You are on page 1of 90

Client ETCHO

Project BURRIAL TAK FOUNDATION


Subject DESIGN OF BURIAL TANK FOUNDATION

DESIGN OF EQUIPMENT PIT


0.65 10.000

Geometry of Tank 0.500


Short Side of Tank 3.50 m
Long side of Tank 11.90 m
Clear Depth of tank below ground .: 6.500 m 3.000
Hight of tank above ground.: 0.20 m
Thickness of Wall 0.25 m
Thickness of Base Slab 0.25 m
Projection of base slab 0.00 m
Clear Height of pedestal 0.75 m 12.400
Length of pedestal 3.00 m
Width of pedestal 0.50 m Y axis Foundation Plan
Dist of cl of pedestal in plan from wall 0.5 m
Left proj'n of pedestal in plan from wall 0.65 m bottom of pit = el 95.0
Spacing of pedestal 10.00 m

Loading Data
For Equipment load refer page 6
Platform Dead + Live Load 21.00 kN
Surcharged Load 10.00 kN/m2
Height of water table below ground 0.00 m

Parameter .:
Unit Weight of Concrete .: 35 kN/m3
Unit Weight of Soil .: 18 kN/m3
Unit Weight of Water .: 10 kN/m3
Angle of repose 15 o
Elevation
Kh Seismic coeff. 0.267807 = (1-Kv)tan phi
Ko at Rest 1- sin f
= 1 - SIN ( 15x 3.14 / 180)
0.741181
Weight of soil wedge for seismic 1 1
We 2 [
H H *tan 45o − ( 2
φ )]
γ
=0.5 x6.75mx (6.75m) x TAN ( ( 45 - 0.5 x 15 ) x 3.14 / 180 ) ) x 18 kN/mm
314.4359 kN
Net allowable pressure.: 50 kN/m2
fcu 25 N/mm2
fy 420 N/mm2
g f 1.5
Es 200 kN/mm2 200000000 KN/M2
Ec = 5.5 x (fcu / g f)^ 0.5
= 5.5 x ( 25 / 1.5 )^ 0.5
22.5 kN/mm2
Poisson ratio 0.4
Assumptions in the Design
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

1 The earth pressure at rest is taken for design considering all the walls are restrained by the perpendicular walls .

2 Safety against sliding is not checked since the active/at rest pressure at one wall is resisted by the passive press
other end wall .

3 Surcharge load is taken as 10 kN/m2

4 Wind loads is not considered since the structure is below the GL.

5 Since there is no loading on the walls from inside no tensions are developed on the wall

6 Since projection of wall above GL is only 0.2 m , wall is analyzed for height soil loading is taken on the projected

7 Design factor for seismic is considered as 1.2 combined with 1.6 for imposed load cases except earth press for

8 Maximum Water level is at ground level. This spreadsheet is not applicable if water level is above ground level

9 Buoyancy has been checked for upward trust of water equal to water displaced by tank pit against self weight of
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

(A) Long Wall Analysis


Length of Tank .: 12.150
Height of Tank .: 6.625
Mx
a= 6.075 m
6.625 m b= 6.625 m
Rx
a/b 0.916981

Ry My
12.150 m

+ +

rc = 10kN/m2 x 0.74 rs =0.74 x 18kN/m3 x 6.625 m rw = 10kN/m3 x(6.625-0)m x(1-


rc = 7.41 rs =88.38583 kN/m2 rw = 17.1467617
(a) Due to Surcharge (b) Due to Soil Pressure c) Due to water
pressure

(A-a) Analysis in vertical Direction

Base Support Bending Moment (-ve) in vertical direction


a) Vertical bending coefficient due to surcharge.:
amy = 0.243 My.:amy*r*b2 =0.24 x 7.41 kN/m2 x
b) Vertical bending coefficient due to soil .:
amy = 0.0845 My.:amy*r*b2 =0.08 x 88.39 kN/m2
c) Vertical bending coefficient due to Water .:
amy = 0.0845 My.:amy*r*b2 =0.08 x 17.15 kN/m2
d) Vertical bending coefficient due Seismic
amy = 0.1585 My.:amy*r*b2 =0.16 x 84.21 kN/m2

