Professional Documents
Culture Documents
Indian Standard
ROTATING ELECTRICAL
MACHINES — SPECIFICATION
( Second Revision)
ICS 621,313-13
0 BIS 2001
/I
-- .
FOREWORD
This Indian Standard (Second Revision) was adopted by the Bureau of Indian Standards, after the draft finalized
by the Rotating Machinery Sectional Committee had been approved by the Electrotechnical Division Council.
In the first revision of this standard following contents have been brought out in separate independent standards:
a) Type of duty and classes of ratings assigned to rotating electrical machines covered in IS 12824:1989,
and
b) Temperature-rise measurements of rotating electrical machines covered in IS 12802:1989.
In this revision, a number of editorial corrections have been incorporated and in addition, some changes have
also been incorporated based on experience for operation of this standard.
The requirements of rotating electrical machines covered in this standard have been updated in line with current
international practices.
While revising this standard, assistance has been derived from the IEC Pub 34(1983) now designated as IEC
60034 ‘Rotating electrical machines’, issued by the International Electrotechnical Commission (IEC).
For the purpose of deciding whether a particular requirement of this standard is complied with, the final value,
observed or calculated, expressing the result of a test, shall be rounded off in accordance with IS 2:1960 ‘Rules
for rounding off numercial values (revised)’. The number of significant places retained in the rounded off value
should be the same as that of the specified value in this standard.
/
-
IS 4722:2001
Indian Standard
ROTATING ELECTRICAL
MACHINES — SPECIFICATION
(Second Revision)
1 SCOPE 3 TERMINOLOGY
1.1 This standard covers requirements for rotating 3.0 For the purpose of this standard, the following
electrical machines without distinction of output and definitiofis shall apply. The definitions of general
voltage but excluding: terms used in this standard are given in IS 1885
(Part 35).
a) Traction equipment, and
b) Motors covered by IS 996:1979 ‘Single phase 3.1 Rating
small ac and universal electric motors (second The whole of the numerical values of the electrical and
revision)’. mechanical quantities with their durations. and
1.1.1 Attention is drawn to certain other standards sequence assigned to the machine by the manufacturer
and stated on the rating plate, the machine complying
listed below which may apply when machines are
required for particular applications. The rating plate with the specified conditions.
of machines built to comply with these standards 3.2 Rated Value
indicate the number of the Indian Standards invoked:
The numerical value of a quantity included in the
IS No. Title rating.
325:1996 Three-phase induction motors
3.3 Rated Output
~ourth revision)
2635:1975 DC electric welding generators The numerical value of the output included in the
(second revision) rating.
The Indian Standards listed in Annex A are necessary The complete absence of all movements and of all
adjuncts to this standard. electrical supply or mechanical drive.
,*-u_
..
.
IS 4722:2001
The statement of the load(s) to which the machine is A method by means of which heat resulting from
subjected, including, if applicable, starting, electric Iossesoccurnng in a machine is given up first to a
braking, no-load and rest andde-energized periods, primary cocdant by increasing its temperature. The
and including their durations and sequence in time. heated primary coolant may be replaced by a new
coolant at a lower temperature or may be cooled by a
3.10 Duty Type
secondary coolant in some form of heat exchanger.
A continuous short time or periodic duty, comprising
3.19 Coolant
one or more loads remaining constant for the duration
specified, or a non-periodic duty in which generally A medium (liquid or gas) by means of which heat is
load and speed vary within the permissible operating transferred.
range.
3.20 Primary Coolant
3.11 Thermal Equilibrium
A medium (liquid or gas) which, by being at a lower
The state reached when the temperature rises of the temperature than a part of the machine and in contact
several parts of the machine do not vary by more than with it, removes heat from that part.
2 K over a period of 1 h.
3.21 Secondary Coolant
3.12 Cyclic Duration Factor
A medium (liquid or gas) which, by being at a lower
The ratio between the period of loading, including temperature than the primary coolant, removes the
starting and electric braking, and the duration of duty heat given up by this primary coolant by means of a
cycle, expressed as a percentage. heat exchanger.
3.13 Locked Rotor Torque 3.22 Direct Cooled (Inner Cooled) Winding
The minimum measured torque which the motor A winding in which the coolant flows through hollow
develops with the rotor locked and rated voltage conductors, tubes or channels which form an integral
applied at rated frequency. part of the winding inside the main insulation.
The measured steady-state root-mean-square current A winding cooled by any other method than that
taken from the line with the rotor locked with rated of 3.22.
voltage and frequency applied. NOTE— In all cases when ‘indirect’ or ‘direct’ is not stated, an
indirect cooled winding is implied.
3.15 Pull-up Torque (of an ac Motor)
3.24 Supplementary Insulation
The smallest torque which the motor develops
between zero speed and the speed which corresponds An independent insulation applied in addition to the
to the breakdown torque when the motor is supplied at basic insulation in order to ensure protection against
the rated voltage and frequency. electric shock in the event of faihtre of the basic
NOTES insulation.
1 This definition does not apply to those asynchronous motors
of which the torque continually decreases with increasein speed.
3.25 Moment of Inertia
2 This value applies to the usual mean torque characteristic The (dynamic) moment of inertia of a body about an
which excludes transient effects. axis is the sum (integral) of the products of its mass
3.16, Breakdown Torque (of an ac Motor) element and the square of their distances (radii) from
the axis.
