NOVATEX LIMITED SOP / E&I / 40
1 PURPOSE:
To start LOSS IN WEIGHT type SCHENCK unit (IPA SCHENCK ) after tripping / maintenance as
per process requirement
2 SCOPE:
Electrical & Instrument (YES)
Process (YES)
Safety (NO)
3 PRE-REQUISITE
Start-up procedure
4 PROCEDURE:
For starting the IPA SCHENCK, no need of a specific work permit, however a cold / critical work
permit must be generated for maintenance on SCHENCK unit
Whenever the IPA SCHENCK trips on any fault or took offline for maintenance, follow the steps
given below to restart it
Reset the inverter and note down fault in case of SCHENCK trip
Ensure that the instrument air valve of XV is open in the field
Make sure that STOP command from DCS by process should be given, before starting the
SCHENCK system, in case of SCHENCK trip
Ask process personnel to start SCHENCK system from DCS and verify that the motor is running in
field
Now if the XV does not open automatically, then either put some weight (approx >5 Kg) on
SCHENCK assembly (Green Color) in field OR press the MENU button of IPA INTECONT
(Panel IP-07 within control room), and scroll down until "FILLING START" appears in the display
then press ENTER button to open the IPA XV
Verify the opening of XV from field
Now press the escape button to skip from MENU
Note down the current from inverter
Make an entry of the said job in the technician log book
5 RELATED DOCUMENT:
Start-up procedure External Manual
Process Control Maintenance MOP / E&I / 16
Control of Monitoring & Measuring Devices ISP / MR / 06
6 RECORD:
Technician Log Book E&I / R10