PARAMETER MANUAL
2013-04
5012602604- CPP4
: The parameter can be set during operation.
1) After settings are done, users can record parameters in the "Note" blank.
2) For more parameter setting, please refer to user manual.
NOTE IM: Induction Motor; PM: Permanent Magnet Motor
Group 0 Drive Parameters
Factory
Parameters Functions Settings Note
Setting
4: 230V, 1HP (0.75kW)
5: 460 V, 1HP (0.75kW)
6: 230V, 2HP (1.5kW)
7: 460 V, 2HP (1.5kW)
8: 230V, 3HP (2.2kW)
9: 460 V, 3HP (2.2kW)
10: 230V, 5HP (3.7kW)
11: 460 V, 5HP (3.7kW)
12: 230V, 7.5HP (5.5kW)
13: 460 V, 7.5HP (5.5kW)
14: 230V, 10HP (7.5kW)
15: 460V, 10HP (7.5kW)
16: 230V, 15HP (11kW)
17: 460V, 15HP (11kW)
18: 230V, 20HP (15kW)
19: 460V, 20HP (15kW)
20: 230V, 25HP (18.5kW)
21: 460V, 25HP (18.5kW)
22: 230V, 30HP (22kW)
23: 460V, 30HP (22kW)
24: 230V, 40HP (30kW) Read
00-00 Identity Code of the
25: 460V, 40HP (30kW) only
AC Motor Drive
26: 230V, 50HP (37kW)
27: 460V, 50HP (37kW)
28: 230V, 60HP (45kW)
29: 460V, 60HP (45kW)
30: 230V, 75HP (55kW)
31: 460V, 75HP (55kW)
32: 230V, 100HP (75kW)
33: 460V, 100HP (75kW)
34: 230V, 125HP(90kW)
35: 460V, 125HP (90kW)
37: 460V, 150HP (110kW)
39: 460V, 175HP(132kW)
41: 460V, 215HP(160kW)
43: 460V, 250HP(185kW)
45: 460V, 300HP(220kW)
47: 460V, 375HP(280kW)
49: 460V, 425HP(315kW)
51: 460V, 475HP(355kW)
53: 460V, 536HP(400kW)
93: 460V, 5.5HP (4.0kW)
Display AC Motor Read
00-01 Display by models
Drive Rated Current only
0: No function
1: Read only
5: Reset KWH display to 0.
6: Reset PLC (including
CANopen Master Index)
7: Reset CANopen Index
00-02 Parameter Reset (Slave) 0
9: All parameters are reset to
factory settings(base
frequency is 50Hz)
10: All parameters are reset
to factory settings (base
frequency is 60Hz)
0: F (frequency command)
1: H (output frequency)
Start-up Display
00-03 2: U (multi-function display, 0
Selection
see Pr.00-04)
3: A (output current)
EN_2
Factory
Parameters Functions Settings Note
Setting
0: Display output current (A)
1: Display counter value (c)
2: Display actual output
frequency (H.)
3: Display DC-BUS voltage
(v)
4: Display output voltage (E)
5: Display output power
angle (n)
6: Display output power in
kW (P)
8: Display estimate output
torque % (t)
10: Display PID feedback in
% (b)
11: Display AVI1 in % (1.)
12: Display ACI in % (2.)
13: Display AVI2 in % (3.)
14: Display the temperature
of IGBT in ℃ (i.)
15: Display the temperature
of capacitance in ℃(c.)
16: The status of digital input
(ON/OFF) (i)
17: The status of digital
output (ON/OFF) (o)
Multi-function 18: Multi-step speed (S)
00-04 Display (user 19: The corresponding CPU 3
defined) pin status of digital
input(d.)
20: The corresponding CPU
pin status of digital output
(0.)
25: Overload counting
(0.00~100.00%)(h.)
26: Ground Fault GFF
(Unit:%)(G.)
27: DC Bus voltage ripple
(Unit: Vdc)(r.)
28: Display PLC data D1043
(C)
30: Display output of user
defined (U)
31: H page x Pr.00-05
Display user Gain(K)
34: Operation speed of fan
(%) (F.)
37: Reserved
38: Display drive status (6.)
41: KWH display, unit
KWH(J)
42: PID Reference, unit %
(L.)
43: PID offset, unit (%) (o.)
44: PID Output frequency,
unit: Hz (b.)
Coefficient Gain in
00-05 Actual Output 0~160.00 1.00
Frequency
00-06 Software Version Read-only #.#
Parameter 0~65535
00-07 Protection 0~4: Recording # of times 0
Password Input of password attempts
EN_3
Factory
Parameters Functions Settings Note
Setting
0 ~ 65535
Parameter 0: No password protection /
00-08 Protection password is entered 0
Password Setting correctly (Pr00-07)
1: Parameter is locked
00-09
~ Reserved
00-10
0:VF(V/F control)
Velocity Control
00-11 2: SVC(Sensor-Less Vector 0
Mode
Control)
00-12
~ Reserved
00-15
0: Normal load
00-16 Load Selection 0
1: Heavy load
00-17 Carrier Frequency 2~15kHz LD: 1~20hp
230V ND: 0.5~15HP
8
2~15kHz LD: 1~25hp
460V ND: 0.5~20HP
2~10kHz LD: 25~60hp
230V ND: 20~50hp
6
2~10kHz LD: 30~100hp
460V ND: 25~75hp
2~9kHz LD: 75~125hp
230V ND: 60~100hp
4
2~9kHz LD: 125~536hp
460V ND: 100~475hp
00-18 Reserved
PLC command
00-19 mask(SOOC, SOOF, 0~65535 0
SOTC, SOPC)
0: Digital keypad
1: RS-485 serial
communication
2: External analog input
Source of the Master (Pr.03-00)
3: External UP/DOWN
00-20 Frequency 0
terminal
Command(AUTO)
6: CANopen communication
card
EN_4
Factory
Parameters Functions Settings Note
Setting
Bit 0~3: user define on
decimal place
0000b: no decimal place
0001b: one decimal place
0010b: two decimal place
0011b: three decimal place
Bit 4~15: user define on unit
000xh: Hz
001xh: rpm
002xh: %
003xh: kg
004xH: m/s
005xH: kW
006xH: HP
007xH: ppm
008xH: 1/m
009xH: kg/s
00AxH: kg/m
00BxH: kg/h
00CxH: lb/s
00DxH: lb/m
User Defined 00ExH: lb/h
00-25 0
Characteristics 00FxH: ft/s
010xH: ft/m
011xH: m
012xH: ft
013xH: degC
014xH: degF
015xH: mbar
016xH: bar
017xH: Pa
018xH: kPa
019xH: mWG
01AxH: inWG
01BxH: ftWG
01CxH: psi
01DxH: atm
01ExH: L/s
01FxH: L/m
020xH: L/h
021xH: m3/s
022xH: m3/h
023xH: GPM
024xH: CFM
0: Disable
0000B: 0~65535 (No
decimal place in Pr.00-25
setting)
0001B: 0.0~6553.5 (One
decimal place in Pr.00-25
Max. User Defined
00-26 setting) 0
Value
0010B: 0.0~655.35(Two
decimal place in Pr.00-25
setting)
0011B: 0.0~65.536 (Three
decimal place in Pr.00-25
setting)
Read
00-27 User Defined Value Read only
Only
EN_5
Factory
Parameters Functions Settings Note
Setting
Bit0 : Sleep Function
Control
0: Cancel sleep function
1: Sleep function and
Auto mode are the
same
Switching from Bit1 : Unit of the Control
00-28 Auto mode to Hand Bit 0
mode 0: Change unit to Hz
1: Same unit as the Auto
mode
Bit2 : PID Control Bit
0: Cancel PID control
1: PID control and Auto
mode are the same.