The maximum torque which the motor develops with NOTE — This quantity is designated by the letter symbol J and
rated voltage and frequency applied at operating is exrmased in K~m2
.
temperature without an abrupt drop in speed.
3.26 Thermal Equivalent Time Constant
NOTES
1 The definition does not apply to those asynchronous motors The thermal equivalent time constant is the time
of which the torque continually decreases with increase in speed.
constant replacing several individual time constants,
2 This value applies to the usual mean torque characteristic
which determines approximately the temperature
which excludes transient effects.
course in a winding after step-wise current change.
3.17 Pull-out Torque (of a Synchronous Motor)
3.27 Encapsulated Winding
The maximum torque which the synchronous motor
develops at operating temperature and at synchronous A winding which is completely enclosed or sealed by
speed with rated voltage, frequency and field current. moulded insulation.
2
IS 4722:2001
Machines shall be designed for the following Hydrogen-cooled machines shall be capable of
operating site conditions, unless other conditions are operating at a rated output underrated conditions with
specified by the purchaser. a coolant containing not less than 95 percent hydrogen
by vohtme.
4.1.1 Altitude NOTE — For safety reason, the hydrogen content should at all
times be maintained at 90 percent or more, it being assumed that
Height above sea level not exceeding 1000 m.
the other gas in the mixture is air.
For machines intended for operation on a site where
the altitude is in excess of 1000 m (see 6.3 of For calculating efficiency in accordance with IS 4889
IS 12802). from tests (excluding machines for traction vehicles),
the standard composition of the gaseous mixture shall
4.1.2 Ambient Temperature and Temperature of the
be 98 percent hydrogen and 2 percent air by volume,
Coolant at the specified values of pressure and re-cooled
4.1.2.1 Maximum ambient and coolant temperature temperature, unless otherwise agreed between the
manufacturer and the purchaser. Windage losses shall
The temperature of the air at operating site (which may be calculated at the corresponding density.
be the primary or the secondary coolant, depending on
the ventilation system of the machine) is subject to 4.2 Electrical Conditions
seasonal variation, but does not exceed 40°C.
4.2.1 Electrical Supply
For machines intended for operation on a site where ac machines within the scope of this standard shall be
the coolant temperature is low, by reason of high
suitable for three-phase 50 Hz, with voltage derived
altitude, see 6.3 of IS 12802.
from the nominal voltages given in IS 12360.
Machines intended for operation with a maximum In deriving rated voltages for machines, it is necessary
ambient temperature other than 40°C are covered by to take into consideration the differences between
5.3 of IS 12802. distribution and utilization system voltages.
NOTE — For large high-voltage ac generators, the voltage may
For machines having water-cooled heat exchangers,
be selected for optimum performance.
the temperature of the water at the intake to the heat
exchangers shall not exceed 25°C (see 6.1.4 of 4.2.2 Form and Symmetry of Voltage and Currents
IS 12802).
Machines shall be so designed as to be capable of
4.1.2.2 Minimum ambient and coolant temperatures operating under the conditions detailed in 4.2.2.1,
4.2.2.2 as appropriate (see also 4.2.2.3).
The minimum temperature of the air at the operating
4.2.2.1 In the case of an ac motor, the supply voltage
site (which may be the primary or the secondary
is assumed to be virtually sinusoidal as defined in item
coolant, depending on the ventilation system of the
(a) below. In the case of a polyphase motor, the supply
machine) is–15°C, the machine being installed and in
voltages are also assumed to forma virtually balanced
operation or at rest and de-energized.
system as defined in item (b) below. Should the limits
This applies to all machines except the following: in items (a), and (b), occur simultaneously in service
at the rated load, this shall not lead to any deleterious
a) ac machines with rated outputs exceeding temperature in the motor and it is recommended that
3300 kW (or lcVA) per 1000 r/rein, machines the excess resulting temperature rise or temperature
with rated outputs less than 600 W (or VA) and related to the limits specified in 13.2 should be not
all machines having a commutator or sleeve more than 10°C.
3
IS 4722:2001 +
the instantaneous value of the fundamental negative-sequence component nor the zero- ,,... .
component does not exceed 5 percent of the sequence component exceeds 5 percent of
amplitude of the latter; the positive sequence component.
In temperature-rise testing, as specified in /
4.2.2.3 In the case of a dc motor supplied from a static
IS 12802 such amplitude difference shall not
power converter, the pulsating voltage and current
exceed 2.5 percent.
affect the performance of the machine. Losses and
b) A polyphase voltage system is deemed to
temperature rise will increase and the communication
form a virtually balanced system of voltages
is more difficult compared with a dc motor supplied
if the negative sequence component does not
from a pure dc power source.
exceed 1 percent of the positive-sequence
component of the system of voltages over a Thus it is necessary for motors intended for static
long period, or 1.5 percent for a short period converter supply to be designed to operate under these
not exceeding a few minutes, and if the voltage conditions and it is often necessary to provide a dc
of the zero-sequence component does not motor with an external inductance for reducing the
exceed 1 percent of positive-sequence pulsation.
component.
NOTE — Motors shall be able to operate with a negative In order to obtain a proper combination of dc motor
sequence component of voltage of 2 percen~ but this and static power converter, the motor manufacturer
may involve very severe conditions which could affect should be consulted.
the life of motors.
