design) 12.8 32.2
Sub Total 74,537 -5,572 68,965 20.0 Sub Total -22,887 -22,887 -6.6 Room Setpoint (design) 23.9 21.1
Room (actual) 24.0 21.1
Internal Gains Internal Gains Mean Radiant Temperature 26.6 20.9
Lights 40,796 - 40,796 11.8 17.2 Lights 0 0 0.0 0.0 Dry Resultant Temperature 25.3 21.0
People 50,489 40,391 90,880 26.4 38.2 People 0 0 0.0 0.0 RH (Design Max Setpoint) (%) 70.0 70.0
Misc, Computers, Equip 37,087 0 37,087 10.8 15.6 Misc, Computers, Equip 0 0 0.0 0.0
Sub Total 128,373 40,391 168,764 49.0 Sub Total 0 0 0.0 AIRFLOW
Cooling Heating
TOTAL 202,910 34,819 237,729 69.0 100 TOTAL -22,887 -22,887 -6.6 100 l/s l/s
Supply (design) 14,934 4,480
COOLING SUMMARY HEATING SUMMARY Reheat Minimum (design) 4,480 4,480
Leakage at Design Flow 0 0
Sensible cooling load (W): 202,910 Sensible heating load (W): 22,887
Ventilation (requirement) 3,446 3,446
Latent cooling load (W): 34,819 Design zone air temp for Supply Airflow calculation (°C): 21.1
Exhaust (requirement) - -
Sensible heat ratio: 0.85
Infiltration 559 559
Design Supply Airflow calculated per: Sensible Loads
Design zone air temp for Supply Airflow calculation (°C): 23.9
CHECKS
Data in this report is firstly from the Room Loads (.clg and .htg) results files and the VE model. When there is an associated ApacheHVAC file, additional data from Load run | 2020/04/11 20:36 | Room Loads - Page 3 of 4
that file is included; however, the reported values for loads and calculated design airflows in these Room Loads reports are not influenced by system operation.
HVAC Sizing IES VIRTUAL ENVIRONMENT
Room Loads Report
Zone: None Second Floor VE 2019
System: 03 c AHU SF HVAC Methodology: ApacheHVAC
COOLING ROOM PEAK HEATING ROOM PEAK AREAS & THERMAL TRANSMITTANCE
Time of Peak (Mo/Hr:Mn) 5 / 15:30 Time of Peak (Mo/Hr:Mn) Heating Design Total Area Glazing Glazing U-value1
Outside Air (DB/WB/RH) 34.8 °C / 20.9 °C / 29.4 % Outside Air (DB/WB/RH) 15.3 °C / 9.7 °C / 49.7 % m² m² % W/m²·K
External
Room Room Net Per Floor Percent Room Net Per Floor Percent Wall (above grade) 822.5 297.0 36.1 2.73
Sensible Latent Value Area of Total Value Area of Total Below Grade Walls - - - -
Envelope Gains/Losses W W W W/m² % Envelope Gains/Losses W W W/m² % Windows2 297.0 297.0 100.0 6.32
External Walls 6,549 - 6,549 1.9 3.2 External Walls -2,637 -2,637 -0.8 19.2 Doors - - - -
Roofs 0 - 0 0.0 0.0 Roofs 0 0 0.0 0.0 Floors - - - -
3
Ground/Exposed Floors 0 - 0 0.0 0.0 Ground/Exposed Floors 0 0 0.0 0.0 Roofs - - - -
External Doors 0 - 0 0.0 0.0 External Doors 0 0 0.0 0.0 COMBINED 822.5 297.0 36.1 2.73
Windows Conduction 11,312 - 11,312 3.3 5.5 Windows Conduction -6,667 -6,667 -1.9 48.5 Internal
Skylights Conduction 0 - 0 0.0 0.0 Skylights Conduction 0 0 0.0 0.0 Ceilings 3,445.5 - - 1.07
Solar 12,954 - 12,954 3.8 6.3 Solar 0 0 0.0 0.0 Floors 3,445.5 - - 1.07
Infiltration 7,494 -5,572 1,922 0.6 0.9 Infiltration -3,975 -3,975 -1.2 28.9 Partitions4 - - - -
Nat/Aux Vent 0 0 0 0.0 0.0 Nat/Aux Vent 0 0 0.0 0.0 1
Area-weighted U-value; 2 Windows/glazing include glass and frames;
3
Internal Building Gains/Losses Internal Building Gains/Losses Roofs incl. skylights; 4 Partitions incl. internal windows and doors.
Internal Walls/Openings 0 - 0 0.0 0.0 Internal Walls/Openings 0 0 0.0 0.0
Internal Floors 1,446 - 1,446 0.4 0.7 Internal Floors -62 -62 0.0 0.5 TEMPERATURES & SETPOINTS
Internal Air & Furniture 0 - 0 0.0 0.0 Internal Air & Furniture 0 0 0.0 0.0 Cooling Heating
Ceilings 3,075 - 3,075 0.9 1.5 Ceilings -418 -418 -0.1 3.0 °C °C
Supply Air (design) 12.8 32.2
Sub Total 42,829 -5,572 37,257 10.8 Sub Total -13,758 -13,758 -4.0 Room Setpoint (design) 23.9 21.1
Room (actual) 24.0 21.1
Internal Gains Internal Gains Mean Radiant Temperature 25.8 21.1
Lights 40,796 - 40,796 11.8 19.8 Lights 0 0 0.0 0.0 Dry Resultant Temperature 24.9 21.1
People 50,489 40,391 90,880 26.4 44.1 People 0 0 0.0 0.0 RH (Design Max Setpoint) (%) 70.0 70.0
Misc, Computers, Equip 37,087 0 37,087 10.8 18.0 Misc, Computers, Equip 0 0 0.0 0.0
Sub Total 128,373 40,391 168,764 49.0 Sub Total 0 0 0.0 AIRFLOW
Cooling Heating
TOTAL 171,201 34,819 206,020 59.8 100 TOTAL -13,758 -13,758 -4.0 100 l/s l/s
Supply (design) 12,600 3,780
COOLING SUMMARY HEATING SUMMARY Reheat Minimum (design) 3,780 3,780
Leakage at Design Flow 0 0
Sensible cooling load (W): 171,201 Sensible heating load (W): 13,758
Ventilation (requirement) 3,446 3,446
Latent cooling load (W): 34,819 Design zone air temp for Supply Airflow calculation (°C): 21.1
Exhaust (requirement) - -
Sensible heat ratio: 0.83
Infiltration 559 559
Design Supply Airflow calculated per: Sensible Loads
Design zone air temp for Supply Airflow calculation (°C): 23.9
CHECKS
Data in this report is firstly from the Room Loads (.clg and .htg) results files and the VE model. When there is an associated ApacheHVAC file, additional data from Load run | 2020/04/11 20:36 | Room Loads - Page 4 of 4
that file is included; however, the reported values for loads and calculated design airflows in these Room Loads reports are not influenced by system operation.