0: Standard HOA function.
EN_6
Factory
Parameters Functions Settings Note
Setting
0: Digital keypad
1: RS-485 serial
communication
2: External analog input
Source of the Master (Pr.03-00)
3: External UP/DOWN
00-30 Frequency 0
terminal
Command(HAND)
6: CANopen communication
card
7: Reserved
8: Communication card (no
CANopen card)
0: Digital keypad
1: External terminals.
Keypad STOP disabled.
2: RS-485 serial
Source of the
communication. Keypad
00-31 Operation Command 0
STOP disabled.
(HAND)
3: CANopen communication
card
5: Communication card (not
include CANopen card)
Digital Keypad 0: STOP key disable
00-32 0
STOP Function 1: STOP key enable
00-33
~ Reserved
00-47
Display Filter Time
00-48 0.001~65.535 sec 0.100
(Current)
Display Filter Time
00-49 0.001~65.535 sec 0.100
(Keypad)
Software Version
00-50 Read only #####
(date)
00-51
~ Reserved
00-60
EN_7
Group 1 Basic Parameters
Factory
Parameters Functions Settings Note
Setting
Max. Operating 60.00/
01-00 50.00~600.00Hz
Frequency (Hz) 50.00
Motor1: Max Output 60.00/
01-01 0.00~600.00Hz
Frequency(Hz) 50.00
230V models:
Motor1: Max Output 0.0V~255.0V 220.0
01-02
Voltage (V) 460V models: 400.0
0.0V~510.0V
Mid-point Frequency 1 of
01-03 0.00~600.00Hz 3.0
Motor 1
Mid-point Voltage 1 of 230V: 0.0V~240.0V 110
01-04
Motor 1 460V: 0.0V~480.0V 220
Mid-point Frequency 2 of
01-05 0.00~600.00Hz 0.50
Motor 1
Mid-point Voltage 2 of 230V: 0.0V~240.0V 4.0
01-06
Motor 1 460V: 0.0V~480.0V 8.0
Min. Output Frequency of
01-07 0.00~600.00Hz 0.00
Motor 1
Min. Output Voltage of 230V: 0.0V~240.0V 0.0
01-08
Motor 1 460V: 0.0V~480.0V 0.0
EN_8
Factory
Parameters Functions Settings Note
Setting
Lower limit of Frequency
01-31 0.00~600.00Hz 0.00
2 setting not allowed
Upper limit of Frequency
01-32 0.00~600.00Hz 0.00
3 setting not allowed
Lower limit of Frequency
01-33 0.00~600.00Hz 0.00
3 setting not allowed
0: Output waiting
1: Zero-speed
operation
01-34 Zero-speed Mode 2: Output at 0
Minimum Frequency
(the 4th output
frequency)
Motor 2: Max Output 60.00/
01-35 0.00~600.00Hz
Frequency (Hz) 50.00
230V models:
Motor 2: Max Output 0.0V~255.0V 200.0
01-36
Voltage (V) 460V models: 400.0
0.0V~510.0V
Mid-point Frequency 1 of
01-37 0.00~600.00Hz 3
Motor 2
230V models:
Mid-point Voltage 1 of 0.0V~240.0V 110/
01-38
Motor 2 460V models: 220
0.0V~480.0V
Mid-point Frequency 2 of
01-39 0.00~600.00Hz 0.50
Motor 2
230V models:
Mid-point Voltage 2 of 0.0V~240.0V 4.0
01-40
Motor 2 460V models: 8.0
0.0V~480.0V
Min. Output Frequency of
01-41 0.00~600.00Hz 0.00
Motor 2
230V models:
Min. Output Voltage of 0.0V~240.0V 0.0
01-42
Motor 2 460V models: 0.0
0.0V~480.0V
0: normal V/F curve
1: Curve to the
01-43 V/f Curve Selection power of 1.5 0
2: Curve to the
power of 2
0: Linear accel.
/decel.
1: Auto accel., Linear
decel.
2: Linear accel., Auto
Optimal
decel.
01-44 Acceleration/Deceleration 0
3: Auto accel. /
Setting
decel.
4: Linear, stall
prevention by auto
accel./decel. (limit by
Pr.01-12 to 01-21)
Time Unit for Accel. 0: Unit: 0.01 sec
01-45 0
/Decel. and S Curve 1: Unit: 0.1sec
Pr. 01-45=0:
CANopen Quick Stop 0.00~600.00 sec
01-46 1.00
Time Pr. 01-45=1:
0.0~6000.0 sec
EN_9
Group 2 Digital Input/Output Parameters
Factory
Parameters Functions Settings Note
Setting
0: 2-wire mode, power on for
operation control
2-wire/3-wire 1: 2-wire mode 2, power on for
02-00 0
Operation Control operation control
2: 3-wire, power on for
operation control
Multi-function Input
02-01 0: No function 1
Command 1 (MI1)
1: Multi-step speed command
Multi-function Input
02-02 1/multi-step position 2
Command 2 (MI2)
command 1
2: Multi-step speed command
Multi-function Input
02-03 2/multi-step position 3
Command 3 (MI3)
command 2
3: Multi-step speed command
Multi-function Input
02-04 3/multi-step position 4
Command 4 (MI4)
command 3
4: Multi-step speed command
Multi-function Input
02-05 4/multi-step position 0
Command 5 (MI5)
command 4
Multi-function Input
02-06 5: Reset 0
Command 6 (MI6)
6: JOG command(By
Multi-function Input
02-07 KPC-CC01 or external 0
Command 7 (MI7)
control)
Multi-function Input 7: Acceleration/deceleration
02-08 0
Command 8 (MI8) speed inhibit
Input terminal of I/O 8: The 1st, 2nd
02-26 extension card acceleration/deceleration time 0
(MI10) selection
Input terminal of I/O 9: The 3rd, 4th
02-27 extension card acceleration/deceleration time 0
(MI11) selection
Input terminal of I/O
02-28 extension card 10: EF Input (Pr.07-20) 0
(MI12)
Input terminal of I/O
11: B.B input from external
02-29 extension card 0
(Base Block)
(MI13)
Input terminal of I/O
02-30 extension card 12: Output stop 0
(MI14)
Input terminal of I/O
extension card 13: Cancel the setting of
02-31 0
(MI15) optimal accel. /decel. time
EN_11
Factory
Parameters Functions Settings Note
Setting
Expansion Card
6: Zero speed, include
02-38 Output Terminal 0
STOP(Frequency command)
(MO12)
Output terminal of
02-39 the I/O extension 7: Over torque 1 0
card (MO13)
Output terminal of
02-40 the I/O extension 8: Over torque 2 0
card (MO14)
Output terminal of
02-41 the I/O extension 9: Drive is ready 0
card (MO15)
Output terminal of
10: Low voltage warning(LV)
02-42 the I/O extension 0
(Pr.06-00)
card (MO16)
Output terminal of
02-43 the I/O extension 11: Malfunction indication 0
card (MO17)
Output terminal of
12: Mechanical brake
02-44 the I/O extension 0
release(Pr.02-32)
card (MO18)
Output terminal of
13: Overheat warning
02-45 the I/O extension 0
(Pr.06-15)
card (MO19)
Output terminal of
14: Software brake signal
02-46 the I/O extension 0
indication(Pr.07-00)
card (MO20)
15: PID feedback error
16: Slip error (oSL)
17: Terminal count value
attained, does not return
to 0 (Pr.02-20)
18: Preliminary count value
attained, returns to 0
(Pr.02-19)
19: External Base Block input
(B.B.)
