You are on page 1of 108

Slide 1

DUCT DESIGN
Slide 2
Slide 3

• CONVEY AIR AS DIRECTLY AS POSSIBLE AT THE


PERMISSIBLE VELOCITIES TO OBTAIN THE DESIRED
RESULTS WITH MINIMUM NOISE AND GREATEST
ECONOMY OF POWER , MATERIAL AND SPACE.

• AVOID SUDDEN CHANGES IN AIR DIRECTION OR


VELOCITY. WHEN SUDDEN CHANGES ARE
NECESSARY AT BENDS, USE TURNING VANES TO
MINIMISE THE PRESSURE LOSS.
Slide 4

• WHERE THE GREATEST AIR CARRYING CAPACITY PER


SQUARE FOOT OF SHEET METAL IS DESIRED, MAKE
RECTANGULAR DUCTS AS NEARLY SQUARE AS
POSSIBLE. AVOID ASPECT RATIO GREATER THAN 8:1.
WHERE POSSIBLE MAINTAIN A RATIO OF 4:1 OR LESS.

• DUCTS SHOULD BE CONSTRUCTED OF SMOOTH


MATERIAL E.G. STEEL OR ALUMINUM SHEET METAL.
FOR OTHER MATERIALS ALLOW FOR CHANGE IN
ROUGHNESS.
Slide 5

• SELECT FANS AND MOTORS TO PROVIDE FOR A


SAFETY FACTOR BECAUSE OF VARIATIONS IN
SMOOTHNESS OF MATERIALS, TYPES OF JOINTS
USED, AND THE ABILITY TO FABRICATE THE SYSTEM
IN ACCORDANCE WITH THE DESIGN.

• AVOID OBSTRUCTING DUCT WITH PIPING,


CONDUITS, OR STRUCTURAL MEMBERS
Slide 6
Slide 7
Slide 8
Slide 9
Slide 10
Slide 11
Slide 12
Slide 13
Slide 14
Slide 15

• Total Pressure – The TP of the air at any point in


the system is a measure of the available energy

• TP = SP + VP

• Static Pressure – The Static Pressure is a measure


of the potential energy at any point in the system.
It is the pressure in a duct which results from the
frictional resistance to air flow
Slide 16

• Static pressure –
–“Collapsing pressure” if it is less than
the atmospheric pressure
–“Bursting pressure” if it is more than
the atmospheric pressure
Slide 17

• Velocity Pressure – The Velocity Pressure is a


measure of the kinetic energy and is defined as the
pressure required to take air from rest and
accelerating it to the velocity in the duct.

• The total pressure which a fan must be able to


create includes the VP plus the total of all frictional
resistances in the system
Slide 18

• FAN Total Pressure – The difference between the


total pressure at the fan outlet and the total
pressure at the fan inlet.

• Fan Static Pressure – the difference between the


FTP and the velocity pressure at the fan outlet
Slide 19

BASIC CONCEPTS OF ENERGY CHANGES


• TP = SP + VP
• ENERGY LOSS CORRESPONDS TO FALL IN TP
• VP is always greater than 0, in the direction of
airflow
• FTP = (TP at fan outlet) – (TP at fan inlet)
• FSP = (SP at fan outlet) – (TP at fan inlet)
• FSP = FTP – (VP at fan outlet)
Slide 20
Slide 21
Slide 22

• VP has not changed


Slide 23

• If the velocity of airflow in a duct is constant,


then VP is constant.

• Losses of energy appears as fall in static


pressure
Slide 24

Consider the flow


of air between two
sections 1 and 2 of
an insulated duct
Slide 25
Slide 26

• Usually PZ1 - PZ2 = negligible

•  SP1 + VP1 + P blower= SP2 + VP2 + PL

Pressure drop in ducts


•Duct friction – frictional loss
•Dynamic losses –
Change in direction and
Change in cross sectional area
Slide 27
Slide 28

Where
Slide 29
Slide 30
Slide 31
Slide 32
Slide 33
Slide 34

• Air accelerated as it approaches the opening,


forming a vena contracta inside the duct. Area
changes from infinity to duct area.

• In such a case the dynamic loss coefficient is 0.85.

• By making a formed entrance the dynamic loss


coefficient can be reduced to 0.03.
Slide 35

• THE DISCHARGE OF AIR FROM THE A DUCT SYSTEM.


• Air in the plane of the open end of the discharge duct
must be virtually atmospheric pressure – since there is
no longer any resisting force to prevent equalization
of pressure.

• The potential energy of the air leaving the system


through an open end is zero. However Kinetic energy
is not zero.

