SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - June 2008) Rev 3 30-Jun-08

SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Air Handling Unit (AHU) Installation SAIC-K-4005 15-Dec-09 HVAC


PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Air Handling Units (AHU's) shall be mounted on a concrete


SAES-K-001
A1 housekeeping pad, at a minimum of 100 mm (4") above the floor or a
Para 5.1.1
minimum of 150 mm (6") above unpaved ground
AHU's shall be installed at the location indicated on the drawings and in SAES-K-001
A2
accordance with details of mounting Para 5.1.7
Evaporators of air handling units shall be mounted a minimum of 150 mm SAES-K-001
A3
(6 inch) off the floor. Para 5.3.4.1
Equipment clearance shall be provided with a minimum of 1 m clearance
on each side of equipment with openable panel or controls, unless SAES-K-001
A4
equipment manufacturer requires greater clearances. Adequate space Para 5.1.4
shall be provided for coil removal
SAES-K-001
A5 Fans shall be V-belt driven.
Para 4.8.9.3
A raw water hose bib with vacuum breaker shall be provided within close
proximity (not to exceed 10 feet) of HVAC equipment that require
SAES-K-001
A6 periodic washing.
Para 5.1.9
Note: Whether the equipment requires periodic washing or not is
determined by either the designer, manufacturer or proponent.

Reciprocating compressors shall be vibration isolated from the unit, and


SAES-K-001
A7 frame shall have vibration isolation (such as a vibration pad) between
Para 4.8.14.2
equipment and equipment base.

Casings shall include doors to provide maintenance and removal access SAES-K-001
A8
for all fans, motors, coils, filters, and humidifiers. Para 4.8.8.5

Access doors or frames shall have resilient gasketing material to prevent


SAES-K-001
A9 air leakage. Access doors shall have corrosion-resistant hinges and
Para 4.8.8.5
positive latches.*
SAES-K-001
A10 Vibration isolators shall be provided between AHU and foundations.
Para 4.8.14.1
The tag or name plate shall be located such that the information is visible SAES-K-001
A11
and can be read after equipment installation Para 4.8.1.2.3
* Verification is required by checking the equipment submittal if verification is not possible by visual inspection
REMARKS:

REFERENCE DOCUMENTS:

1-SAES-K-001 -- Heating, Ventilating and Air Conditioning (HVAC), 25 November, 2006

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

Page 1 of 2
Quality Record Approved:
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED