You are on page 1of 2

Client:

Project:
Tag Number:
Service:
Model:

Please provide response/s under TQ #: 1

QUERY ITEM #1
TQ1: Please provide the following information regarding the Query Date: 02-May-2019
following queries:

1. The required water flow rate is only 86 m 3/h,


but the minimum flow rate you quoted is 3900
L/min (234 m3/h). Please recommend a model
that is economical enough to handle the
required capacity.

2. The hot water temperature specified in your


quotation is 37 deg. C., but the inlet
temperature needed to be cooled I s at least 50
deg. C. Please confirm if your models can
handle a temperature range of 50 – 70 deg. C.

3. Please specify the following information:


a. Dry Bulb Temperature
b. Relative Humidity
c. Drift Loss
d. Structural Info
- Wind Velocity the structure is designed
for.
- Seismic Factor
- Elevation Above Sea Level

4. Please specify the driver details:


a. Driver Type. We require TEFC.
b. Number of Motors.
c. Fan Motor Speed
d. Phase. We require 3.
e. Voltage. We require 440.
f. Cycle. We require 60 hz.

5. Please specify the fan details:


a. Number of fans.
b. Fan Type. We require axial.
c. Number of Fan Blades.
d. Fan Tip Speed.

6. Please specify the materials of the following:


a. Filler Material. We require plastic
b. Basin Material. We require fiber glass.
c. Structural Members Materials. We require
galvanized carbon steel.
d. Fan Blade Material. We require aluminium.

7. Please give inlet/outlet nozzle specifications.


We require FF for inlet, RF for outlet, and 150#
ASME 16.5 for both nozzles.

Response 1:

OTHER INFORMATION
Prepared by:
Company:
Attachment #