• If a grille or diffuser is placed over the open end of the


duct on its upstream side must be greater than that
on its downstream side by an amount equal to the
frictional loss incurred by the flow of air through the
grille.
Slide 36

• TP1 = TP2 + frictional loss past the grille

• VP1 + SP1 = VP2 + SP2+ frictional loss past the


grille

• Since VP1 = VP2

• Hence SP1 -SP2= frictional loss part the grille

• SP2 - virtually the same as atmospheric pressure

• SP1 - frictional loss past the grille


Slide 37

• PRESSURE LOSS IN DIVIDED FLOW FITTINGS:

• Whenever air is diverted to a branch, there is a


velocity reduction in the straight through section.

• If there is no loss the change in velocity pressure is


completely converted into regain in static pressure.
Slide 38

• However due to dynamic loss, the actual static


pressure regain is reduced by the static regain
factor, R.

The total pressure loss becomes,


• PL = (1-R)(PV1 – PV2)

For branch offs, the values of the dynamic loss


coefficient based on branch velocities are
available.
Slide 39
Slide 40
Slide 41
Slide 42
Slide 43
Slide 44
Slide 45

• AIRFLOW THROUGH A GRADUALLY EXPANDING


DUCTS E.G. AN IDEAL EXPANSION PIECE.
• NO LOSSES
• TP1 = TP2
• 100% STATIC REGAIN
• IF THERE ARE LOSSES DUE TO FRICTION AND
TURBULENCE
• THEN TP1  TP2
• TP = TP1 – TP2
• TP = (SP1 + VP1) – (SP2 + VP2)
• ACTUAL STATIC REGAIN
= SP2 – SP1 = VP1 – VP2 - TP
Slide 46
Slide 47

• Total pressure loss expressed in terms of


upstream velocity pressure.
Slide 48

• Air flow through an abruptly reducing duct.

Two places where turbulence occurs

• The shoulders of contraction

• Shortly after the neck, formation of a vena


contracta
Slide 49
Slide 50
Slide 51
Slide 52
Slide 53

• GRADUALLY REDUCING DUCT.

• Losses in this case is quite small

• Usual to express the loss as a fraction of the


downstream velocity pressure

• No possibility of static regain


Slide 54

• Energy required to accelerate flow

• Fall in static pressure occasioned by the losses at


the vena contracta and losses resulting from skin
friction.

• TP = TP1 – TP2

• TP = (SP1 + VP1) – (SP2 + VP2)

• This fall is not recoverable


Slide 55
Slide 56

• Very large R/W ratio means that flow will be


gradually turned and less turbulence.

• But if bend is very gradual, then it is expensive and


occupies a very large amount of space and
unsightly in appearance.
Slide 57
Slide 58
Slide 59
Slide 60
Slide 61
Slide 62
Slide 63

• Problem 1- A bend for a duct is 1800 mm wide and

350 mm high. The center line radius to width ratio

is unity. Determine the best position for the

insertion of TWO splitters.


Slide 64
Slide 65
Slide 66
Slide 67
Slide 68
Slide 69
Slide 70
Slide 71
Slide 72
Slide 73
Slide 74
Slide 75

FAN is used to:


• Accelerate the air outside the system from rest to
the velocity at the air intake.
• Offset the energy losses resulting from any
turbulence and friction as the air enters the
system.
• Overcome the frictional resistance offered by each
item in the system
• Offset the resistance in the duct
Slide 76

• Nullify the frictional resistances presented by the


inlet louvres and discharge grilles.

• Offset any pockets of turbulence set up anywhere


in the system

• Offset the kinetic energy loss from the system at


the exits
Slide 77
Slide 78
Slide 79
Slide 80
Slide 81
Slide 82

DUCT DESIGN METHODS


Duct design methods for HVAC systems and for
exhaust systems conveying vapors, gases, and
smoke

• The equal-friction method

• The static regain method,

• The T-method.
Slide 83

• Equal friction and static regain are non-optimizing


methods
• The T-method is a practical optimization method
introduced by Tsal et al. (1988).

• To ensure that system designs are acoustically


acceptable, noise generation should be analyzed and
sound attenuators and/or acoustically lined duct
provided where necessary.
Slide 84

Equal-Friction Method

• In the equal-friction method, ducts are sized for a


constant pressure loss per unit length. The shaded
area of the friction chart (see Figure 9) is the
suggested range of friction rate and air velocity.
Slide 85

Figure 9. Friction Chart for Round Duct (ρ = 1.20 kg/m3 and ε = 0.09 mm)
Slide 86

METHODOLOGY:
• Decide what pressure drop will be available
• Compute the equivalent length of all runs (Sum of
all length of straight ducts plus the equivalent
length of fittings)
• Calculate the pressure drop per unit length for
longest run
• With same pressure drop per unit length and flow
rate in each section select the duct size of all those
sections
• For remaining sections, select the size to use the
available pressure drop but stay within velocities
appropriate for noise reductions.
Slide 87

• Note: for free exit conditions may have to calculate


the pressure drop for other runs and then
determine diameter etc…
Slide 88

• When energy cost is high and installed ductwork


cost is low, a low-friction-rate design is more
economical.

