Professional Documents
Culture Documents
The comparison of SFRA results measured under different conditions could be one of the
possible reasons for getting the wrong SFRA results assessment. Attention must be given to some
factors, which are influencing the response of the SFRA traces. This paper will describe how to
identify those different factors and avoid their influence on the SFRA plots. Without this
knowledge, it is often very critical or even impossible to distinguish between measurement
mistakes and real damage inside the tested transformer.
SFRA is a powerful diagnostic tool because SFRA trace represents a fingerprint of a transformer
winding’s construction and physical position within the main tank of the transformer. Therefore,
if the SFRA trace deviates from a baseline trace, then it is probable that some components of the
transformer are physically changed or the test was not repeated in the same way as the first time.
Some of the following factors are influencing the results:
If the maximum tap is chosen, then the whole tap changer is examined by the test. This applies to
both DETC and OLTC. Typically, the test will be carried out at a full winding position and
neutral.
Figure 4:
Bushing replacement effect on SFRA (blue trace – new bushing, red trace – old bushing, 110 kV)
Measurement direction
One of the important details that should be included in the SFRA test report is on which terminal
the signal is being injected and from which terminal the response signal is being measured (e.g.
H1-H0 injection or H0-H1 injection). If not specified otherwise, it is recommended to connect
the generator signal on the phase terminal and measure response on the neutral terminal.
Comparing measurements made on the same side of the power transformer but in different
directions, discrepancies in the higher frequencies, as shown in Figure 5. could be visible.
There is no influence of measurement voltage in higher frequencies. The higher frequency region
is influenced by the condition of the winding which can be considered as a liner system and in
principle remains unaffected by the output voltage. When a measurement is repeated on the same
test object, it must be ensured that the same measurement voltage is used. Otherwise, there will
be deviations in the low-frequency range that might lead to the wrong conclusion.
To eliminate any influence of the grounding system on the SFRA results, the grounding braids
should be always connected using the shortest path following the body of the bushing. This way
of connecting is especially important for the repeatability of the traces in the high-frequency
ranges.
Figure 9: Proper
braid connection – left figure, bad braid connection – right figure (electrical contact between
braid and terminal)
Figure 10: Red trace – electrical
contact between braid and terminal, black trace – proper connection
If the tertiary delta connection is made outside the tank and earthed, for better phase comparison
(in case of no other reference measurement available) the earth connection should be removed
leaving the delta connection intact. Otherwise, the capacitive couplings among windings will be
different for each phase, resulting in a very significant difference between the responses of three
phases in the middle frequency ranges.
Conclusion
Not always the transformer is tested under the same conditions and if this is the case, the
conditions have to be properly documented to allow a reliable interpretation and to reproduce
repeatable measurements. Therefore, it is important to recognize measurement on-site mistakes
and to repeat the questionable tests after finishing the required corrections.
Substation bus-bar connections (e.g., was the busbar disconnected or connected to the
bushing terminals when the measurement was performed).
A high deviation in temperature can cause a minor shift of the resonances within the
whole frequency range. The temperature differences cause changes in winding resistance
and hence the amplitude of the frequency response.
All connections from the transformer except the tank ground should be removed.
The contacts of the bushings should be cleaned, and the connection clamps must be
tightened firmly to assure reliable electrical contact.
Three shielded coaxial cables should be the same length.
Aluminum ground braids should not have electrical contact with the terminal contacts.
Aluminum ground braids must have low inductance, with a large surface, and be made of
many small wires to reduce the skin effect at higher frequencies.
Aluminum ground braids connection to the base of the bushing (transformer tank is the
reference potential) should be as short as possible.
Contact between braid and tank must be solid to get reliable results.
Detailed information about the test setup should be stored together with the test data.
Detailed photos of the connection setup are recommended as well.
The oil temperature does not affect the results considerably, but it is recommended to be
documented.
To get the most suitable measuring conditions, the characteristic impedance of the
measuring cables must be adjusted to fit the input impedance of the measuring instrument
(usually a 50 Ohm impedance is widely accepted).
The experience has shown that in many cases, the condition of the tertiary winding
(open/closed), during measurements in the primary or secondary windings could change
the responses.
To download the .pdf format of this article, please log in and visit the following link. Literature
and copyrights are stated in the original document.