4.3 Voltage and Frequency Variation During
In temperature-rise testing as, specified in IS 12802,
Operation
negative-sequence component shall be less than 0.5
percent of the positive sequence component of the 4.3.1 Generators complying with these requirements
system of voltages, the influence of zero-sequence shall be capable of suppl ying their rated output at rated
system being eliminated. By agreement between speed (and at rated power factor where separately
manufacturer and purchaser, the negative-sequence controllable) at a voltage that may vary between
component of the system of currents maybe measured 95 percent and 105 percent of their rated voltage.
instead of the negative-sequence component of the
voltages, and this shall not exceed 2.5 percent of the 4.3.2 Motors complying with these requirements
positive-sequence component of the system of shall be capable of providing their rated output with:
currents. .
a) The terminal voltage differing from its rated
NOTE — In the vicinity of large single-phase loads (for value by not more than * 6 percent, or
example, induction furnaces), and in rural areas particularly on
mixed industrial and domestic systems, supplies may be
b) The frequency differing from its rated value by
distorted beyond the limits set out above. Special not more than i 3 percent, or
arrangements will then be necessary between the manufacturer c) Any combination of (a) and (b).
and purchaser.
In the case of continuous operation at the extreme
4.2.2.2 In the case of an ac generator, the circuit which voltage limits specified above, the temperature-rise
it supplies is assumed to be virtually non-deforming limits stated in Table 1 and Table 2 of IS 12802 shall
and virtually balanced as defined in items (a) and (b) not exceed by more than:
below. Should the limits defined in items (a) and (b)
occur simultaneously in service at the rated load, this a) 10°C for machines of outputs up to and
shall not lead to any deleterious temperature in the including 1000 kW (or kVA), and
generator and it is recommended that the excess b) 5° C for machines of outputs exceeding 1000
resulting temperature rise of temperature related to the kW ( or kVA).
limits specified in Table 1, Table 2 and Table 3 of
Motors, when operated at the extreme conditions of
IS 12802 should be not more than 10”C.
voltage and frequency variation, may not necessarily
a) A circuit is considered to be virtually non- have their performance specified in the relevant
deforttiing if, when supplied by a sinusoidal, standard.
that is to say, none of the instantaneous values NOTE — Machines should not be operated in service at loads
differ from the instantaneous value of the same in excess of their rated load or under conditions differing from
phase of the fundamental wave by more than the rated conditions unless it is known that they are suitable for
such use.
5 percent of the amplitude of the latter.
I
IS 4722:2001
/I
IS 4722:2001
Table 3 Overspeed 7.4.2 The output ratings above 110 kW shall follow
(Clauses 4.2.2.2 and 17.1) the R20 series covered in IS 1076.
6
I
IS 4722:2001
“
9.1.2 Tests conformity with 9.1.1, shall be verified by 11 DUTY AND RATING
type tests on ac generators. The range of frequencies
The type of duty and class of rating of rotating ,$
measured shall cover all harmonics from rated
electrical machine shall be in accordance with
frequency up to 5000 Hz. Either the THF may be
IS 12824.
measured directly by means of a meter and associated ,.$,
,-.
; 1.6
The shaft need not be electrically connected to the
earth terminal unless the bearings are insulated and the
0.4 accessible parts of the shaft and of these insulated
0.2 bearings can be subjected to dangerous contact
voltages under fault conditions.
0 0 12.1.4 When an earth terminal is provided in the
FREQUENCY Iiz
terminal box, it shall be assumed that the earth
conductor is made of the same metal as the live
FIG. 1 WEIGHING CURVE
conductors.
10 CO-ORDINATION OF VOLTAGES AND 12.1.5 When an earth terminal is provided on the
OUTPUTS frame, the earth conductor may, by agreement, be
made of another metal (that is, steel). In this case, in
In the case of ac machines, the rated output should be
designing the terminal, proper consideration shall be
greater than the limits given below in terms of the rated
given to the conductivity of the conductor.
voltage:
Rated Voltage (UtJ Minimum Rated Output 12.1.6 The earth terminal shall be designed to
kV kW or kVA accommodate an earth conductor of crosssectional
area in accordance with the Table 2. If an earth
2< U. <3.3 100 conductor larger than the size given in the Table 2 is
3.3< u. <6.6 200 used, it is recommended that it should correspond as
nearly as possible to one of the other sizes listed.
6.6<U. <11 1000
7
IS 4722:2001
12.1.7 For other cross-sectional areas of the live 14.1 Occasional Excess Current for ac Generators
conductors, the earth protective conductor shall have
ac generators having rated outputs not exceeding 1200
cross-sectional areas at least equivalent to:
MVA shall be capable of withstanding a current equal
a) that of the live conductor for cross-sectional
to 1.5 times the rated current for not less than 30s.
areas less than 25 mm2,
b) 25 mm2forcross-sectional areas between25 14.1.1 ac generators having rated outputs above 1200
MVA shall be capable of withstanding a current equal
mm2 and 50 mm2,
to 1.5 times the rated current for a period which shall
c) 50 percent of that of the live conductor for
be agreed between the manufacturer and the
cross-sectional areas exceeding 50 mm2, and purchaser, but this period shall not be less than 15s.
d) the earth terminal shall be identified by
symbol_!_. 14.2 Occasional Excess Current for dc Machines
= and ac Motors (Except Commutator Motors)
12.2 Mounting Arrangements
Three-phase ac motors having outputs not exceeding
The designation for types of construction and 315 kW and rated voltage not exceeding 1 kV shall be
mounting arrangements shall be in accordance with capable of withstanding a current equal to 1.5 times
IS 2253. the rated current for not less than 2 min.
