Professional Documents
Culture Documents
Michael Czarick With all inlets closed turn on approximately 1 cfm per square foot of exhaust
The University of Georgia
fan capacity…measure the resulting pressure
very poor More than 1.2 ft2 /1,000 ft2 (0.05” or lower)
marginal Between 1.2 and 0.6 ft2 /1,000 ft2 (0.06” – 0.13”)
good Between 0.6 and 0.4 ft2 /1,000 ft2 (0.14” – 0.22”)
outstanding Less than 0.4 ft2 /1,000 ft2 (0.23” or higher)
1
If we use the spreadsheet we can see specifically what the
Let’s start with a “very poor ” house (0.05” or lower) challenge will be…
Total required opening area for specified fan(s) @ 0.10" (ft2) 26.7 1 cfm per square foot of floor space of timer fan capacity or less.
Total house leakage area (ft2) 26.5
40’ X 500’ house = 20,000 ft2
Total required inlet area @ 0.10" (ft2) 0.2
20,000 ft2 = 20,000 cfm
Percentage of air that will entering through inlets 1% This amount of fan capacity will be operated off an interval timer based on air
Approximate required air inlet opening size/height (inches) 0.01 quality
Even if you are using partial house brooding… Input the number of inlets to be used…25
2
All/nearly all the inlets on nonbrooding end should be
closed For instance:
If there are no bird in an area of a house we really don’t need to ventilate it A 40’ X 500’ house has 25,000 birds
much if at all Minimum ventilation rate of 1,900 cfm (75 cfm/1,000 chicks)
Most importantly leaving inlets open on the nonbrooding end reduces the Two 36” fans (18,000 cfm) are used for minimum ventilation
amount of fresh air the fans are bringing into the brooding end of the house One on brooding end, one on nonbrooding end
Inlets opened/closed on nonbrooding end Next input the size of the inlets…
Total required opening area for specified fan(s) @ 0.10" (ft2) 26.7
Total house leakage area (ft2) 26.5
Brooding end Nonbrooding end
Total required inlet area @ 0.10" (ft2) 0.2
1,700 cfm 200 cfm
Minimum Ventilation Inlet Opening Requirements: Minimum Ventilation Inlet Opening Requirements:
Minimum ventilation fan capacity (cfm) 20000 Minimum ventilation fan capacity (cfm) 20000
Number of air inlets to be used 25 Number of air inlets to be used 25
Maximum air inlet height/opening (inches) 6.0 Maximum air inlet height/opening (inches) 6.0
Air inlet length (inches) 48.0 Air inlet length (inches) 48.0
Total side wall air inlet area (ft2) 50.0 Total side wall air inlet area (ft2) 50.0
Total required opening area for specified fan(s) @ 0.10" (ft2) 26.7 Total required opening area for specified fan(s) @ 0.10" (ft2) 26.7
Total house leakage area (ft2) 26.5 Total house leakage area (ft2) 26.5
Total required inlet area @ 0.10" (ft2) 0.2 Total required inlet area @ 0.10" (ft2) 0.2
Percentage of air that will entering through inlets 1% Percentage of air that will entering through inlets 1%
Approximate required air inlet opening size/height (inches) 0.02 Approximate required air inlet opening size/height (inches) 0.02
3
These houses are basically too loose to effectively use
“Very poor ” houses (0.05” or lower) side wall inlets for minimum ventilation
When the timer fans operate they are bringing in air…
Total required opening area for specified fan(s) @ 0.10" (ft2) 40.0
Total house leakage area (ft2) 26.5
Total required inlet area @ 0.10" (ft2) 13.5
For example…increase minimum ventilation fan capacity to 1.5 cfm/ft2… Percentage of air that will entering through inlets 34%
Approximate required air inlet opening size/height (inches) 1.62
73.2°F
4
Example of too much fan capacity coming on at one time
If it is 30oF outside and 80oF inside (fans start operating)
1 cfm/ft2 (30 seconds/300) will cause a 5.3oF decrease in house temperature 100.0°F
100
1.5 cfm/ft2 (30 seconds/300) will lead to a 7.9oF decrease in house
temperature 95
90
85
80
As a general rule we want to use a few timer fans as possible so as to not
shock the house with a lot of cold air (1 cfm/ft2 or less).
75.0°F
Example of too much fan capacity coming on at one time Example of too much fan capacity coming on at one time
(+15 seconds) (+30 seconds)
100.0°F 100.0°F
100 100
95 95
90 90
85 85
80 80
75.0°F 75.0°F
It is important to keep in mind that since the house is not very tight, even
with circulation fans, the house will have a significantly higher heating costs
than a properly tight house.