20: Warning output
21: Over voltage warning
22: Over-current stall
prevention warning
23: Over-voltage stall
prevention warning
24: Operation mode indication
25: Forward command
26: Reverse command
27: Output when current >=
Pr.02-33
28: Output when current
<Pr.02-33
29: Output when frequency >=
Pr.02-34 02-34)
30: Output when frequency <
Pr.02-34
31: Y-connection for the motor
coil
32: △-connection for the
motor coil
33: Zero speed (actual output
frequency)
34: Zero speed include
stop(actual output frequency)
35: Error output selection
1(Pr.06-23)
EN_12
Factory
Parameters Functions Settings Note
Setting
36: Error output selection
2(Pr.06-24)
37: Error output selection
3(Pr.06-25)
38: Error output selection
4(Pr.06-26)
40: Speed attained (including
Stop)
44: Low current output
45: UVW Magnetic Contactor
enabled
47: Brake output closed
50: Output for CANopen
control
51: Output for RS485
52: Output for communication
card
53: Fire mode indication
54: Bypass fire mode
indication
55: Motor #1 Output
56: Motor #2 Output
57: Motor #3 Output
58: Motor#4 Output
59: Motor#5 Output
60: Motor #6 Output
61: Motor#7 Output
62: Motor#8 Output
Multi output
02-18 000h ~ FFFh (0: N.O.; 1: N.C.) 0
direction
Terminal counting
02-19 0~65500 0
value attained
Preliminary
counting value
02-20 0~65500 0
attained (not return
to 0)
02-21 Reserved
Desired Frequency 60.00/
02-22 0.00~600.00Hz
Attained 1 50.00
The Width of the
02-23 Desired Frequency 0.00~600.00Hz 2.00
Attained 1
Desired Frequency 60.00/
02-24 0.00~600.00Hz
Attained 2 50.00
The Width of the
02-25 Desired Frequency 0.00~600.00Hz 2.00
Attained 2
02-32 Brake Delay Time 0.000~65.000 秒 0.000
Output Current
Level Setting for
02-33 0~100% 0
Multi-function
External Terminals
Output frequency
setting
02-34 for multi-function 0.00~600.00Hz 0.00
output
terminal
External Operation
0: Disabled
Control Selection
02-35 1: Drive runs if run command 0
after Reset and
exists after reset
Activate
02-47 Reserved
02-48 Reserved
02-49 Reserved
EN_13
Factory
Parameters Functions Settings Note
Setting
Status of
Monitor the status of Read
02-50 Multi-function Input
multi-function input terminals Only
Terminal
Status of
Monitor the status of Read
02-51 Multi-function
multi-function output terminals Only
Output Terminal
Display External
Monitor the status of PLC input Read
02-52 Output terminal
terminals Only
occupied by PLC
Display Analog
Monitor the status of PLC Read
02-53 Input Terminal
output terminals Only
occupied by PLC
Display the
Frequency Read
02-54 Read Only
Command Memory Only
of External Terminal
EN_14
Group 3 Analog Input/Output Parameters
Factory
Parameters Functions Settings Note
Setting
03-00 Analog Input 1 (AVI1) 0: No function 1
03-01 Analog Input 2(ACI) 1: Frequency command 0
(torque limit under torque
control mode)
4: PID target value
5: PID feedback signal
03-02 Analog Input 3 (AVI2) 6: PTC thermistor input 0
value
11: PT100 thermistor input
value
12~17: Reserved
03-03 AVI1 Analog Input Bias -100.0~100.0% 0
03-04 ACI Analog Input Bias -100.0~100.0% 0
AVI2 Analog Positive
03-05 -100.0~100.0% 0
Voltage Input Bias
03-06 Reserved
AVI1 positive/negative 0: No bias
03-07 0
bias mode 1: Lower than bias=bias
ACI positive/negative 2: Greater than bias=bias
03-08 0
bias mode 3: The absolute value of
the bias voltage while
AVI2 positive/negative serving as the center
03-09 0
bias mode 4: Serve bias as the
center
0: Negative frequency
input is disabled. Forward
and reverse motions are
controlled by digital
keypad or by external
terminal.
Analog Frequency 1: Negative frequency
03-10 Command for input is enabled. Forward 0
Reverse Run motion when positive
frequency, reverse motion
when negative frequency.
Forward and reverse
motions are not controlled
by digital keypad or by
external terminal.