NOTE — For three-phasemotors having rated outputs above
12.3 Shaft Extension Key 315 kW and all single-phasemotors, no occasional excess
currentis specified.
When the machine shaft extension is provided with
keyway, it should be provided with a full key of normal 14.3 Occasional Excess Current for dc Machines
shape and length. and ac Commutator Motors
NOTE — The use of shaft extension key for the purpose of dc motors and generators and ac commutator motors
vibration measurement is covered in IS 12075.
shall be capable of withstanding at the highest
13 TEMPERATURE-RISE full-field speed (rated speed of a generator) and
corresponding armature voltage. A current equal to 1.5
13.1 The determination of temperature-rise of times the rated current for not less than 1 min.
rotating electrical machine delivering rated output
14.3.1 For large machines, a shorter time may be
under the rated condition of voltage, frequency and
agreed between the manufacturer and the purchaser
power factor shall be in accordance with IS 12802.
but this shall be not less than 30s.
13.2 The limits of temperature-rise applicable to
15 MOMENTARY EXCESS TORQUE FOR
rotating electrical machines shall be in accordance
MOTORS
with Table 1 to Table 3 of IS 12802.
15.1 Polyphase Induction Motors and dc Motors
14 OCCASIONAL EXCESS CURRENT FOR
(Excluding Motors in 15.2)
ROTATING MACHINES
The motors shall, whatever their duty and
The excess current capability of machines is given for construction, be capable of withstanding for 15 s,
the purpose of co-ordinating these machines with without stalling or abrupt change in speed (under
control and protective devices. Tests to demonstrate gradual increase of torque), an excess torque, of 60
these capabilities are not a requirement of this percent of their rated torque, the voltage and frequency
standard. (induction motors) being maintained at their rated
values. For dc motors, the torque maybe expressed in
The heating effect in the machine windings varies
terms of overload current.
approximately as the product of the time and the
square of current. A current in excess of the rated 15.1.1 Motors for duty Type S9 (see IS 12824) shall
current will result in increased temperattrte. Unless be capable of withstanding momentarily an excess
otherwise agreed between the manufacturer and the torque determined according to the duty specified.
purchaser, it can be assumed that the machine will not NOTE — For an approximate determination of the change of
be operated at the excess currents specified for more temperature due to the course of the current-related losses,
than a few short periods during the lifetime of the thermal equivalent time constant, determined according to
IS 12S02 maybe used. In addition in the case of commutator
machine. machine, attention, should be given to the limits of commutation
capability.
When an ac machine is to be used both as generator
and a motor, the excess current capability should be 15.2 Induction Motors for Specific Applications
the subject of agreement between the manufacturer
For motors intended for specific application which
and the purchaser,
require high torque (for example, for hoisting), excess
8
IS 4722:2001
b) For output equal to or greater than 100 kW: 19.1.1 For three-phase turbine-type machines, see
0.3 times the rated torque, and IS 5422.
0.5 times the locked rotor torque.
19.1.2 The check may be carried out by calculation or
16.2 Multi-Speed Three-Phase Motors by means of a test at a voltage of 50 percent of the rated
voltage or above.
0.3 times the rated torque.
8
9
IS 4722:2001
Table 4 Unbalanced Operating Conditions for 20.1.2 The test is considered satisfactory if no
Synchronous Machines harmful deformation occurs and if the requirements of
(Clause 18.1) the applied voltage dielectric test (see 30 and Table 6)
are met after the short-circuit test. For three-phase
Item Machine Type Maxtmum (12/1.)Maximum (lz/1n)2t turbine-type-machines (see IS 5422).
No. for Continuous for Oswatfon
Operation Und& Fault 20.2 Excitation
Conditions
(1) (2) (3) (4) 20.2.1 Generator Reserve Excitation
1 Salient pole machines When running at the rated operating temperature and
Indirectly cooled:
at rated speed, generators shall be capable of
motors 0.1 20
generators 0.08 20 developing for a short time their rated voltage and a
synchronous condensers 0.1 20 current eqtrat to 125 percent of the rated current
2 Directly cooled (innercooled) stator (at rated power factor for ac generators). For
and/or field separately excited or self excited machines, the field
motors 0.08 15 winding shall be designed accordingly. For machines
generators 0.05 15
with direct coupled exciter, the exciter shall be capable
synchronous condensers 0.08 15
cylindrical rotor synchronous of supplying the required excitation voltage.
machines NOTES
1 The operating conditions stated above are only intended to
3 Indirectly cooled rotoc
air-cooled 0.1 15 ascertain that the reserve excitation is sufficient and are not
hydrogen-cooled 0.1 10 associated with any temperature-rise condhion. However, if the
test is carried out after a temperature-rise test, it is recommended
4 Directly cooled (innercooled) rotor that its duration be limited in order to prevent winding
<350 MVA 0.08 8 temperatures from exceeding the limits of temperature resulting
>350 <900 MVA see Note 1 see Note 2 from the values specified in Tables 1 to 3 of IS 12802.