But, crack ventilation can perform reasonably well if the producer is willing to
spend enough on fuel.
5
“Very poor ” houses (0.05” or lower) Moderately tight (0.06” – 0.13”)
Side wall inlets should be used during second/third stage ventilation Marginal houses…
(temperature control). 0.06” – crack ventilate
0.13” – inlet ventilate
Will we get the cold air from the side wall all the way to the center of the Inlet design:
house? What direction is the air moving when it enters the house?
6
Does the inlet direct the incoming air upward or
outward when open a small amount? Upward….
34.0°C
Outward:
30
It will more likely make it
to the center of the house
25
95.0°F
95
20
15 90
15.0°C
85
Typically between 2” to 3”
to obtain optimal direction
Inlets low in the side wall will make more difficult to To get inlets installed low in the side wall to perform,
get air to the center of the house with small openings inlet openings typically need to be larger
90.0°F
90
80
100.0°F
100
70
90
80 60
69.4
70
60.0°F
50.0°F
Sometimes 3” or more
7
Inlets close to the ceiling tend to perform better with Ceiling inlets will also tend to perform better than those
small openings… located lower in the side wall with small openings
Because the air attaches to the ceiling sooner
Galvanized ceiling inlet with 1 1/2” opening For a surface mounted ceiling inlet…
Sometimes a 1” opening will work
8
Surface mounted ceiling inlet with a “rough” ceiling Surface mounted ceiling inlet with a “rough” ceiling
and a small inlet opening and a large inlet opening
If the obstruction is small and not But the closer it is to the inlet
close to the inlet the the bigger the potential problem
disruption is minimal
9
Even if it relatively small Once a house is built these three factors typically
don’t change:
Inlet design
Inlet placement
Ceiling smoothness
But, there are three other factors that managers can change that will affect
inlet performance:
Static pressure
Inlet opening
Temperature difference
It is best to keep everything off the ceiling within at least 8’ of the side wall
Entrance speed vs. Static pressure Entrance speed vs. Static pressure
2,000
1,800
1,600
Air Velocity (ft/min)
1,400
1,200
1,000
800
600
400
200
0
0
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.2
Static pressure (“)
Typical entrance velocity will be between 900 and 1,400 ft/min
In general low static pressures result in lower entrance But precisely far will the air moving into the house at
velocities and reduced air-jet travel distance different static pressures?
Higher static pressures will result in higher entrance velocities… There are some guidelines out there…
Which in turn will result in increased travel distances into the house before House Width Operating Air speed Distance before
the air moves to the floor. Pressure the air drops
33’ (10 m) 0.04” (8 Pa) 700 ft/min (3.5 m/sec) 16’ (5 m)
39’ (12 m) 0.05” (10 Pa) 800 ft/min (4 m/sec) 20’ (6 m)
49’ (15 m) 0.08” (17 Pa) 1,000 ft/min (5 m/sec) 25’ (7.5 m)
59’ (18 m) 0.10” (26 Pa) 1,260 ft/min (6.3 m/sec) 30’ (9 m)
69’ (21 m) 0.15” (37 Pa) 1,500 ft/min (7.5 m/sec) (10.5 m)
79’ (24 m) 0.17” (42 Pa) 1,600 ft/min (8 m/sec) (12 m)
10
There is much more to inlet performance than most people Inlet performance is as much of a science as nutrition or
realize… genetics…
There are dozens and dozens of theoretical inlet performance equations
Theoretical inlet performance equation: Theoretical air inlet performance vs. Static Pressure
Xd=1.1(CdAo)0.5(Bg((Tr-Tj)/CdAo).5 (Vcc)-2 Xd=1.1(CdAo)0.5(Bg((Tr-Tj)/CdAo).5 (Vcc)-2
Air jet detachment distance vs. Static pressure 40’ wide house
Detachment distance:
How far will the air travel before it detaches from the ceiling and start moving toward
the floor/birds.
40’ wide house = 20’?
