When defining the test sequence of the active protective functions in the OCC, the following steps are recommended. · Step 1: Testing the protective functions which only use voltage measurements (e.g. voltage, frequency, etc.). · Step 2: Testing the protective functions which only use current measurements (e.g. OVL, DIFF, I2, etc.). · Step 3: Testing the protective functions which use voltage and current measurements (e.g. reverse power, underexcitation, etc.). In the OCC the test modules can be summarized in folders (groups) to structure the test document. Voltage measurements only Current measurements only