>900<1250MVA see Note 1 5 2 The above requirement shall not apply to compound
>1250< 1600 MVA 0.05 5 generators without any voltage regulation system.
NOTES 3 If the operating temperatureof field winding is not known, it
1 Forthesemachines,the@ue of12/1.k calculatedasfollows: shatl be considered to be 75°C for windkrg of Classes A, E and
B and 115°Cfor Classes F and H.
[1
s“ -350
12/1. = 0.08- —
3 x 104
The ceiling voltage shall not be less than 1.4 times the
2 For these mach:nes, the ~alue of (12/1,,)is calculated as
follows: rated excitation voltage for a minimum of 10s.
(12/[.)2[= (84.005 45) (S. - 350) 20.2.2 Ceiling Voltage (Up)
Where
S,,is the ratedapparentpowerin MVA
The ceiling voltage of the excitation system of “
10
IS 4722:2001
(
P = Q; ~n~ 24 POWER FACTOR
Uflr
If a statement of power factor is required for an “
tl = The time required for the excitation induction motor the purchaser shall specify at the time
voltage U. to increase from of enquiry the loads on which the statement is to be
. ‘4
Ufn to ( Ufn + 0.632 (UP - Ufn)). based. Tolerances are given in Table 5.
..” . . .
11
IS 4722:2001
b) Speedof dc seriesmotors (at full load and at working temperature) &20 percent, if (kW/l COOrev/rein)< 0.67
f 15 percent, if [0.67s (kW/l 000 revlmin) <2.51
+ 10 percent, if [2.5 S (kW/ 1000 rev/rein)< 101
f 7,5 percent, if (kW/100 rev/rein) 210
c) Speed of dc compound excitation motors (at full load and at working Tolerances as per item 4 (b) unless otherwise
temperature) agreed between the manufacturerand the purchaser.
5 a) Slip of induction motors (at full load and at working temperature):
1) machines having output 1 kW(or kVA) or more i 20 percent of the guaranteed slip
2) machines having output less than 1 kW (or kVA) i 30 percent of the guaranteed slip
b) Speed of ac motors with shunt characteristics (at full load and at working On the highest speed:
temperature) -3 percent of the synchronous speed
On the lowest speed:
+ 3 percent of the synchronous speed
6 inherent voltage regulation of dc generators, shut or separately excited at any f 20 percent of the guaranteed regulation at that
point on the characteristic point
7 Inherent voltage regulation of generatcxswithcompoundexcitation (at the rated f 20 percent of the guaranteed regulation, with a
powerfactor in the case of alternating current) minimum of +3 percent of the rated voltage
(TMs tolerance appfies to the maximum deviation
at any load between the observed voltage at that
load and a stmightlinedrawn between the points of
guaranteed no-load and full-load voltage)
8 Locked rotor current of cage induction motors with short-circuited rotor and +20 percent of the guaranteed current (no lower
with any specified starting apparatus limit)
9 Peak values of short-circuit of ac generator under specified conditions * 30 percent of the guaranteed value
10 Steady short-circuit current of an ac generator under specified conditions * 15 percent of guaranteed value
12
IS 4722:2001
a) Rated frequency in Hz and number of phases; 29.2.1 Unless otherwise specified when inviting
b) Power factor; tenders, the purchaser if so desired by the
c) Winding connectors designated by appropriate manufacturer, shall accept manufacturer’s certificate,
symbols in accordance with IS 4728; as evidence of the compliance of the machine with the
d) Rated field (excitation) current and voltage at requirements of temperature-rise test (see IS 12802),
rated output; and 14 and 15 on a machine identical in essential details
e) The permissible overspeed, if applicable (for with the one purchased, together with routine tests on
example, turbine-type generators and each individual machine. In the case when a batch of
hydraulic-turbine driven generators). 20 or more similar machines is supplied on one order,
type
.- tests, as specified, shall be made on one of these
27.2.3 Synchronous Motor or Synchronous Induction machines, if the purchaser so requires.
Motor or Condensers
29.2.2 Certificates of routine tests shall show that the
The rating plate shall carry the following information machine purchased has been run and has been found
or rating plate, in addition to those given in 27.1: to be electrically and mechanically sound and in
a) Rated frequency in Hz and number of phases; working order in all particulars.
b) Winding connections designated by ap-
29.2.3 If so specified, at the time of enquiry, tests shall
propriate symbols in accordance with IS 4728;
be carried out at the manufacturer’s works in the
c) Rated input in kVA or MVA, in case of presence of the purchaser or his representative to
synchronous condensers; ensure that the machine complies in every respect with
d) Rated current in amperes or rated output (for the requirements given in this draft standard and
motors) and input (for condensers) agreed to earlier at the time of agreement.
e) Rated field (excitation) current and voltage at
rated input for separately excited machines; 29.2.4 Certificates of all type tests together with a
Power factor; record of any alterations, whether essential or not,
f)
For asynchronous motor intended to be started which have been made to the machine since the type
g)
as an induction motor, standstill voltage be- tests were carried out, shall be kept available by the
tween the sliprings (or secondary terminals) in manufacturer for inspection.
starting condition; 29.3 Classification of Tests
h) Secondary current for synchronous induction
motOrs; and NOTE — Impulse tests on windings of rotating electrical
machines are under consideration.
j) Permissible overspeed, if applicable.
