Local hardware configuration: 3 voltage outputs must be activated as phase-to-earth voltages. 1 trip command and the signal 'f<> Warning' must be routed to separate binary inputs. Note: For this application example the warning signals of all protective functions are routed to a binary relay output as a group signal ('S-Warning'). Settings in the test module: In the ‘State Sequencer’ module the trip times of the 4 frequency elements are tested one after another. The inserted test steps ‘Healthy 1 … 5’ guarantee a safe reset of the relay after each trip. Note: During the test all 3 voltages must be set to nominal voltage and be symmetrical, in order to