DUCT SIZE CALCULATOR (SI)

A. AIR VOLOUME (L/s) 934


W H
B. DUCT SIZE (MM) 660 305
C. DUCT MATERIAL GALVANISED
D. ABS ROUGHNESS(mm) 0.15
E. EQUIVALAENT DIAMETER (MM) 481.6
F. HYDRAULIC DIAMETER (MM) 417.2
G. DUCT VELOCITY (m/s) 4.6
H. VELOCITY PRESSURE (Pa) 13.0
I. REYNOLDS NO.(Re) 128,534
J. FRICTION FACTOR (f) 0.01872
K. DUCT FRICTION (Pa/ M) 0.582

For this calculation pleae check only duct friction &


height factor

HEIGHT AS PER AVAILABILITY OF SPACE.


DUCT FRICTION AS PER RECOMMENDED VALUE.

ONLY INPUT YELLOW FIGURE.


DON'T CHANGE ANY OTHER VALUE OR FORMULAE.

A= 9.3845E+20
B= 2.7911E-09
f= 0.01916846
DUCT SIZE CALCULATOR (IP)

A. AIR VOLOUME (CFM) 4000


W H
B. DUCT SIZE (INCH) 40 16
C. DUCT MATERIAL GALVANISED
D. ABS ROUGHNESS (ft) 0.0005
E. EQUIVALAENT DIAMETER (INCH) 27.0
F. HYDRAULIC DIAMETER (INCH) 22.9
G. DUCT VELOCITY (FPM) 900.0
H. VELOCITY PRESSURE (Inch) 0.050
I. REYNOLDS NO.(Re) 176,091
J. FRICTION FACTOR (f) 0.01749
K. DUCT FRICTION (Inch/ 100 FT) 0.046

For this calculation pleae check only duct friction & height
factor

HEIGHT AS PER AVAILABILITY OF SPACE.


DUCT FRICTION AS PER RECOMMENDED VALUE.

ONLY INPUT YELLOW FIGURE.


DON'T CHANGE ANY OTHER VALUE OR FORMULAE.

A= 3.680645E+21
B= 1.812365E-11
f= 0.0161594951
1219.2