• For low energy cost and high duct cost, a higher


friction rate is more economical.

• After initial sizing, calculate total pressure loss for


all duct sections, and then resize sections to
balance pressure losses at each junction.
Slide 89

VELOCITY REDUCTION METHOD

• VRM: The main duct is designed as above.


Arbitrary reductions are made in the air
velocity as we move down the duct run.

• Equivalent diameters are then found from


the friction chart.
Slide 90

Static Regain Method

• This design method is only applicable to supply air

systems. The objective is to obtain the same static

pressure at diverging flow junctions by changing

downstream duct sizes.


Slide 91

• The principle of the SRM is to maintain a constant


static pressure before each terminal and each
branch. Achieved by sizing the duct in such a
manner that after each branch or outlet, the static
gain due to a reduction in velocity exactly balances
the pressure drop in the succeeding duct section.
Slide 92

• This design objective can be developed by


rearranging Equation (7a) and setting ps,2 equal to
ps,1 (neglecting thermal gravity effect term). This
means that the change in static pressure from one
section to another is zero, which is satisfied when
the change in total pressure is equal to the change
in velocity pressure
Slide 93
Slide 94

• Total Pressure Balancing. After completing duct


sizing by the static regain method, any residual
unbalance can be reduced or eliminated by
calculating the system’s total pressure and
changing duct sizes or fittings in other paths to
increase the paths’ total pressure to approximate
what is needed in the critical paths.
Slide 95

T-method
• T-method optimization (Tsal et al. 1988) is a
dynamic programming procedure
Slide 96

• Ductwork sizes are determined by minimizing the


objective function:
where
• E = present-worth owning and operating cost
• Ep = first-year energy cost
• Es = initial cost
• PWEF = present worth escalation factor (Smith
1968), dimensionless
Slide 97

The following constraints are necessary for duct


optimization (Tsal and Adler 1987):

• Continuity.
• Pressure balancing.
• Nominal duct size.
• Air velocity restriction.
• Construction restriction.
Slide 98

• T-method simulation, developed by Tsal et al.


(1990), determines the flow in each duct section
of an existing system with a known operating
fan performance curve.
Slide 99
Slide 100

• Study the building plans, and arrange supply and


return outlets to provide proper distribution of air
in each space. Adjust calculated air quantities for
duct heat gains or losses and duct leakage. Also,
adjust supply, return, and/or exhaust air quantities
to meet space pressurization requirements.
Slide 101

• Select outlet sizes from manufacturers’ data.

• Sketch the duct system, connecting supply outlets


and return intakes with the air-handling units/air
conditioners. Use rigid round ducts, minimize the
number of fittings, and avoid close-coupled fittings
because little is known about the resulting loss
coefficients. If space is restricted and a properly
designed round duct is too large, the next best
option to minimize leakage and pressure losses is
to use flat oval ductwork. Multiple runs of round
duct should also be considered.
Slide 102

• Divide the system into sections and number each


section. A duct system should be divided at all
points where flow, size, or shape changes. Assign
fittings to the section toward the supply and
return (or exhaust) terminals.
Slide 103

• Size ducts by the selected design method.


Calculate system total pressure loss; then select
the fan
• Lay out the system in detail. If duct routing and
fittings vary significantly from the original design,
recalculate pressure losses. Reselect the fan if
necessary.
Slide 104

• Resize duct sections to approximately balance


pressures at each junction.

• Analyze the design for objectionable noise levels,


and specify lined duct, double-wall duct, and
sound attenuators as necessary.
Slide 105

• The Actual System


2009 ASHRAE Handbook -- Fundamentals (SI)
Slide 106

• The Actual
2009 ASHRAE Handbook -- Fundamentals (SI)
System
Slide 107

2009 ASHRAE Handbook -- Fundamentals (SI)


Slide 108

REFERENCES
• Engineering Thermodynamics by Rogers and
Mayhew
• 2009 ASHRAE Handbook – Fundamentals
• 2010 ASHRAE Handbook - Refrigeration
• Principles of Refrigeration by Roy J Dossat
• Refrigeration and Air Conditioning by G F Hundy, A.
R. Trott and T. C. Welch
• Thermodynamics – An Engineering Approach –
Cengel & Boles
• Air Conditioning Engineering – W P Jones

You might also like