Total UnFactored Moment 79.05 + 327.802 + 63.593 + 585.808


1056.2525 kNm /m
Total Factored Moment 79.05 x 1.4 + 327.802 x 1.2 + 63.593 x 1.2 + 585.808 x 1.2
1283.313 kNm /m

Maximum Shear Force at base support IN VERT DIRECT


a) Shear force due to surcharge for vertical direction steel
aRy = 0.845 Ry.:aRy*r*b =0.85 x 7.41 kN/m2 x
b) Shear force due to soil for vertical direction steel
aRy = 0.4584 Ry.:aRy*r*b =0.46 x 88.39 kN/m2
c) Shear force due to water for vertical direction steel
aRy = 0.4584 Ry.:aRy*r*b =0.46 x 17.15 kN/m2
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

d) Shear force due to Seismic for vertical direction steel


aRy = 0.3866 Ry.:aRy*r*b =0.39 x 84.21 kN/m2

Total UnFactored Shear 41.492 + 268.419 + 52.073 + 215.676


577.6601 kN /m
Total Factored Shear 41.492 x 1.4 + 268.419 x 1.2 + 52.073 x 1.2 + 215.676 x 1.2
701.49057 kN /m

Midhight Bending Moment (+ve) in vertical direction


a) Vertical bending coefficient due to surcharge.:
amy = 0.1232 My.:amy*r*b2 =0.12 x 7.41 kN/m2 x
b) Vertical bending coefficient due to soil .:
amy = 0.0444 My.:amy*r*b2 =0.04 x 88.39 kN/m2
c) Vertical bending coefficient due to water .:
amy = 0.0444 My.:amy*r*b2 =0.04 x 17.15 kN/m2
d) Vertical bending coefficient due to Seismic .:
amy = 0.0788 My.:amy*r*b2 =0.08 x 84.21 kN/m2

Total UnFactored Moment 40.078 + 172.241 + 33.415 + 291.241


536.97467 kNm /m
Total Factored Moment 40.078 x 1.4 + 172.241 x 1.2+ 33.415 x 1.2 + 291.241 x 1.2
652.38521 kNm /m

Mymidspan 652.3852 kNm /m Mymidspan

Tank Tank
Soil Soil

MySupport 1283.313 kNm /m MySupport


Ry 701.4906 kN /m Ry
Factored Values UnFactored Values
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

(A-b) Analysis in Horizontal Direction

Side Support Bending Moment (-ve) in horizontal direction


a) Horizontal bending Coefficient due to surcharge
amx = 0.2613 Mx.:amx*r*b2 =0.26 x 7.41 kN/m2 x
b) Horizontal bending Coefficient due to soil
amx = 0.0644 Mx.:amx*r*b2 =0.06 x 88.39 kN/m2
c) Horizontal bending Coefficient due to water
amx = 0.0644 Mx.:amx*r*b2 =0.06 x 17.15 kN/m2
d) Horizontal bending Coefficient due to Seismic
amx = 0.1969 Mx.:amx*r*b2 =0.2 x 84.21 kN/m2 x

Total UnFactored Moment 85.003 + 249.828 + 48.466 + 727.732


1111.029 kNm /m
Total Factored Moment 85.003 x 1.4 + 249.828 x 1.2 + 48.466 x 1.2 + 727.732 x 1.2
1350.2355 kNm /m

maximum Horizontal Shear Force at sides


a) Shear force due to surcharge for horizontal direction steel
aRx = 1.2115 Rx.:aRx*r*b =1.21 x 7.41 kN/m2 x
b) Shear force due to soil for horizontal direction steel
aRx = 0.1985 Rx.:aRx*r*b =0.2 x 88.39 kN/m2 x
c) Shear force due to water for horizontal direction steel
aRx = 0.1985 Rx.:aRx*r*b =0.2 x 17.15 kN/m2 x
d) Shear force due to Seismic for horizontal direction steel
aRx = 1.013 Rx.:aRx*r*b =1.01 x 84.21 kN/m2