Xd
Xd
11
We don’t necessarily have to get the air jet to the center of
Air jet detachment distance vs. Static pressure the house before detaching
20 Depending on house width and ceiling height 5’ or 10’ from the center of the
18 house is often acceptable
Detachment Distance (ft)
16
Wider houses a little sooner
14
Taller houses a little sooner
12
10
8
6
4
2
0
0
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
0.11
0.12
0.13
0.14
Static Pressure (") Xd
40’ wide house Air jet detachment distance vs. Static pressure
20
18
Detachment Distance (ft)
16
14
12
10
8
6
4
2
0
0
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
0.11
0.12
0.13
0.14
Static Pressure (")
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
0.11
0.12
0.13
0.14
0.12” = minimum
12
Air jet detachment distance vs. Static pressure Theoretical air inlet performance vs. Static Pressure
20 Xd=1.1(CdAo)0.5(Bg((Tr-Tj)/CdAo).5 (Vcc)-2
18
Detachment Distance (ft)
16
14 Assumptions:
12 Inlet is located at the ceiling…
Table indicates 20’
10 Air enters parallel to the ceiling…
8 Ceiling is smooth…
6
Air inlet is 48” long…
4
2” inlet opening…
2
0 80oF inside air temperature and
40oF outside air temperature.
0
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
0.11
0.12
0.13
0.14
Air detachment distance vs. Outside temperature Theoretical air inlet performance vs. Outside temperature
The greater the difference between inside and outside temperature the Assumptions: 100.0°F
greater the difference in the density of the air and the quicker it will tend to Static pressure = 0.12”
fall. Inlet is located at the ceiling… 80
20% 60.0°F
Air inlet is 48” long…
15%
2” inlet opening…
10% 80oF inside air temperature
5%
0%
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
Temperature difference (F)
Air jet detachment distance vs. Outside temperature Air jet detachment distance vs. Outside temperature
20 20
18 18
Detachment Distance (ft)
16 16
14 14
12 12
10 10
8 8
6 6
4 4
2 2
0 0
20 25 30 35 40 45 50 55 60 65 70 20 25 30 35 40 45 50 55 60 65 70
Outside Temperature (F) Outside Temperature (F)
13
So what is the reason for the difference between the table
Air jet detachment distance vs. Outside temperature and the equation?
30 Xd=1.1(CdAo)0.5(Bg((Tr-Tj)/CdAo).5 (Vcc)-2
28
26 House Width Operating Air speed Distance before
Detachment Distance (ft)
24
22 Pressure the air drops
20 33’ (10 m) 0.04” (8 Pa) 700 ft/min (3.5 m/sec) 16’ (5 m)
18
16 39’ (12 m) 0.05” (10 Pa) 800 ft/min (4 m/sec) 20’ (6 m)
14 49’ (15 m) 0.08” (17 Pa) 1,000 ft/min (5 m/sec) 25’ (7.5 m)
12
10 59’ (18 m) 0.10” (26 Pa) 1,260 ft/min (6.3 m/sec) 30’ (9 m)
8 69’ (21 m) 0.15” (37 Pa) 1,500 ft/min (7.5 m/sec) (10.5 m)
6
4 79’ (24 m) 0.17” (42 Pa) 1,600 ft/min (8 m/sec) (12 m)
2
0 The table is based on the assumption that there is no temperature difference
20 25 30 35 40 45 50 55 60 65 70 between outside and inside
Outside Temperature (F) “isothermal air-jet”
Air jet detachment distance vs. Static pressure Air jet detachment distance vs. Static pressure
(40oF outside – 80oF inside) (40oF outside and 70oF outside)
30 30
Detachment Distance (ft)
25 25
20 20
15 15
10 10
5 5
0 0
0
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
0.11
0.12
0.13
0.14
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
0.11
0.12
0.13
0.14
Static Pressure (") Static Pressure (")
40 F 40 F 70 F
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.11
0.12
0.13
0.14
0
0.1
14
Inside and outside temperature difference… Moderately tight (0.06” – 0.13”)
Plays a major role in air inlet performance Marginal houses…(warm weather)
0.06” – inlet ventilate
0.13” – inlet ventilate
How does inlet opening affect inlet performance? Air detachment distance Vs. Inlet opening
The larger the inlet opening the further the air will tend to throw before
detaching.
Theoretical air inlet performance Vs. Inlet opening 40’ wide house – 15’ detachment distance
Assumptions:
Static pressure = 0.12”
Inlet is located at the ceiling…
Air enters parallel to the ceiling…
Ceiling is smooth…
Air inlet is 48” long…
80oF inside air temperature and
40oF Outside temperature
15
Theoretical air inlet performance Vs. Inlet opening Theoretical air inlet performance
20 20
18 18
Detachment Distance (ft)
2” or greater…no problem
Will a 1.6” inlet opening work? Theoretical air inlet performance Vs. Inlet opening
20
18
Detachment Distance (ft)
16
14
12
10
8
6
4
2
Will we get the cold air from the side wall all the way to the center of the 0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
house?