Analog Input Gain 1
03-11 -500.0 ~ 500.0 % 100.0
(AVI 1)
Analog Input Gain 2
03-12 -500.0 ~ 500.0 % 100.0
(ACI)
Analog Input Gain 3
03-13 -500.0 ~ 500.0 % 100.0
(AVI 2)
Analog Input Gain 4
03-14 -500.0 ~ 500.0 % 100.0
(AVI 2)
Analog Input Filter
03-15 0.00~20.00 seconds 0.01
Time (AVI1)
Analog Input Filter
03-16 0.00~20.00 seconds 0.01
Time (ACI)
Analog Input Filter
03-17 0.00~20.00 seconds 0.01
Time (AVI2)
0: Disable addition
Addition Function of function (AVI1, ACI, AVI2)
03-18 0
the Analog Input 1: Enable addition
function
0: Disable
1: Continue operation at
the last frequency
03-19 Loss of the ACI Signal 0
2: Decelerate to 0Hz
3: Stop immediately and
display ACE
Multi-function Output 1
03-20 0: Output frequency (Hz) 0
(AFM1)
EN_15
Factory
Parameters Functions Settings Note
Setting
Multi-function Output 2 1: Frequency command
03-23 0
(AFM2) (Hz)
2: Motor speed (Hz)
3: Output current (rms)
4: Output voltage
5: DC Bus voltage
6: Power factor
7: Power
9:AVI1 %
10:ACI %
11:AVI2 %
20: CANopen analog
output
21: RS485 analog output
22: Communication card
analog output
23: Constant voltage
output
Gain for Analog Output
03-21 0~500.0% 100
1 (AFM1)
0: Absolute output voltage
Analog Output 1 Value 1: Reverse output 0V;
03-22 in REV Direction Positive output 0-10V 0
(AFM1) 2: Reverse output 5-0V;
Positive output 5-10V
Gain for Analog Output
03-24 0~500.0% 100
2 (AFM2)
0: Absolute output voltage
1: Output 0V in REV
Analog Output 2 Value direction; output 0-10V in
03-25 in REV Direction FWD direction 0
(AFM2) 2: Output 5-0V in REV
direction; output 5-10V in
FWD direction
03-26 Reserved
03-27 AFM2 Output Offset -100.00~100.00% 0.00
0: 0-10V
03-28 AVI1 Selection 1: 0-20mA 0
2: 4-20mA
0: 4-20mA
03-29 ACI Selection 1: 0-10V 0
2: 0-20mA
Status of PLC Output Monitor the status of PLC Read
03-30
Terminal output terminals Only
AFM2 0-20mA Output 0: 0-20mA 0
03-31
Selection 1: 4-20mA
AFM1 0~20mA Output 0: 0~20mA output
03-34 0
Selection 1: 4~20mA output
AFM1 DC output setting
03-32 0.00~100.00% 0
level
AFM2 DC Output
03-33 0.00~100.00% 0
Setting Level
03-35 AFM1 filter output time 0~ 20.00 Seconds 0.01
03-36 AFM2 filter output time 0 ~ 20.00 Seconds 0.01
03-37
~ Reserved
03-49
Analog Calculation
03-50 0~7 7
Selection
03-51 AVI1 – Low Point 0~10.00 / 0~20.00 0
AVI1 Low Point
03-52 0~100% 0
Percentage
03-53 AVI1 Mid Point 0~10.00 / 0~20.00 5.00
EN_16
Factory
Parameters Functions Settings Note
Setting
AVI1 Mid Point
03-54 0~100% 50
Percentage
03-55 AVI1 High Point 0~10.00 / 0~20.00 10.00
AVI1 High Point
03-56 0~100% 100
Percentage
03-57 ACI Low Point 0~10.00 / 0~20.00 4.00
ACI Low Point
03-58 0~100% 0
Percentage
03-59 ACI Mid Point 0~10.00 / 0~20.00 12.00
ACI Mid Point
03-60 0~100% 50
Percentage
03-61 ACI High Point 0~10.00 / 0~20.00 20.00
ACI High Point
03-62 0~100% 100
Percentage
03-63 AVI2 Low Point Voltage 0~10.00V 0
AVI2 Low Point
03-64 0~100% 0
Percentage
03-65 AVI2 Mid Point Voltage 0~10.00V 5.00
AVI2 Mid Point
03-66 0~100% 50
Percentage
03-67 AVI2 High Point Voltage 0~10.00V 10.00
AVI2 High Point
03-68 0~100% 100
Percentage
EN_17
Group 4 Multi-step Speed Parameters
Factory
Parameters Functions Settings Note
Setting
04-00 1st Step Speed Frequency 0.00~600.00Hz 0
04-01 2nd Step Speed Frequency 0.00~600.00Hz 0
04-02 3rd Step Speed Frequency 0.00~600.00Hz 0
04-03 4th Step Speed Frequency 0.00~600.00Hz 0
04-04 5th Step Speed Frequency 0.00~600.00Hz 0
04-05 6th Step Speed Frequency 0.00~600.00Hz 0
04-06 7th Step Speed Frequency 0.00~600.00Hz 0
04-07 8th Step Speed Frequency 0.00~600.00Hz 0
04-08 9th Step Speed Frequency 0.00~600.00Hz 0
04-09 10th Step Speed Frequency 0.00~600.00Hz 0
04-10 11th Step Speed Frequency 0.00~600.00Hz 0
04-11 12th Step Speed Frequency 0.00~600.00Hz 0
04-12 13th Step Speed Frequency 0.00~600.00Hz 0
04-13 14th Step Speed Frequency 0.00~600.00Hz 0
04-14 15th Step Speed Frequency 0.00~600.00Hz 0
04-15
~ Reserved
04-49
04-50 PLC Buffer 1 0~65535 0
04-51 PLC Buffer 2 0~65535 0
04-52 PLC Buffer 3 0~65535 0
04-53 PLC Buffer 4 0~65535 0
04-54 PLC Buffer 5 0~65535 0
04-55 PLC Buffer 6 0~65535 0
04-56 PLC Buffer 7 0~65535 0
04-57 PLC Buffer 8 0~65535 0
04-58 PLC Buffer 9 0~65535 0
04-59 PLC Buffer 10 0~65535 0
EN_18
Group 5 Motor Parameters
Factory
Parameters Functions Settings Note
Setting
0: No function
1: Measure induction motor in
dynamic status (motor
spinning) (Rs, Rr, Lm, Lx,
05-00 Motor Auto Tuning 0
no-load current)
2: Measure induction motor in
static status (motor not
spinning)
Full-Load current 10~120% of the drive’s rated
05-01 of Induction Motor current 0
1 (Amps)
Rated Power of 0~655.35kW
05-02 Induction Motor 1 0
(kW)
Rated Rotational 0~65535
Speed of 1710(60Hz 4 poles);
05-03 1710
Induction Motor 1 1410(50Hz 4 poles)
(rpm)
Pole Number of 2~20
05-04 4
Induction Motor 1
No Load Current 0~ Pr.05-01 of factory setting
05-05 of Induction Motor 0
1 (Amps)
Stator Resistance 0~65535m
05-06 (Rs) of Induction 0
Motor 1
Rotor Resistance 0~65535m
05-07 0
(Rr) of Mo1
Magnetizing 0~65535mH
Inductance (Lm)
05-08 0
og Induction Motor
1
Stator Inductance 0~65535mH
05-09 (Lx) of Induction 0
Motor 1
05-10
~ Reserved
05-12
Rated Current of 0~65535
05-13 Induction Motor 2 0
( Amps)
Rated Power of 0~655.35kW