Total UnFactored Shear 59.489 + 116.233 + 22.549 + 565.131


763.40175 kNm /m
Total Factored Shear 59.489 x 1.4 + 116.233 x 1.2 + 22.549 x 1.2 + 565.131 x 1.2
927.97981 kNm /m

Midspan Bending Moment (+ve) in horizontal direction


Horizontal bending Coefficient due to surcharge
amx = 0.1008 Mx.:amx*r*b2 =0.1 x 7.41 kN/m2 x 6
Horizontal bending Coefficient due to soil
amx = 0.0276 Mx.:amx*r*b2 =0.0276 x 88.39 kN/m
Horizontal bending Coefficient due to water
amx = 0.0276 Mx.:amx*r*b2 =0.0276 x 17.15 kN/m
Horizontal bending Coefficient due to Seismic
amx = 0.0732 Mx.:amx*r*b2 =0.0732 x 84.21 kN/m

Total UnFactored Moment 32.791 + 107.069 + 20.771 + 270.543


431.17467 kNm /m
Total Factored Moment 32.791 x 1.4 + 107.069 x 1.2 + 20.771 x 1.2 + 270.543 x 1.2
523.96783 kNm /m

Inside Tank
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

MxSupport Rx: MxSupport


1350.235 927.980 1111.029
kNm / m kN / m kNm / m
Mxmidspan
523.968 kNm / m
Factored Values
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

(B) Short Wall Analysis

Length of Tank .: 3.750


Mx Height of Tank .: 6.625

6.625 m a= 1.875
Rx b= 6.625

a/b 0.28
Ry My
3.750 m

+ +

rc = 10kN/m2 x 0.74 rs =0.74 x 18kN/m3 x 6.625 m rw = 10kN/m3 x(6.625-0)m x(1-


rc = 7.412 rs = 88.386 kN/m2 rw = 17.147 kN/m
(a) Due to Surcharge (b) Due to Soil Pressure c) Due to water
pressure

(B-a) Analysis in vertical Direction

Base Support Bending Moment (-ve) in vertical direction


a) Vertical bending coefficient due to surcharge.:
amy = 0.0534 My.:amy*r*b2 =0.05 x 7.41 kN/m2 x
b) Vertical bending coefficient due to soil .:
amy = 0.0325 My.:amy*r*b2 =0.03 x 88.39 kN/m2
c) Vertical bending coefficient due to Water .:
amy = 0.0325 My.:amy*r*b2 =0.03 x 17.15 kN/m2
d) Vertical bending coefficient due Seismic
amy = 0.0209 My.:amy*r*b2 =0.02 x 84.21 kN/m2

Total UnFactored Moment 17.371 + 126.078 + 24.459 + 77.245


245.153 kNm /m
Total Factored Moment 17.371 x 1.4 + 126.078 x 1.2 + 24.459 x 1.2 + 77.245 x 1.2
297.658 kNm /m

Maximum Vertical Shear Force at base support


a) Shear force due to surcharge for vertical direction steel
aRy = 0.4572 Ry.:aRy*r*b =0.46 x 7.41 kN/m2 x
b) Shear force due to soil for vertical direction steel
aRy = 0.3236 Ry.:aRy*r*b =0.32 x 88.39 kN/m2
c) Shear force due to water for vertical direction steel
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

aRy = 0.3236 Ry.:aRy*r*b =0.32 x 17.15 kN/m2


d) Shear force due to Seismic for vertical direction steel
aRy = 0.1336 Ry.:aRy*r*b =0.13 x 84.21 kN/m2