29.3.1 Induction Motors and Generators
27.2.4 Irrduction Motor and ac Commutator Motor
29.3.1.1 Type tests
The following information, in addition to 27.1, shall
be given on the rating plate: The following shall constitute the type tests:
13
c. ,
————
,“
A
IS 4722:2001
a) Measurements of stator resistance and rotor d) Measurement of leakage reactance and potier
resistance of slipring motors; reactance (for generators only);
b) No load running of motor and reading of volt- e) Measurement of open-circuit characteristic
age, current, power input and speed; (for generators only); -.
c) Open circuit voltage ration on slipring f) Measurement of short-circuit characteristic
motors: (for generators only);
d) Reduced voltage running up test at no load (for g) Efficiency test;
.“
squirrel cage motors only) h) Temperature-rise test;
To check the ability of the motor to run up to j) Occasional excess current test;
full speed on no load, the value of reduced k) Overspeed test
voltage in case of motors up to 37 kW shall be m) Insulation resistance test (both before and after
I/@of the rated line voltage in each direction Dielectric test);
of rotation of motors. n) Dielectric tes~
For motors above 37 kW, the value of reduced P) Starting current and torque test (for
voltage shall be l/~ of rated line voltage of synchronous motors);
less but only in the specified direction of @ Determination of deviation of voltage wage-
rotation of motov form from sinusoidal (for generators only);
e) Locked rotor readings of voltage, current, r) Measurement of bearing current for machines
power input and torque of squirrel cage above 1000 kW;
motors; s) Short-circuit withstand test and measurement
NOTE —This test may be made at a reduced voltage. of reactance and time constants (for generators
f-) Full load values of voltage, current, power above 1000 kW only); and
input and slip; t) Pressure test on coolers for closed circuit
g) Temperature-rise test; cooling.
h) Momentary excess torque;
29.3.2.2 Routine tests
j) Insulation resistance test (both before and after
the high Dielectric tests); and The following shall constitute the routine tests:
k) Dielectric tests.
a) Measurement of winding resistance;
29.3.1.2 Routine tests b) Insulation resistance test;
c) Phase sequence test;
The following shall constitute the routine tests:
d) Regulation test (for generators only);
a) Insulation resistance tests (before Dielectric e) Measurement of open-circuit characteristic
..
test only); (for generators only);
b) Dielectric test; f) Measurement of short-circuit characteristic
c) No load running of motor and reading of (for generators only)(see Note 1);
current in the three-phase and voltage; @ Dielectric test;
d) Locked-rotor readings of voltage, current h) Measurement of bearing currents for machines
power input at a suitable reduced voltage; above 1000 kW; and
e) Reduced voltage running up test at no load to j) Pressure test on coolers for closed-circuit
check the ability of the motor to run up to full cooling.
speed on no load in each direction of rotation
with l/fi of the rated line voltage applied to 29.3.3 de Motors and Generators
the stator terminals (for squirrel cage motors
29.3.3.1 Type tests
only); and
f) Open circuit voltage ratio (for slipring motors The following shall constitute the type tests:
only).
a) Measurement of winding resistance;
29.3.2 Synchronous Motors and Generators b) Measurement of insulation resistance;
c) Determination of open-circuit characteristics
29.3.2.1 ;ype tests
(subject to agreement between the purchaser
and the supplier);
The following shall constitute the type tests:
d) Determination of regulation characteristics
a) Measurement of winding resistance; (subject to agreement between the purchaser
b) Phase sequence test; and the supplier);
c) Regulation test (for generators only);
14
IS 4722:2001
e) Determination of external characteristics( for 30.1.4 The test shall be commenced at a voltage of not
generators only) this test shall be applicable for more than one half of the full test voltage. The voltage
generators having output ratings above shall then be increased to the full value steadily or in
150 kW and shall be subject to agreement steps of not more than 5 percent of the full value, the
between the purchaser and the supplie~ time allowed for the increase of the voltage from half
f) Temperature-rise test; value being not less than 10 s. The full test voltage
.9 Commutation-rise test; shall then be maintained for 1 minute in accordance
h) Determination of efficiency of machines; with the value as specified in Table 6.
NOTE — For sliprings alternators these tests are 30.1.5 During the routine testing of quantity produced
conducted with respect to main field current and for
brusbless these tests are carried out with respect to field machines, the one-minute test may be replaced:
current.
a) for machines up to 200 kW (or kVA) and with
j) Load saturation characteristics (for exciters
rated voltages up to 660 V, by a test of
only);
approximately 5 s at the normal test voltage
k) Nominal exciter response for dc exciters specified in Table 6; and
(subject to agreement between the purchaser
b) for machines up to 5 kW (or kVA) by a test of
and the supplier);
approximately 120 percent of the normal test
m) Overspeed test; and voltage in Table 6.
n) Dielectric test.
The test voltage being applied by means of probe.
29.3.3.2 Routine tests
30.1.6 The high voltage test at full voltage made on
The following shall constitute the routine tests:
the windings on acceptance shall not be repeated. If,
a) Measurement of winding resistance; however, a second test is made at the request of the
b) Measurement of insulation resistance, before purchaser after further drying if considered necessary,
and after high voltage test; the voltage shall be 80 percent of the voltage specified
c) Commutation test; and in Table 6.
d) Dielectric test.