05-14 Induction Motor 2 0
(kW)
Rated Rotational 0~65535
Speed of 1710(60Hz 4poles);1410(50Hz
05-15 1710
Induction Motor 2 4 poles)
(rpm)
Pole Number of 2~20
05-16 4
Induction Motor 2
No-load Current of 0~Parameter05-01 factory
05-17 Induction Motor 2 setting 0
(A)
Stator Resistance 0~65.535
05-18 (Rs) of Induction 0
Motor 2
Rotor Resistance 0~65.535
05-19 0
(Rr) of Motor 2
Magnetizing 0~65535mH
Inductance (Lm)
05-20 0
og Induction Motor
2
Stator Inductance 0~65535mH
05-21 (Lx) of Induction 0
Motor 2
EN_19
Factory
Parameters Functions Settings Note
Setting
Induction Motor 1/ 1: motor 1
05-22 1
Motor 2 Selection 2: motor 2
Frequency for 0.00~600.00Hz
Y-connection/△
05-23 -connection 60.00
Switch of
Induction Motor
Y-connection/△ 0:Disable
05-24 -connection 1:Enable 0
Switch of
Induction Motor
Delay Time for 0.000~60.000 seconds
Y-connection/△
05-25 -connection 0.200
Switch of
Induction Motor
Accumulative Watt Read only
Per Second of
05-26 0
Motor in Low
Word (W-sec)
Accumulative Watt Read only
Per Second of
05-27 0
Motor in High
Word (W-sec)
Accumulative Read only
05-28 Watt-hour of 0
Motor (W-Hour)
Accumulative Read only
Watt-hour of
05-29 0
Motor in Low
Word (KW-Hour)
Accumulative Read only
Watt-hour of
05-30 0
Motor in High
Word (KW-Hour)
Accumulated 00~1439
05-31 Motor Operation 0
Time (minutes)
Accumulative 00~65535
05-32 Motor Operation 0
Time (day)
EN_20
Group 6 Protection Parameters
Factory
Parameters Functions Settings Note
Setting
230V:160.0~220.0Vdc
180
Frame E and above:
360
06-00 Low Voltage Level 190.0~220.0V Frame E
460V:320.0~440.0Vdc and above:
Frame E and above: 200.0/400.0
380.0~440.0V
Over-voltage Stall 230V:350.0~450.0Vdc 380.0
06-01
Prevention 460V:700.0~900.0Vdc 760.0
0: Traditional over-voltage
Selection for
stall prevention
06-02 over-voltage stall 0
1: Smart over-voltage
prevention
prevention
Normal duty:
Normal
Over-current Stall 0~160%(100%: drive’s
duty:120;
06-03 Prevention during rated current);
Light
Acceleration Light duty: 0~130%(100%:
duty:120
drive’s rated current)
Normal duty:
Normal
Over-current Stall 0~160%(100%: drive’s
duty:120;
06-04 Prevention during rated current);
Light
Operation Light duty: 0~130%(100%:
duty:120
drive’s rated current)
0: by current accel/decel
time
1: by the 1st accel/decel
time
Accel. /Decel.
2: by the 2nd accel/decel
Time Selection of
06-05 time 0
Stall Prevention at
3: by the 3rd accel/decel
Constant Speed
time
4: by the 4th accel/decel
time
5: by auto accel/decel
0: No function
1: Over-torque detection
during constant speed
operation, continue to
operate after detection
2: Over-torque detection
Over-torque during constant speed
06-06 Detection operation, stop operation 0
Selection (OT1) after detection
3: Over-torque detection
during operation, continue
to operate after detection
4: Over-torque detection
during operation, stop
operation after detection
Over-torque 10~200%(100%: drive's
06-07 Detection Level 120
rated current)
(OT1)
Over-torque
06-08 Detection Time 0.0~60.0 seconds 0.1
(OT1)
EN_21
Factory
Parameters Functions Settings Note
Setting
0: No function
1: Over-torque detection
during constant speed
operation, continue to
operate after detection
2: Over-torque detection
Over-torque during constant speed
06-09 Detection operation, stop operation 0
Selection (OT2) after detection
3: Over-torque detection
during operation, continue
to operation after detection
4: Over-torque detection
during operation, stop
operation after detection
Over-torque 10~200%(100%: drive's
06-10 Detection Level 120
rated current)
(OT2)
Over-torque
06-11 Detection Time 0.0~60.0 seconds 0.1
(OT2)
Maximum Torque 0~200% (100%: drive’s
06-12 150%
Limit rated current)
0: Motor with constant
torque output
Electronic Thermal
1: Motor with variable
06-13 Relay Selection 2
torque output
(Motor 1)
2: Electronic Thermal Relay
disabled
Electronic Thermal
06-14 Characteristic for 30.0~600.0 seconds 60.0
Motor 1
Heat Sink
06-15 Over-heat (OH) 0.0~110.0℃ 100.0
Warning
0~100%
Stall Prevention
06-16 (Parameter06-03, 50
Limit Level
Parameter06-04)
Current Error
06-17 0: No fault record 0
Record
Second Most
1: Over-current during
06-18 Recent Error 0
acceleration (ocA)
Record
Third Most Recent 2: Over-current during
06-19 0
Error Record deceleration (ocd)
Fourth Most
3: Over-current during
06-20 Recent Error 0
constant speed(ocn)
Record
Fifth Most Recent
06-21 4: Ground fault (GFF) 0
Error Record
Sixth Most Recent
06-22 5: IGBT short-circuit (occ) 0
Error Record
6: Over-current at stop
(ocS)
7: Over-voltage during
acceleration (ovA)
8: Over-voltage during
deceleration (ovd)
9: Over-voltage during
constant speed (ovn)
10: Over-voltage at stop
(ovS)
11: Low-voltage during
acceleration (LvA)
12: Low-voltage during
deceleration (Lvd)
EN_22
Factory
Parameters Functions Settings Note
Setting
13: Low-voltage during
constant speed (Lvn)
14: Stop mid-low voltage
(LvS)
15: Phase loss protection
(PHL)
16: IGBT over-heat (oH1)
17: Capacitance over-heat
(oH2) (over 40hp)
18: tH1o (TH1 open: IGBT
over-heat
protection error)
19: tH2o (TH2 open:
capacitance over-heat
protection error)
20: Reserved
21: Drive over-load (oL)
(When current is 150%
of the rated current, the
drive will be
overloaded.)
22: Electronics thermal
relay 1 (EoL1)
23: Electronics thermal
relay 2 (EoL2)
24: Motor overheat (oH3)
(PTC)
25: Reserved
26: Over-torque 1 (ot1)
27: Over-torque 2 (ot2)
28: Under current 1 (uc)
29: Reserved
30: Memory write-in error
(cF1)
31: Memory read-out error
(cF2)
32: Reserved
33: U-phase current
detection error (cd1)
34: V-phase current
detection error (cd2)
35: W-phase current
detection error (cd3)
36: Clamp current detection
error (Hd0)
37: Over-current detection
error (Hd1)
38: Over-voltage detection
error (Hd2)
39: Ground current
detection error (Hd3)
40: Auto tuning error (AuE)
41: PID feedback loss
(AFE)
42~47 Reserved
48: ACI reference input loss
(ACE)
49: External fault input (EF)
50: Emergency stop (EF1)
51: External Base Block
(BB)
52: Password Error
(Pcode)
53:Reserved
EN_23
Factory
Parameters Functions Settings Note
Setting
54: Communication error
(cE1)
55: Communication error
(cE2)
56: Communication error
(cE3)
57: Communication error
(cE4)
58: Communication
Time-out (cE10)
59: PU Time-out (cP10)
60: Brake transistor error
(bF)
61: Y-connection/△
-connection switch
error (ydc)
62: Decel. Energy Backup
Error (dEb)
63: Slip error (oSL)
64~65:Reserved
73: External safety gate S1
74: FIRE mode output
79: U phase over current
(Uocc)
80: V phase over current
(Vocc)
81: W phase over current
(Wocc)
82: U phase output phase
loss (OPHL)
83: V phase output phase
loss (OPHL)
84: W phase output phase
loss (OPHL)
101: CANopen software
disconnect1 (CGdE)
102: CAN open software
disconnect2 (CHbE)
103: CANopen
synchronous error (CSYE)
104: CANopen hardware
disconnect (CbFE)
105: CANopen index
setting error (CIdE)
106: CANopen slave
station number setting error
(CAdE)
107: CANopen index
setting exceed limit (CFrE)
Fault Output 0~65535(refer to bit table
06-23 0
Option 1 for fault code)
Fault Output 0~65535(refer to bit table
06-24 0
Option 2 for fault code)
Fault Output 0~65535(refer to bit table
06-25 0
Option 3 for fault code)
Fault Output 0~65535(refer to bit table
06-26 0
Option 4 for fault code)
0: Motor with constant
torque output
Electronic Thermal
1: Motor with variable
06-27 Relay Selection 2 2
torque output
(Motor 2)
2: Electronic Thermal Relay
disabled
EN_24
Factory
Parameters Functions Settings Note
Setting
Electronic Thermal
06-28 Operating Time of 30.0~600.0(Seconds) 60.0
Motor 2 (Seconds)
0: Warn and keep operation
PTC Detection 1: Warn and ramp to stop
06-29 0
Selection 2: Warn and coast to stop
3: No warning
06-30 PTC Level 0.0~100.0% 50.0
Frequency
06-31 Command when 0.00~655.35 Hz Read Only
Malfunction
Output Frequency
06-32 0.00~655.35 Hz Read Only
when Malfunction
Output Voltage
06-33 0.0~6553.5 V Read Only
when Malfunction
DC Voltage at Read Only
06-34 0.0~6553.5 V
Malfunction
Output Current at Read Only
06-35 0.00~655.35 Amp
Malfunction
IGBT Temperature Read Only
06-36 0.0~6553.5 ℃
at Malfunction
Read Only
Capacitance
06-37 Temperature at
0.0~6553.5 ℃
Malfunction
Motor Speed in Read Only
06-38 0~65535
rpm at Malfunction
06-39 Reserved
Status of Read Only
Multi-function Input
06-40 0~65535
Terminal when
Malfunction
Status of Read Only
Multi-function
06-41 0~65535
Output Terminal
when Malfunction
Drive Status when Read Only
06-42 0~65535
Malfunction
06-43 Reserved
06-44 Reserved
0: Warn and keep operation
Action for detected
1: Warn and ramp to stop
06-45 Output Phase Loss 3
2: Warn and coast to stop
(OPhL)
3: No warning
Time of detected
06-46 0~65.535 seconds 0.5
Output Phase Loss
Detected Current
06-47 0~655.35% 1.0
Bandwidth
DC Brake Time of
06-48 0~65.535 seconds 0.1
Output Phase Loss
06-49 Reserved
Time of detected
06-50 0.00~600.00 seconds 0.20
Input Phase Loss
06-51 Reserved
230V models: 0.0 ~ 160
Ripple of the
Vdc
06-52 detected Input 30/60
460V models : 0.0 ~ 320
Phase Loss’ Ripple
Vdc
Action for detected
0: warn and ramp to stop
06-53 Input Phase Loss 0
1: warn and coast to stop
(OrP)
06-54 Reserved
EN_25
Factory
Parameters Functions Settings Note
Setting
0: Constant rated current
and limit carrier wave by
loaded current and
temperature
1: Constant carrier
Derating
06-55 frequency and limit
Protection
loaded current by setting
carrier wave
2: Constant rated
current(same as setting 0),
but current limit is closed
PT100 Detection
06-56 0~10000 v 5000
Level 1
PT100 Detection
06-57 0~10000 v 7000
Level 2
PT100 Level 1
06-58 0~600.00 Hz 0
Frequency Protect
Delay time of
PT100 Level 1
06-59 0~6000 seconds 60
Frequency
Protection
Software Detection
GFF Current Level
06-60 0~6553.5% 60.0
(% rated current of
the drive)
Software detection
06-61 of GFF Low pass 0~655.35 sec 0.10
Filter gain
Disable Level of 230V models: 0~220.0 Vdc 180.0/
06-62
dEb 460V models: 0~440.0 Vdc 360.0
Fault Record 1 0~65535 days
06-63 Read Only
(Day)
Fault Record 1 0~1439 min Read Only
06-64
(Min)
Fault Record 2 0~65535 days Read Only
06-65
(Day)
Fault Record 2 Read Only
06-66 0~64799 min
(Min)
Fault Record 3 Read Only
06-67 0~65535 days
(Day)
Fault Record 3 Read Only
06-68 0~1439 min
(Min)
Fault Record 4 Read Only
06-69 0~65535 days
(Day)
Fault Record 4 Read Only
06-70 0~1439 min
(Min)
Low Current
06-71 0~100.0% 0
Setting Level
Low Current
06-72 0~360.00 seconds 0
Detection Time
0 : No function
1 : Warn and coast to stop
Options when low 2 : Warn and ramp to stop
06-73 0
current occurs by 2nd deceleration time
3 : Warn and operation
continues
06-74 Reserved
06-76 Reserved
0: No function
06-80 Fire mode 1: Forward operation 0
2: Reverse Operation
Operating
Frequency when
06-81 0.00 to 60000Hz 6000
running Fire
Mode(Hz)
EN_26
Factory
Parameters Functions Settings Note
Setting
Bypass Fire Mode 0: Disable Bypass
06-82 0
enabled 1: Enable Bypass
Delayed Time
06-83 when Bypass Fire 0.0 to 6550.0 sec 0
Mode
Auto reset
06-84 counter of Fire 0~10 0
Mode
Length of time to
06-85 reset auto-counter 0.0 to 6000.0 sec 600
(seconds)
EN_27
Group 7 Special Parameters
Factory
Parameters Functions Settings Note
Setting
230V series:
Setup Software Brake 350.0~450.0Vdc 380.0
07-00
Level 460V series: 760.0
700.0~900.0Vdc
DC Brake Current
07-01 0~100% 0
Level
DC Brake Time at
07-02 0.0~60.0 seconds 0.0
Start-up
07-03 DC Brake Time at Stop 0.0~60.0 seconds 0.0
Startup Frequency for
07-04 0.00~600.00Hz 0.00
DC Brake
Voltage Increasing
07-05 0~200% 100%
Percentage
0: Stop operation
1: Speed search starting
from last speed before
Restart after
the moment of power
07-06 Momentary Power 0
down.