Total UnFactored Shear 22.45 + 189.486 + 36.76 + 74.533


323.229 kNm /m
Total Factored Shear 22.45 x 1.4 + 189.486 x 1.2 + 36.76 x 1.2 + 74.533 x 1.2
392.364 kNm /m

Midhight Bending Moment (+ve) in vertical direction


a) Vertical bending coefficient due to surcharge.:
amy = 0.0134 My.:amy*r*b2 =0.01 x 7.41 kN/m2 x
b) Vertical bending coefficient due to soil .:
amy = 0.0087 My.:amy*r*b2 =0.01 x 88.39 kN/m2
c) Vertical bending coefficient due to water .:
amy = 0.0087 My.:amy*r*b2 =0.01 x 17.15 kN/m2
d) Vertical bending coefficient due to Seismic .: .
amy = 0.0047 My.:amy*r*b2 =0 x 84.21 kN/m2 x 6

Total UnFactored Moment 4.359 + 33.75 + 6.547 + 17.371


62.028 kNm /m
Total Factored Moment 4.359 x 1.4 + 33.75 x 1.2 + 6.547 x 1.2 + 17.371 x 1.2
75.304883 kNm /m

Mymidspan 75.305 kNm /m Mymidspan

Tank Tank
Soil Soil

MySupport 297.658 kNm /m MySupport


Ry 392.364 kN /m Ry
Factored Values UnFactored Values
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

(B-b) Analysis in Horizontal Direction

Side Support Bending Moment (-ve) in horizontal direction


a) Horizontal bending Coefficient due to surcharge
amx = 0.0852 Mx.:amx*r*b2 =0.09 x 7.41 kN/m2 x
b) Horizontal bending Coefficient due to soil
amx = 0.0151 Mx.:amx*r*b2 =0.02 x 88.39 kN/m2
c) Horizontal bending Coefficient due to water
amx = 0.0151 Mx.:amx*r*b2 =0.02 x 17.15 kN/m2
d) Horizontal bending Coefficient due to Seismic
amx = 0.0701 Mx.:amx*r*b2 =0.07 x 84.21 kN/m2

Total UnFactored Moment 27.716 + 58.578 + 11.364 + 259.086


356.74377 kN /m
Total Factored Moment 27.716 x 1.4 + 58.578 x 1.6 + 11.364 x 1.6 + 259.086 x 1.2
433.63579 kN /m

maximum Horizontal Shear Force at sides


a) Shear force due to surcharge for horizontal direction steel
aRx = 0.5101 Rx.:aRx*r*b =0.51 x 7.41 kN/m2 x
b) Shear force due to soil for horizontal direction s.
aRx = 0.0326 Rx.:aRx*r*b =0.03 x 88.39 kN/m2
c) Shear force due to water for horizontal direction steel
aRx = 0.0326 Rx.:aRx*r*b =0.03 x 17.15 kN/m2
d) Shear force due to Seismic for horizontal direction steel
aRx = 0.4775 Rx.:aRx*r*b =0.48 x 84.21 kN/m2

Total UnFactored Shear 25.048 + 19.089 + 3.703 + 266.387


314.22709 kNm /m
Total Factored Shear 25.048 x 1.4 + 19.089 x 1.2 + 3.703 x 1.2 + 266.387 x 1.2
382.08202 kNm /m

Midspan Bending Moment (+ve) in horizontal direction


Horizontal bending Coefficient due to surcharge
amx = 0.0432 Mx.:amx*r*b2 =0.04 x 7.41 kN/m2 x
Horizontal bending Coefficient due to soil
amx = 0.097 Mx.:amx*r*b2 =0.097 x 88.39 kN/m2
Horizontal bending Coefficient due to water
amx = 0.0097 Mx.:amx*r*b2 =0.0097 x 17.15 kN/m
Horizontal bending Coefficient due to Seismic
amx = 0.0335 Mx.:amx*r*b2 =0.0335 x 84.21 kN/m