Inlet open (")
Will we get the cold air from the side wall all the way to the center of the
house?
Maybe not to the center but it is likely to be good enough
16
With relatively small inlet openings (< 2”)… Fewer inlets…larger openings…improved direction
it is often best to latch closed ½ of the inlets on the brooding end of the Better throw
house to create a minimum ventilation inlet system to obtain a 2”+ during
cold weather
Minimum Ventilation Inlet Opening Requirements:
Minimum ventilation fan capacity (cfm) 20000
Number of air inlets to be used 14
Maximum air inlet height/opening (inches) 6.0
Air inlet length (inches) 48.0
Total side wall air inlet area (ft2) 28.0
Total required opening area for specified fan(s) @ 0.10" (ft2) 26.7
Total house leakage area (ft2) 13.0
Total required inlet area @ 0.10" (ft2) 13.7
If we use only half the inlets will we have big variations in Typically the variation is minimal if alternate inlets are
house conditions? closed (1/2 on each side of the house) and…
16 16
14 14
12 12
10 10
8 8
6 6
4 30 4
2 28 2
26
0 0
Detachment Distance (ft)
24
0 0.5 1 1.5 2 2.5 3 22
3.5 4 4.5 5 20 25 30 35 40 45 50 55 60 65 70
20
Inlet open (") 18 Outside Temperature (F)
16
14
12
10
8
6
4
2
0
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
Pressure (")
17
To determine what combination of inlet opening and static pressure Evaluating air inlet performance using tape installed along
will be required to get the incoming air to the center of the house… the ceiling
Will always require a little experimentation!
Place survey tape 5’ from the side wall, 10’ from the side wall and 5’ from the peak of
the ceiling
16 16
14 14
12 12
10 10
8 30 8
6 28 6
26
4 4
Detachment Distance (ft)
24
2 22 2
20
0 18 0
0 0.5 1 1.5 2 2.5 3 3.5
16 4 4.5 5 20 25 30 35 40 45 50 55 60 65 70
Inlet open (") 14 Outside Temperature (F)
12
10
8
6
4
2
0
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
Pressure (")
18
Wider house using all side wall inlets…proper inlet, proper pressure,
small inlet opening, low in the side wall, rough ceiling Cold side walls…warm center
95.0°F 95.0°F
90 90
70.2
80 80
70 70
60.7
60.0°F 60.0°F
Closed 2/3 of the inlets to obtain a larger opening Closed 2/3 of the inlets to obtain a larger opening
95.0°F 95.0°F
90 90
80 80
70.0
70 70
67.3
60.0°F 60.0°F
19
Not obtaining optimal throw of cold incoming air Not obtaining optimal throw of cold incoming air
100.0°F 100.0°F
100 87.1 100
90.7
95 95
90 90
85 85
75.5
80.0
80.0°F 80.0°F
Another example.. Not obtaining optimal throw of cold incoming air (center)
100.0°F 100.0°F
100 100
95 95
90 90
85 85
92.9
88.3 84.2
75.6 80 80
75.0°F 75.0°F
95
90
90
85
80 80
75
72.0°F
70.0°F
20
What about our very tight houses? House tightness spreadsheet
good Between 0.6 and 0.4 ft2 /1,000 ft2 (0.14” – 0.22”)
outstanding Less than 0.4 ft2 /1,000 ft2 (0.23” or higher)
Total required opening area for specified fan(s) @ 0.10" (ft2) 26.7
Total house leakage area (ft2) 7.8
Total required inlet area @ 0.10" (ft2) 18.9
Very tight house using a single 36” fan and 12 side wall air
Something else to consider for very tight houses inlets
The house may be tight enough to use less than 1 cfm/ft2 of exhaust fan
capacity for timer fans Minimum Ventilation Inlet Opening Requirements:
Minimum ventilation fan capacity (cfm) 11000
Number of air inlets to be used 12
Maximum air inlet height/opening (inches) 6.0
Air inlet length (inches) 48.0
Total side wall air inlet area (ft2) 24.0
Total required opening area for specified fan(s) @ 0.10" (ft2) 14.7
Total house leakage area (ft2) 7.8
Total required inlet area @ 0.10" (ft2) 6.9
For instance using a single 36” fan with a very tight brooding curtain Percentage of air that will entering through inlets 47%
Approximate required air inlet opening size/height (inches) 1.72
21
A single 36” fan on an interval timer would operate twice as
long as two 36” fans Or possibly two 24” fans could be used
One on the brooding end…one on the nonbrooding end
Reducing the downtime between fan cycles thereby creating a more uniform
environment.
22