You are on page 1of 9

Introduction

The comparison of SFRA results measured under different conditions could be one of the
possible reasons for getting the wrong SFRA results assessment. Attention must be given to some
factors, which are influencing the response of the SFRA traces. This paper will describe how to
identify those different factors and avoid their influence on the SFRA plots. Without this
knowledge, it is often very critical or even impossible to distinguish between measurement
mistakes and real damage inside the tested transformer.

SFRA is a powerful diagnostic tool because SFRA trace represents a fingerprint of a transformer
winding’s construction and physical position within the main tank of the transformer. Therefore,
if the SFRA trace deviates from a baseline trace, then it is probable that some components of the
transformer are physically changed or the test was not repeated in the same way as the first time.
Some of the following factors are influencing the results:

 Residual magnetism effect


 Tap-changer position
 Bushings condition effect
 Measurement direction
 Test voltage value
 Poor grounding and measurement lead connection
 Effect of the insulating oil
 Effects of the tertiary winding

Residual magnetism effect


The residual magnetism influences the SFRA results. It is highly recommended that the SFRA
test is performed before the DC tests on the power transformer or immediately after the
transformer core has been successfully demagnetized. The magnetized core causes the traces to
deviate (shifted to the right side) in frequencies less than 10 kHz only for the open-circuit type of
tests, as shown in Figure 1. Moreover, the trace response in this area is mostly affected by the
core. Short-circuit SFRA tests are not influenced by residual magnetism.
Figure 1: Shifting of low-frequency
core resonance to the right due to residual magnetism
(red trace – core magnetized, blue trace – core demagnetized)

Tap changer position


To compare FRA trace to a baseline measurement, the transformer must be tested in the same
tap-changer positions as the baseline measurement. Changing the tap changer position will cause
continuous changes in the curve shape over a wide frequency range, as shown in Figures 2 and 3.
It is suggested to perform measurements for each relevant phase on the lowest, highest, and
middle positions of the tap changer.

If the maximum tap is chosen, then the whole tap changer is examined by the test. This applies to
both DETC and OLTC. Typically, the test will be carried out at a full winding position and
neutral.

Figure 2: U-N open circuit test for


three different positions – DETC; position 1 blue, position 3 red, position 5 green, 235 kV
Figure 3: U-V open circuit test for
three different positions – OLTC; position 1 blue, position 9 green, position 17 red, 15.75 kV

Bushing’s condition effect


According to the relevant standards, SFRA tests must be performed with the same transformer
configuration to get repeatable results. Sometimes, different transformer bushings could be used
during factory acceptance tests and on-site tests, or for some reason, the bushings could be
replaced on the transformer during the service life. SFRA tests on different bushings may cause
differences in the high frequencies, as shown in Figure 4.

Figure 4:
Bushing replacement effect on SFRA (blue trace – new bushing, red trace – old bushing, 110 kV)

Measurement direction
One of the important details that should be included in the SFRA test report is on which terminal
the signal is being injected and from which terminal the response signal is being measured (e.g.
H1-H0 injection or H0-H1 injection). If not specified otherwise, it is recommended to connect
the generator signal on the phase terminal and measure response on the neutral terminal.
Comparing measurements made on the same side of the power transformer but in different
directions, discrepancies in the higher frequencies, as shown in Figure 5. could be visible.

Figure 5: Measurement direction


effect on frequency response (blue H1 – H0, red H0 – H1, 110 kV)

Test voltage value


As previously explained, the response of the traces in low-frequency areas can be influenced by
remanence magnetism. Furthermore, since in the low-frequency region, the frequency response
is dominated by core inductance it also depends on the output test voltages, as shown in Figure 6.

There is no influence of measurement voltage in higher frequencies. The higher frequency region
is influenced by the condition of the winding which can be considered as a liner system and in
principle remains unaffected by the output voltage. When a measurement is repeated on the same
test object, it must be ensured that the same measurement voltage is used. Otherwise, there will
be deviations in the low-frequency range that might lead to the wrong conclusion.

Figure 6: Influence of different


output voltages on SFRA traces (LV side – open circuit test)
The transformer core permeability varies with the applied voltage, which makes the SFRA
responses at low frequencies voltage-dependent. Consistent voltage is, therefore, very important
for SFRA testing. A test instrument with variable output voltage (like DV Power’s FRA500) is
suggested so that the test can be performed at the same voltage as the reference curve. FRA500
instrument offers test voltages in a range from 0.1 V up to 12 V (or 0.2 Vp-p up to 24 Vp-p).