Down
2: Speed search starting
from minimum output
frequency
Maximum Power Loss
07-07 0.1~20.0 seconds 2.0
Duration
07-08 Base Block Time 0.1~5.0 seconds 0.5
Current Limit for
07-09 20~200% 100
Speed Search
0: Stop operation
1: Speed search starting
from last speed before
Base Block Speed the moment of base
07-10 0
Search (oc, ov, bb) block.
2: Speed search starting
from minimum output
frequency
# of Auto Reset after
07-11 0~10 0
Errors Occurred
0: Disable
1: Speed search starting
from maximum output
frequency
Speed Search while 2: Speed search starting
07-12 0
Start-up from start-up motor
frequency
3: Speed search starting
from minimum output
frequency
0: Disable
Deceleration Time at 1: 1st decel. time
Momentary Power 2: 2nd decel. time
07-13 Down ( dEb function: 3: 3rd decel. time 0
Deceleration Energy 4: 4th decel. time
Backup) 5: system decel. time
6: Auto decel. time
07-14 DEB Return Time 0.0~25.0 sec(0~250) 0
0.00~
07-15 Dwell Time at Accel. 0
600.00sec(0~60000)
Dwell Frequency at
07-16 0.00~600.00Hz(0~60000) 0
Accel.
0.00~
07-17 Dwell Time at Decel. 0
600.00sec(0~60000)
Dwell Frequency at
07-18 0.00~600.00Hz(0~60000) 0
Decel.
EN_28
Factory
Parameters Functions Settings Note
Setting
0: Fan always ON
1: 1 minute after the AC
motor drive stops, fan
will be OFF
2: When the AC motor
drive runs, the fan is
ON. When the AC
07-19 Fan Cooling Control 0
motor drive stops, the
fan is OFF
3: Fan turns ON when the
preliminary heat sink’s
temperature reached
around 60℃ (140°F).
4: Fan always OFF
0: Coast stop
1: By deceleration Time 1
Emergency Stop (EF) 2: By deceleration Time 2
07-20 & Force to Stop 3: By deceleration Time 3 0
Selection 4: By deceleration Time 4
5: System Deceleration
6: Automatic Deceleration
Auto Energy-sAVI1ng 0: Disable
07-21 0
Operation 1: Enable
07-22 Energy-sAVI1ng Gain 10~1000% 100
0: Enable AVR
Auto Voltage
1: Disable AVR
07-23 Regulation(AVR) 0
2: Disable AVR during
Function
deceleration
Filter Time of Torque
07-24 Command (V/F and 0.001~10.000seconds 0.020
SVC control mode)
Filter Time of Slip
Compensation (V/F
07-25 0.001~10.000 seconds 0.100
and SVC control
mode)
Torque Compensation
07-26 Gain (V/F and SVC 0~10 0
control mode)
Slip Compensation
07-27 Gain (V/F and SVC 0.00~10.0 0.00
control mode)
07-28 Reserved
0.0~100.0%
07-29 Slip Deviation Level 0
0: Not-detectable
Detection Time of Slip
07-30 0.0~10.0 seconds 1.0
Deviation
0: Warn and keep
operation
07-31 Over Slip Treatment 1: Warn and ramp to stop 0
2: Warn and coast to stop
3: No warning
07-32 Motor Hunting Gain 0~10000 1000
Recovery Time to
Pr.07-11 (# of auto
07-33 00~60000 seconds 60.0
reset after error
occurred)
EN_29
Group 8 High-function PID Parameters
Factory
Parameters Functions Settings Note
Setting
0: No function
1: Negative PID feedback:
input from external terminal
Input Terminal for
08-00 AVI1 (Pr.03-00) 0
PID feedback
4: Positive PID feedback from
external terminal AVI1
(Pr.03-00)
Proportional Gain
08-01 0.0~100.0% 1.0
(P)
08-02 Integral Time (I) 0.00~100.00 seconds 1.00
08-03 Derivative Time (D) 0.00~1.00seconds 0.00
Upper Limit of
08-04 0.0~100.0% 100.0
Integral Control
PID Output
08-05 0.0~110.0% 100.0
Frequency Limit
PID Feedback Read
08-06 0.00 ~ 200.00%
Value Only
08-07 PID Delay Time 0.0~35.0 seconds 0.0
Feedback Signal
08-08 0.0~3600.0 seconds 0.0
Detection Time
0: Warn and keep operation
1: Warn and ramp to stop
Options on
08-09 2: Warn and coast to stop 0
Feedback Error
3: Warn and operate at last
frequency
Sleep Reference 0.00~600.00Hz or
08-10 0.00
Point 0~200.00%
Wake-up Reference 0.00~600.00Hz or
08-11 0.00
Point 0~200.00%
08-12 Sleep Time 0.0~600.00 seconds 0.0
08-13 PID Deviation Level 1.0~50.0% 10.0
08-14 PID Deviation Time 0.1~300.0 seconds 5.0
Filter Time for PID
08-15 0.1~300.0 seconds 5.0
Feedback
PID Compensation 0: Parameter setting
08-16 0
Selection 1: Analog input
08-17 PID Compensation -100.0~+100.0% 0
Setting of Sleep 0: Follow PID output command
08-18 0
mode function 1: Follow PID feedback signal
Integral Limit during
08-19 0~200.0% 50.0%
Wakeup
0: Serial connection
08-20 PID Mode Selection 0
1: Parallel connection
0: Operation direction cannot
Enable PID to
be changed
08-21 Change Operation 0
1: Operation direction can be
Direction
changed
08-22 Wakeup Delay Time 0 ~ 600.00 sec 0.00
EN_30
Group 9 Communication Parameters
Factory
Parameters Functions Settings Note
Setting
COM1
09-00 Communication 1~254 1
Address
COM1 Transmission
09-01 4.8~115.2Kbps 9.6
Speed
0: Warn and continue
operation
COM1 Transmission 1: Warn and ramp to stop
09-02 3
Fault Treatment 2: Warn and coast to stop
3: No warning and
continue operation
COM1 Time-out
09-03 0.0~100.0 seconds 0.0
Detection
0: 7N1 (ASCII)
1: 7N2 (ASCII)
2: 7E1 (ASCII)
3: 7O1 (ASCII)
4: 7E2 (ASCII)
5: 7O2 (ASCII)
6: 8N1 (ASCII)
7: 8N2 (ASCII)
COM1
8: 8E1 (ASCII)
09-04 Communication 1
9: 8O1 (ASCII)
Protocol
10: 8E2 (ASCII)
11: 8O2 (ASCII)
12: 8N1 (RTU)
13: 8N2 (RTU)
14: 8E1 (RTU)
15: 8O1 (RTU)
16: 8E2 (RTU)
17: 8O2 (RTU)
09-05
~ Reserved
09-08
09-09 Response Delay Time 0.0~200.0ms 2.0
Main Communication
09-10 0.00~600.00Hz 60.00
Frequency (Hz)
09-11 Block Transfer 1 0~65535 0
09-12 Block Transfer 2 0~65535 0
09-13 Block Transfer 3 0~65535 0
