possible to the batch target, by minimizing the amount of overshoot. To enable the batch AOC, see pages 32-33.
The batch AOC must be calibrated:
• When the discrete batch application is installed • If consistent overshooting or undershooting of the target is observed • If equipment (valve or pump) is changed
To calibrate the batch AOC:
1. Press the security button on the display face. Maintenance 2. Select Maintenance. Calibration 3. Select Calibration. Batch AOC 4. Select Batch AOC. 5. Select Start Calibration. 6. Press EXIT repeatedly to return to the operation screen. 7. Run two to 10 batches. 8. When overshoot has been adequately minimized, repeat steps 1 through 4. 9. Select Save Calibration.