Poor grounding and measurement leads connections


The IEC 60076-18 standard and CIGRÉ WG A2.26 guide describe the recommended procedure
for a proper and reproducible measurement setup in detail. To ensure the highest available
frequency response in a noisy environment, the standards recommend for SFRA measurement
the usage of shielded coaxial cables, which have to be grounded by wide flat aluminum braids.
The center conductor of the cable is connected to the transformer terminal while the outer
conductor is connected to the instrument chassis, which should be grounded. This practice
prevents the center conductor from picking up noise. Separate measurement leads shall be used
for each of the generator, reference, and measurement connections. Coaxial leads used for the
measurement should be the same length and have a characteristic impedance of 50 Ohm.

To eliminate any influence of the grounding system on the SFRA results, the grounding braids
should be always connected using the shortest path following the body of the bushing. This way
of connecting is especially important for the repeatability of the traces in the high-frequency
ranges.

Use the shortest ground braid connection


A large number of measurement errors occur due to inadequate shield grounding of the coaxial
cables. To ensure the repeatability of the traces, especially at the high-frequency ranges, the
shortest braid connection between the test clamp and bushing flange should be used. This is the
only way to repeat the same connection for every measurement on a given transformer.

Figure 7: Braid connection on the left bushing represents a good


grounding practice, and connection on the right bushing represents poor grounding practice
Poor grounding of the transformer tank
Figure 8: A very noisy curve in low-
frequency region indication of poor transformer grounding
The ground braid should not have electrical contact with the terminal contacts

Figure 9: Proper
braid connection – left figure, bad braid connection – right figure (electrical contact between
braid and terminal)
Figure 10: Red trace – electrical
contact between braid and terminal, black trace – proper connection

Effect of the insulating oil


Figure 11 shows the responses of the SFRA open-circuit tests performed on the HV side of the
power transformer with and without insulating oil. The higher permittivity of the oil increases the
capacitance, which means that the whole curve will be shifted towards lower frequencies since
all the stray capacitances are increased by about the same factor. Changes in the frequency
responses are expected in case the same transformer was tested in different conditions (e.g. was
the transformer originally tested without the main tank insulating fluid and then later tested with
the insulating fluid, was the transformer tested with the main tank filled with different types of
insulating fluid, etc.). Such information should always be noted in the final test report.

Figure 11: HV open-circuit test


with oil-filled (blue trace) and unfilled (red trace) transformer tank

Effects of the tertiary winding


The phases of star-connected windings are only connected at the neutral (star-point), while the
phases of a delta-connected winding are directly linked at the line terminals. This direct coupling
has a profound influence on the frequency response of the phases of a transformer with a delta
winding particularly in the frequency region dominated by the interaction between windings.
Figure 12 shows the measurement results of the windings of the power transformer with the
tertiary delta connection grounded and ungrounded.

If the tertiary delta connection is made outside the tank and earthed, for better phase comparison
(in case of no other reference measurement available) the earth connection should be removed
leaving the delta connection intact. Otherwise, the capacitive couplings among windings will be
different for each phase, resulting in a very significant difference between the responses of three
phases in the middle frequency ranges.

Figure 12: Open circuit test on


LV side (black trace – tertiary grounded, red trace – tertiary ungrounded)

Conclusion
Not always the transformer is tested under the same conditions and if this is the case, the
conditions have to be properly documented to allow a reliable interpretation and to reproduce
repeatable measurements. Therefore, it is important to recognize measurement on-site mistakes
and to repeat the questionable tests after finishing the required corrections.

Attention should be paid to the following :

 Substation bus-bar connections (e.g., was the busbar disconnected or connected to the
bushing terminals when the measurement was performed).
 A high deviation in temperature can cause a minor shift of the resonances within the
whole frequency range. The temperature differences cause changes in winding resistance
and hence the amplitude of the frequency response.
 All connections from the transformer except the tank ground should be removed.
 The contacts of the bushings should be cleaned, and the connection clamps must be
tightened firmly to assure reliable electrical contact.
 Three shielded coaxial cables should be the same length.
 Aluminum ground braids should not have electrical contact with the terminal contacts.
 Aluminum ground braids must have low inductance, with a large surface, and be made of
many small wires to reduce the skin effect at higher frequencies.
 Aluminum ground braids connection to the base of the bushing (transformer tank is the
reference potential) should be as short as possible.
 Contact between braid and tank must be solid to get reliable results.
 Detailed information about the test setup should be stored together with the test data.
Detailed photos of the connection setup are recommended as well.
 The oil temperature does not affect the results considerably, but it is recommended to be
documented.
 To get the most suitable measuring conditions, the characteristic impedance of the
measuring cables must be adjusted to fit the input impedance of the measuring instrument
(usually a 50 Ohm impedance is widely accepted).
 The experience has shown that in many cases, the condition of the tertiary winding
(open/closed), during measurements in the primary or secondary windings could change
the responses.

To download the .pdf format of this article, please log in and visit the following link. Literature
and copyrights are stated in the original document.

You might also like