09-14 Block Transfer 4 0~65535 0
09-15 Block Transfer 5 0~65535 0
09-16 Block Transfer 6 0~65535 0
09-17 Block Transfer 7 0~65535 0
09-18 Block Transfer 8 0~65535 0
09-19 Block Transfer 9 0~65535 0
09-20 Block Transfer 10 0~65535 0
09-21 Block Transfer 11 0~65535 0
09-22 Block Transfer 12 0~65535 0
09-23 Block Transfer 13 0~65535 0
09-24 Block Transfer 14 0~65535 0
09-25 Block Transfer 15 0~65535 0
09-26 Block Transfer 16 0~65535 0
09-27
~ Reserved
09-29
Communication 0:Decoding Method 1
09-30 1
Decoding Method 1:Decoding Method 2
Internal
0: Modbus 485
09-31 Communication 0
1: BACnet
Protocol
09-32 ~
Reserved
09-34
09-35 PLC Address 1~254 2
EN_31
Factory
Parameters Functions Settings Note
Setting
CANopen Slave 0: Disable
09-36 0
Address 1~127
0:1M
1:500k
09-37 CANopen Speed 2: 250k 0
3: 125k
4: 100k (Delta Only)
5: 50k
09-38 Reserved
bit 0:CANopen Guarding
Time out
bit 1:CANopen Heartbeat
Time out
bit 2:CANopen SYNC
Time out
bit 3:CANopen SDO Time
out
bit 4:CANopen SDO buffer
CANopen Warning
09-39 overflow 0
Record
bit 5:Can Bus Off
bit 6:Error protocol of
CANopen
bit 8:The setting values of
CANopen indexs are fail
bit 9:The setting value of
CANopen address is fail
bit10:The checksum value
of CANopen indexs is fail
0:Delta defined decoding
CANopen Decoding method
09-40 1
Method 1: CANopen DS402
Standard
0:(Node Reset State)
1:(Com Reset State)
CANopen 2:(Boot up State)
09-41 Communication 0
3:(Pre Operation State)
Status
4:(Operation State)
5:(Stop State)
0:(Not Ready For Use
State)
1:(Inhibit Start State)
2:(Ready To Switch On
State)
3:(Switched On State)
CANopen Control
09-42 4:(Enable Operation 0
Status
State)
7:(Quick Stop Active
State)
13:(Err Reaction Active
State)
14:(Error State)
bit0: reset address 20XX to
0.
bit1: reset address 264X to
0
09-43 Reset CAN Initial Idx 65535
bit2: reset address 26AX to
0
bit3: reset address 60XX to
0
09-44 Reserved
CANopen Master 0: Disable
09-45 0
function 1: Enable
EN_32
Factory
Parameters Functions Settings Note
Setting
CANopen Master
09-46 1~127 100
Address
09-47
~ Reserved
09-49
09-50 BACnet Dnet 0~127 10
09-51 BACnet Baud Rate 9.66~76.8 kbps 38.4
09-52 BACnet Device ID L 0~9999 1
09-53 BACnet Device ID H 0~419 0
09-54 Reserved
09-55 BACnet Max Address 0~127 127
09-56 BACnet Password 0~65535 0
0: No communication card
1: DeviceNet Slave
2: Profibus-DP Slave
Identification of
09-60 3: CANopen Slave 0
Communication Card
4: Modbus-TCP Slave
5: EtherNet/IP Slave
6~8: Reserved
Firmware Version of
09-61 Read Only ##
Communication Card
09-62 Product Code Read Only ##
09-63 Error Code Read Only ##
09-64
~ Reserved
09-69
Address of DeviceNet: 0-63
09-70 1
Communication Card Profibus-DP: 1-125
Standard DeviceNet:
0: 100Kbps
1: 125Kbps
2: 250Kbps
3: 1Mbps (Delta only)
EN_33
Factory
Parameters Functions Settings Note
Setting
Address Mask 2 of the
09-81 0~255 0
Communication Card
Address Mask 3 of the
09-82 0~255 0
Communication Card
Address Mask 4 of the
09-83 0~255 0
Communication Card
Gateway Address 1 of
09-84 the Communication 0~255 0
Card
Gateway Address 2 of
09-85 the Communication 0~255 0
Card
Gateway Address 3 of
09-86 the Communication 0~255 0
Card
Gateway Address 4 of
09-87 the Communication 0~255 0
Card
Password for
09-88 Communication Card 0~99 0
(Low word)
Password for
09-89 Communication Card 0~99 0
(High word)
0: No function
Reset Communication
09-90 1: Reset to return to the 0
Card
factory setting
Bit 0: Enable IP Filter :
Bit 1: Enable internet
parameters (1bit)
Once the setup of
internet parameter
is done, the Bit 1
will be enabled. But
after the parmeters
of the
communication
card are updated,
this Bit 1 will be
Additional Setting for
09-91 disabled. 0
Communication Card
Bit 2: Enable login
password (1bit)
When login
password is
correctly entered,
the Bit 2 will be
enabled. But after
the parameters of
the communication
card are updated,
this Bit 2 will be
disabled.
Bit 0: Enable password.
When the
communication
card is locked by a
Status of password, this Bit
09-92 0
Communication Card 0 will be enabled.
When the
password is clear,
this Bit 0 will be
disabled.
EN_34
12 PUMP Parameter
Factory
Parameters Functions Settings Note
Setting
0: No operation
1: Fixed Time Circulation (by
time)
2: Fixed quantity circulation
(by PID)
12-00 Circulative Control 0
3: Fixed quantity control
4: Fixed Time Circulation+
Fixed quantity circulation
5: Fixed Time Circulation+
Fixed quantity control
Number of motors From only 1 and up to 8
12-01 1
to be connected motors
Operating time of
12-02 each motor 0 to 65500 min 0
(minutes)
Delay Time due to
the Acceleration (or
12-03 0.0 to 3600.0 sec 10
the Increment ) at
Motor Switching
Delay Time due to
the Deceleration
12-04 ( or the Decrement) 0.0 to 3600.0 sec 10
at Motor Switching
(seconds)
Delay time while
fixed quantity
12-05 circulation at Motor 0.0 to 3600.0 sec 100
Switching
(seconds)
Frequency when
switching motors at
12-06 0.00 to 600.00 Hz 6000
fixed quantity
circulation (Hz)
Action to do when 0: Turn off all output
Fixed Quantity 1: Motors powered by mains
12-07 0
Circulation breaks electricity continues to
down. operate.
Frequency when
12-08 stopping auxiliary 0.00 to 600.00 Hz 0
motor (Hz)