You are on page 1of 3

Basic concepts of Plate Type Heat Exchanger How To Find Cold Fluid Outlet Temperat

Fundamental criteria for Plate and Frame Heat Exchanger design calculation Sl No

In the design of PHE mainly required two types of parameters –   a) Process


1
parameter     b) Geometrical data
Process parameters : In heat exchanger mainly done heat exchanged from 2
hot fluid to cold fluid
Hot fluid parameters 3
Flow rate 4
Inlet temperature 5
Outlet temperature 6
Density 7
Thermal conductivity 8
Specific heat 9
Fouling factor 10
Cold fluid parameters
Flow rate How To Find Vapour Flow Rate Requirem
Inlet temperature Sl No
Outlet temperature 1
Density 2
Thermal conductivity 3
Specific heat 4
Fouling factor 5
Geometrical data 6
Length of plate 7
Width of plate 8
Corrugation angle 9
Plate thickness
How To Find Plate Type Heat Exchanger
Plate enhancement factor S.No
Amplitude of corrugation 1
Flow configuration 2
The Overall heat transfer coefficient (OHTC) is very impotent factor in the 3
design of plate type heat exchange design
OHTC units – Kcal / hr/m2/ °C or Kw/m2/ °C, 4
It is mainly depends upon the following parameters 5
a) Cold fluid film resistance 6
b) Hot fluid film resistance 7
c) Plate resistance – According to MOC (material of construction) of the plate 8
d) Resistance of scale. ( fouling factor) 9
e) Velocity of hot and cold fluid inside the heaters 10
11
12
13
14
15
16
17
18

19

20
21
ow To Find Cold Fluid Outlet Temperature
Circuit Parameter

 Hot Side (Hot Water)  Mass Flow Rate

 Hot Side (Hot Water)  Specific Heat

 Hot Side (Hot Water)  Inlet Temperature


 Hot Side (Hot Water)  Outlet Temperature
 Hot Side (Hot Water)  Heat Exchanged
 Cold Side (Cane Juice)  Mass Flow Rate
 Cold Side (Cane Juice)  Specific Heat
 Cold Side (Cane Juice)  Inlet Temperature
 Cold Side (Cane Juice)  Heat Exchanged
 Cold Side (Cane Juice)  Outlet Temperature

ow To Find Vapour Flow Rate Requirement To Achieve Required Outlet Temperature Of The Cold Fluid.
Circuit Parameter
 Cold Side (Cane Juice)  Mass Flow Rate
 Cold Side (Cane Juice)  Specific Heat
 Cold Side (Cane Juice)  Inlet Temperature
 Cold Side (Cane Juice)  Outlet Temperature Required 
 Cold Side (Cane Juice)  Heat Exchanged
 Hot Side (Saturated  Vapour)  Temperature Of Vapour
 Hot Side (Saturated  Vapour)  Latent Heat Of Vapour
 Hot Side (Saturated  Vapour)  Heat Exchanged
 Hot Side (Saturated  Vapour)  Vapour Flow Rate

ow To Find Plate Type Heat Exchanger Heat Transfer Area


Circuit Parameter
 Hot Side (Hot Water)  Mass Flow Rate
 Hot Side (Hot Water)  Specific Heat
 Hot Side (Hot Water)  Inlet Temperature
 Hot Side (Hot Water)  Outlet Temperature
 Hot Side (Hot Water)  Heat Exchanged
 Cold Side (Cane Juice)  Mass Flow Rate
 Cold Side (Cane Juice)  Specific Heat
 Cold Side (Cane Juice)  Inlet Temperature
 Cold Side (Cane Juice)  Outlet Temperature
 Cold Side (Cane Juice)  Heat Exchanged
 Hot Side (Hot Water)  ∆T
 Cold Side (Cane Juice)  ∆T
 Hot Side (Hot Water) &  Cold Side (Cane Juice)  ∆T1
 Hot Side (Hot Water) &  Cold Side (Cane Juice)  ∆T2
 Logarithmic Mean Temperature Difference - LMTD LMTD
 Heat Transfer Coefficient
 Heat Exchanged By Hot Fluid
 Heat Exchanged By Cold Fluid

 Heat Exchanged Is Also Equals

Area Equals
Area Equals
Symbol/ Formula Uom  Values

 Q Hot  Kg/Hr 120000

 C Hot  KCal/Kg/°C 1

 T In  °C 75
 T Out  °C 50
 H = Q Hot * C Hot * (T In – T Out)  KCal/Hr 3,000,000.00
 Q Cold  Kg/Hr 160000
 C Cold  KCal/Kg/°C 0.93
 T In  °C 35
 H = Q Cold * C Cold * (T Out – T In)  KCal/Hr 3,000,000.00
 T Out = T In + [H /(Q Cold x C Cold)]  °C 53.749891016259

Symbol/ Formula Uom  Values


 Q Cold  Kg/Hr 270000
 C Cold  KCal/Kg/°C 0.95
T In  °C 95
T Out  °C 110
 H = Q Cold x C Cold x (T Out – T In)  KCal/Hr 3847500
 T Hot  °C 112
 λ (As Per Steam Table)  KCal/Kg/°C 531
 H = Q Cold x C Cold x (T Out – T In)  KCal/Hr 3847500
 Q Hot = H / λ  (Not Considered Sensible Heat Of  Kg/Hr 7245.7627118644
Condensate)

Symbol/ Formula Uom  Values


 Q Hot  Kg/Hr 120000
 C Hot  KCal/Kg/°C 1
 T In  °C 75
 T Out  °C 55
 Q Hot x C Hot x (T In – T Out)  KCal/Hr 2400000
 Q Cold  Kg/Hr 160000
 C Cold  KCal/Kg/°C 0.93
 T In  °C 35
 T Out  °C 51
 Q Cold x C Cold x (T Out – T In)  KCal/Hr 2380800
T Hot In - T Hot Out  °C 20
T Cold Out - T Cold In  °C 16
T Hot In - T Cold Out  °C 24
T Hot Out - T Cold In  °C 20
 (∆T1 – ∆T2) / [Ln(∆T1 / ∆T2)]  °C 21.939259790988
K  KCal/Hr/M2/oC 1800
 Q Hot x C Hot x (T In – T Out)  KCal/Hr 2400000
 Q Cold x C Cold x (T Out – T In)  KCal/Hr 2380800

K *  Area * LMTD  KCal/Hr

[Q Hot x C Hot x (T In – T Out)]/[K * LMTD] M2 60.773852264652


[Q Cold x C Cold x (T Out – T In)]/[K * LMTD] M2 60.287661446534