30.1.7 Completely rewound windings shall be tested
30 ELECTRIC STRENGTH at the full test voltage for new machines.
30.1 Dielectric Test 30.1.8 When a user and a repair contractor have
agreed to carry out dielectric tests in cases where
30.1.1 The high voltage shall be applied between the windings have been partially rewound or in the case
windings under test and the frame of the machine with of an overhauled machine, the following provisions
the core and the windings not under test connected to are recommended:
the frame. It shall be applied only to a new and
completed machine with all its parts in place under a) Partially rewound windings are tested at
conditions equivalent to normal working conditions 75 percent of the test voltage for a new
and shall be carried out at the manufacturer’ works. machine. Before the test, the old part of the
When the temperature-rise test is carried out, the winding shall be carefully cleaned and dried;
and
dielectric test shall be carried out immediately after
b) Overhauled machines after cleaning and
this test.
drying are subjected to a test at a voltage equal
30.1.2 In the case of polyphase machines with rated to 1.5 times the rated voltage with a minimum
voltage above lkV having both ends of each phase of 1 000 V if the rated voltage is equal to or
individually accessible, the test voltage shall be greater than 100 V and a minimum of 500 volt
applied between each phase and the frame, with the if the rated voltage is less than 100 V.
core and the other phases and windings not under test
connected to the frame. 30.2 Insulation Resistance Test
30.1.3 The test voltage shall be of power- 30.2.1 The procedure for determination of insulation
resistance of insulated parts of the machines given in
frequency and shall be as near as possible to sine wave
form. IS 7816 shall be followed. The value of recommended
dc voltage at which the test may be carried out are
given in Table 7.
15
A
IS 4722:2001
7) Exciters (except as below) As per the windhrgs to which they are connected
Exception 1 — Exciters of synchronous motors (Including 1000 V + twice the rated exciter voltage with at minimum of
synchronous induction motors) if connected to earth or 1500V
disconnected from the field windings during starting.
Exception 2 — Separately excited field windings of exciters
Isee S1No. (4)]
8) Assembled group machines and apparatus A repetition of the test in S1No. 1 to 6 above should be avoided, if
possible, but if a test on an assembled group of several pieces of
new apparatus each one of which has previously passed its high
voltagetest, is made the test voltage to be applied to such assembled
group shall be 80 percent of the lowest test voltage appropriate for
any part of the group (see Note 4)
NOTES
1 For two-phase windings having one terminal in common, the voltage in the formula shafl be the highest rms voltage arising between
any two terminals during operations.
2 High-voltage tests on machines having graded insulation should be the subject of an agreement between the manufacturer and the
purchaser.
3 The voltage occuring between the terminals of the field windings, or sections thereof under the specified starting conditions maybe
measured at any convenient reduced supply voltage and the voltage so measured shall be increased in the ratio of specified starting
voltage to the test supply voltage.
4 For windings of one or more machines connected together elcctnca\Iy the voltage to be considered is the maximum vohage that
occurs in relation to earth.
16
.
‘..-.! L
------ -.. . .
1s 47LL : Z(JU1
Table 7 Test Voltages for Insulation Resistance standard. In case of type test, this is to be carried out
(Clause 30.2.1) at the conclusion of the temperature-rise test of the
machine.
Rated Voltage Test Voltagefor Insulation
ac Resistance, dc 32 OVERSPEED TEST
(1) (2)
The test, if agreed, shall be made, to verify the
Up to 660 5MIv requirements of 17 of this standard.
Above 660 up to and 1000 V or higher value as agreed
includhrg I 100 between the manufacturer and the 33 UNBALANCED CURRENTS OF
mer
SYNCHRONOUS MACHINES
30.2.2 The minimum values of insulation resistance
The test, if agreed, shall be carried out to verify the
shall be determined by the following empirical
provisions of 18 of this standard.
relationship:
Rm=kV+l 34 SHORT-CIRCUIT CURRENT TEST
Where
The test, if agreed, shall be carried out to verify the
R. = Minimum insulation resistance in
provisions of 19 and 20 of this standard.
megaohms at 40°C of entire machine
windings; and 35 OCCASIONAL EXCESS CURRENT
kv = Rated voltage of the motor, in kilovolts.
This test shall be carried out to verify the provisions
NOTE — Rm at 40° C is in effectone megaohmper 1000 volts
plus one megaohm. of 14 of this standard.
30.2.3 ac machines rated above 3.3 kV and having 36 MOMENTARY EXCESS TORQUE
output more than 1 000 kW may also be tested for
This test shall be earned out to verify the provisions
polarization index (PI) of insulated windings. The
of 15 of this standard.
method for measurement of polarization index shall be
in accordance with IS 7816. The minimum values of 37 PULL UP TORQUE FOR MOTORS
PI (lRlornin/lRl rein) shall be 1.5 for Class A, 2.0 for
Class B and 1.75 for Class E insulation systems. This test shall be carried out to verify the provisions
NOTE — The recommended minimum value of PI
of 16 of this standard.
