Fundamental criteria for Plate and Frame Heat Exchanger design calculation Sl No
19
20
21
ow To Find Cold Fluid Outlet Temperature
Circuit Parameter
ow To Find Vapour Flow Rate Requirement To Achieve Required Outlet Temperature Of The Cold Fluid.
Circuit Parameter
Cold Side (Cane Juice) Mass Flow Rate
Cold Side (Cane Juice) Specific Heat
Cold Side (Cane Juice) Inlet Temperature
Cold Side (Cane Juice) Outlet Temperature Required
Cold Side (Cane Juice) Heat Exchanged
Hot Side (Saturated Vapour) Temperature Of Vapour
Hot Side (Saturated Vapour) Latent Heat Of Vapour
Hot Side (Saturated Vapour) Heat Exchanged
Hot Side (Saturated Vapour) Vapour Flow Rate
Area Equals
Area Equals
Symbol/ Formula Uom Values
C Hot KCal/Kg/°C 1
T In °C 75
T Out °C 50
H = Q Hot * C Hot * (T In – T Out) KCal/Hr 3,000,000.00
Q Cold Kg/Hr 160000
C Cold KCal/Kg/°C 0.93
T In °C 35
H = Q Cold * C Cold * (T Out – T In) KCal/Hr 3,000,000.00
T Out = T In + [H /(Q Cold x C Cold)] °C 53.749891016259