During start-up, fusible loop is charged to allow air from instrument air system pressurizing the loop. The pressure
remains constant during normal operation. If there is fire and the surrounding temperature rises, the fusible plug
will melt. The air in the loop relieves and subsequently the pressure inside the tubing reduces. Loss of pressure in
the loop will be detected by pressure transmitter in the fusible loop charge panel and it will signal the control
room. Next action in the control system could be activate fire alarm, trigger ESD, open deluge valve, etc.
Fusible Plug is non-resettable type. To restore the system into normal surveillance after activation will require
replacement of parts i.e. the fusible plug.
The other disadvantage of fusible loop is that the plug could melt by other source of heat other than fire such as
hot surfaces, motors, etc.