You are on page 1of 3

Application Note

Case study – Analysing sound and vibration on a


turbine-generator set
This case study illustrates the successful step-by-step approach followed in separating vibration
signals from sound signals suddenly emitted by a turbine–generator machine group in a power plant.
Using a vibration sensor and a microphone, a portable instrument and a PM software programme, the
source of the high-pitched sound and the cause of the apparent fault were identified.

Fig. 2: The bearing pedestal and coupling


Fig. 1: The troublesome turbine-generator
between turbine and generator
machine group

The background and analytical measurement


After many years of relatively trouble-free
approach
operation in the power plant, the generating set
suddenly began emitting a loud, high-pitched
A decision was made to carry out an urgent
sound from somewhere in the area of the
investigation into the cause of the loud whistling
coupling and bearing pedestal between the
noise in the area of the coupling and bearing
turbine and the generator. This caused some
pedestal between the turbine and generator,
alarm because of the apparent proximity
shown in figure 2 above, from where the noise
between the sound location and the bearing
seemed to emanate, because any delay in the
pedestal between the turbine and the generator.
investigation could have resulted in severe and
expensive damage and a protracted shutdown of
Clearly if the bearing was damaged it had to be
the set. Since there was no backup power
identified as quickly as possible so that the
generating set, the plant would have to rely on
shutdown of the set, organisation of the
purchased power, at much higher cost, for the
maintenance specialists, ordering of the
duration of the repair.
necessary spare parts and the repair could be
scheduled immediately.
Because the set was not equipped with a
permanent vibration monitoring system there
were no permanently-installed non-contacting
sensors to which the portable vibration analyser
could be connected. Therefore it was not
possible to be able to conduct an analysis of the
relative shaft vibrations of either the
1
turbine or generator. An initial vibration
measurement had to be carried out at the
bearing pedestal between the generator and
turbine using an acceleration sensor to
investigate whether the noise was being caused
by damage to the journal bearing. Bearing Generator
pedestal housing
This type of damage can cause a loud high-
pitched noise because of possible damage to the
surface material of the bearing which can result
in the bearing running dry. Figure 3 below shows
the resulting vibration velocity spectrum which
reveals no apparent damage to the bearing. The
only significant components were at 50 and 100
Hz as can be expected from a machine group of
Fig. 4: Structure-borne vibration spectra from the
this type.
generator housing and bearing pedestal.

Note the interesting structure-borne vibration


component at approx. 9.6 kHz in the generator
housing spectrum in figure 4 above. This is the
only significant component in the high-frequency
audio range.

Generator
housing
Fig. 3: Initial structure-borne vibration
measurement from the bearing pedestal Bearing
pedestal

On the basis of this spectrum measurement, and


because of the high-frequency of the noise, it
was decided that air-borne sound measurements
would be acquired, using a microphone, at both Fig. 5: Air-borne sound spectra from the
the bearing pedestal and the generator housing. generator housing and bearing pedestal areas.
This because it is often extremely difficult to tell
the direction of the source of an air-borne sound,
especially in an industrial environment where the In the air-borne sound spectra above, apart from
signal may be reflected by the surrounding the low frequency turbine noise at 50 and 100
machine housings and building walls and roof. Hz only the components at 9.6 kHz and 10.2 kHz
are in the high-frequency audible range. The 9.6
In addition because it is also common for an air- kHz component coincided with the 9.6 kHz
borne sound signal to excite components of the component of structure-borne vibration in the
machine into mechanical vibrations, the decision spectrum of figure 4 above, suggesting that the
was made that structure-borne vibration air-borne sound signal was also exciting a
measurements, using an acceleration sensor mechanical vibration of the generator housing.
should also be acquired at the bearing pedestal
and generator housing.

A correlation of the air-borne sound and the


structure-borne vibrations signals would then be
made to see any relationship between them.

2
taking place at any point on the generator
housing.
Structure-
borne It was therefore presumed that this was a noise
vibration caused by streaming taking place through the
cooling tubes of the generator. On the basis of
Air-
the measurement results and the assumptions
borne
sound made, the customer decided it was not
necessary to effect an immediate shutdown and
made the decision to continue to run the
generating set until the next scheduled
shutdown.

The eventual finding


Fig. 6: A composite of the structure-borne
vibration signal and air-borne sound signal from During the course of the maintenance at the next
the generator. planned shutdown the generator was dismantled
and the cooling system was examined. This
examination revealed that a sealing component
From the composite diagram in figure 6 it had loosened and caused a partial blockage of
became evident that the 9.6 kHz components three of the cooling tubes, restricting the
are congruent with the structure-borne sound diameter of the tubes, thus acting like an organ
signal (acceleration) at the generator housing pipe and resulting in the sudden onset of the
and the air-borne sound signal at the generator high-frequency noise.
housing. This confirmed that the high-pitched
sound was being emitted by the generator. The analysis procedure which resulted in making
the correct decision concerning the criticality of
the problem emphasises that it is important, in
Estimation of danger potential for the the case of an unusual problem such as this, to
machine draw upon the full range of measurement and
analysis options that are available to determine
Although the 9.6 kHz component is clearly the source of the fault.
visible as a structure-borne vibration component
from the generator, a mechanical rub of some A correlation of the two types of spectra –
type between the generator rotor and stator, vibration and sound – and thermal
which could cause a vibration and such a high- measurements quickly and efficiently revealed
frequency audible sound, was discounted since that the machine set was not in any apparent
there was no partial heating danger and could continue to operate, thus
preventing an unnecessary panic shutdown and
resultant loss of production.

Brüel & Kjær Vibro A/S Brüel & Kjær Vibro GmbH E-mail: info@bkvibro.com
2850 Nærum – Denmark 64293 Darmstadt – Germany Internet: www.bkvibro.com
Tel.: +45 4580 0500 Tel.: +49 (0) 6151 428 1100
Fax: +45 4580 2937 Fax: +49 (0) 6151 428 1200 BAN0037-EN-11
3

You might also like