(!~=vhq~~)shall be 1.3 for all classes of insulations of the
windings. 38 LIMITS OF VIBRATION
31 COMMUTATION TEST If agreed between the user and the manufacturer, this
test may be arranged to verify the specified limits of
31.1 The commutation test shall be made to verify the vibration according to IS 12075.
machine meets the requirements specified in 22 of this
ANNEX A
(Clause 2)
LIST OF REFERRED INDIAN STANDARDS
17
.—f -,
4
IS 4722:2001
ANNEX B
(Clause 22.1)
GRADES OF SPARKING
E!ln
ABSENCE OF SPARKING
(BLOCK COMMUTATION)
MODERATE SPARKING
THE BRUSHES
ON ALL
No. 1+
No.3
No.1+ No.4
B
SLIGHT SPARKING UNDER MOST VICIOUS SPARKING ON ALL THE
OF THE BRUSHES BRUSHES WITH STREAMERS
OR GLOWING
18
,-
---
.
IS 4722:2001
Traces of black spots on commutator which can be Permitted only for direct on load starting and for the
removed by petrol. Traces of burning on brushes. starting period. Easily spottable blackening of
commutator which cannot be removed by petrol.
B-1.3 No. 2
Burning and slight damaging of brushes.
Permitted only for short time overloads. Trace of B ~ ~ No d
black spots on commutator which cannot be removed - “ “
by petrol. Traces of bums on brushes. To much blackening of commutator which cannot be
removed by petrol. Damaging of brushes.
ANNEX C
(Clauses 28 and 31.3)
INFORMATION TO BE GIVEN WITH ENQUIRY AND ORDER
19
.-.
$,
d
IS 4722:2001
“
0 Breakaway torque required; and f) Direction of rotation of machine and phase
g) Any information regarding the driven machine sequence of supply;
which has a bearing upon the torque required /3) Method of starting to be employed;
during the accelerating period, the kinetic h) Breakaway torque required;
energy of the moving parts to be accelerated, j) Nature of the load and any information regard-
and the number of starts during a specific ing the driven machine which has a bearing
period. upon the torque required during the accelerat-
ing period, the kinetic energy of the moving ,’
C-4 ADDITIONAL INFORMATION FOR ac
parts to be accelerated, and the number of
GENERATOR
starts during a specified period;
When enquiring for and ordering an ac generator, the k) Any information having bearing on the use of
following particulars should be supplied in addition to the motor for supplying wattless current.
the requirements of C-1: Unless otherwise specified, the machine will
a) Frequency, in Hz; be designed for unity power factor at its rated
b) Number of phases and in the case polyphase mechanical output;
machines, the interconnection between the m) Whether the machine is to have its own exciter
phases, if any; driven through the motor shaft, or whether the
c) Electrical output, in kVA or MVA; excitation is to be obtained from a separate
d) Rated voltage; source; and
e) Power-factor, if other than 0.8; n) Excitation voltage, if the motor is not to be
f) Current, in amperes; provided with its own exciter.
g) Speed, in revolutions per minute, at no-load
and at rated load; C-6 ADDITIONAL INFORMATION FOR
h) Direction of rotation; INDUCTION MOTOR OR ac COMMUTATOR
MOTOR
j) Whether the machine is to have its own exciter,
and if so, the methods of drive or whether the When enquiring for and ordering an induction motor,
excitation is to be obtained from a separate the following particulars should be supplied in
source; addition to the requirements of C-1:
k) Excitation voltage, if the generator is not to be
provided with its own exciteq a) Frequency, in Hz;
m) Conditions to be met in cases of parallel b) Number of phases;
operation; c) Mechanical output, in kilowatt;
n) Whether the neutral point is to be brought out d) Rated voltage;
to a terminal to deal with current in the neutral e) Speed in revolutions per minute, at the rated
line in normal service, and, if so, the magnitude output; .
of current in amperes to be carried; f) Direction of rotation;
P) Short-circuit ratio; and g) Rotor, whether squirrel cage or slipring;
q) Under excited MVAR. h) Type of slipring gear, whether continuously
NOTE — Similar information should be furnished for rated or for starting purposes only and whether
synchronouscondensers. to be fitted with brush lifting and/ or short-
circuiting arrangements and if inler-iocks are
C-5 ADDITIONAL INFORMATION FOR
required;
SYNCHRONOUS MOTOR OR
j) Method of starting to be employed;
SYNCHRONOUS INDUCTION MOTOR
k) Breakaway torque in terms of the rated load
When enquiring for and ordering a synchronous torque and the corresponding breakaway start-
motor, the following particulars should be supplied in ing current which may be taken from the
addition to the requirements of C-1: supply with the starting apparatus in circuit;
a) Frequency, in Hz; m) Nature of load and any information regarding
b) Number of phases and, in the case of polyphase the driven machine which has a bearing upon
machine, the interconnection between the the torque required during the acceleration
phases, if any; period, the kinetic energy of the moving parts
c) Mechanical output, in kilowatt; to be accelerated, and the number of starts
d) Rated voltage; during a specified period; and
e) Speed, in revolutions per minute; n) Where possible, fault capacity of the system to
which the motor is connected.
20
/I
Bureau of Indian Standards
BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods
and attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in “writing of BIS. This does not preclude the free use, in the cotrrse of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publications), BIS.
Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of
‘BIS Catalogue’ and ‘Standards: Monthly Additions’.
This Indian Standard has been developed from Doc : No. ET 15 ( 3059 ).
Headquarters :
Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002 Telegrams : Manaksanstha
Telephones :323 Of 31, 3233375,3239402 (Common to all offices)