Total UnFactored Moment 14.053 + 376.293 + 7.3 + 123.814


521.46062 kNm /m
Total Factored Moment 14.053 x 1.4 + 376.293 x 1.2 + 7.3 x 1.2 + 123.814 x 1.2
628.56341 kNm /m

Inside Tank
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

MxSupport Rx: MxSupport


433.636 382.082 356.744
kNm / m kN / m kNm / m

Mxmidspan 628.563 kNm / m Mxmidspan


Factored Values
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

(C) Bearing Pressure Check

Base Slab

0.13 0.775 10 1.375 0.13 0.13

Longitudinal Section through Pit

Explanation of Forces of various element on base Slab

Add. Platf. Water Seismic Empty


Self Wt. Soil Wt. Surch. Wt. Seismic Wt.X
Wt. Wt. Wt.Y Wt.

1 2 3 4 5 6 7 8
V1 kN 219.844 10
My1 kNm/m -126.078 -17.371 -24.459 -77.245
Hx1 kN /m 189.486 22.450 36.760 74.533
V2 kN 219.844 10
My2 kNm/m 126.078 17.371 24.459 77.245
Hx2 kN/m -189.486 -22.450 -36.760 -74.533
V3 kN 712.294 10
Mx3 kNm/m 327.802 79.050 63.593 585.808
Hy3 kN/m 268.419 41.492 52.073 215.676
V4 kN 712.294 10
Mx4 kNm/m -327.802 -79.050 -63.593 -585.808
Hy4 kN/m -268.419 -41.492 -52.073 -215.676
V5 kN 39.375 170
M5x kNm 0
M5y kNm 0
H5x kN 0
H5y kN 0
V6 kN 39.375 170
M6x kNm 0
M6y kNm 0
H6x kN 0
H6y kN 0
V7 kN 0.000
V8 kN 0.000
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

V9 kN 0.000
V10 kN 0.000
V11 kN 434.000
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

Combination used for Bearing Pressure Check

(A) Equipment Operating without Seismic condition

A1 Self + Add Self + Soil Wt.+ x + x + Eq Oper.


A2 Self + Add Self + Soil Wt.+ Surchg + x + Eq Oper.
A3 Self + Add Self + Soil Wt.+ + Water Wt + Eq Oper.
A4 Self + Add Self + Soil Wt.+ Surchg + Water Wt. + Eq Oper.

(B) Equipment Operating with Seismic condition

B1 Self + Add Self + Soil Wt.+ x + Eq Oper.Seis X +Soil Seis. X


B2 Self + Add Self + Soil Wt.+ x + Eq Oper.Seis Y +Soil Seis. Y
B3 Self + Add Self + Soil Wt.+ Surchg + Eq Oper.Seis X + Soil Seis. X
B4 Self + Add Self + Soil Wt.+ Surchg + Eq Oper.Seis Y +Soil Seis. Y
B5 Self + Add Self + Soil Wt.+ + Water Wt + Eq Oper.Seis X + Soil Seis. X
B6 Self + Add Self + Soil Wt.+ + Water Wt + Eq Oper.Seis Y +Soil Seis. Y
B7 Self + Add Self + Soil Wt.+ Surchg + Water Wt. + Eq Oper.Seis X + Soil Seis. X
B8 Self + Add Self + Soil Wt.+ Surchg + Water Wt. + Eq Oper.Seis Y +Soil Seis. Y

(C) Equipment Empty without Seismic condition

C1 Self + Add Self + Soil Wt.+ x + x + Eq Empty


C2 Self + Add Self + Soil Wt.+ Surchg + x + Eq Empty.
C3 Self + Add Self + Soil Wt.+ x + Water Wt. + Eq Empty
C4 Self + Add Self + Soil Wt.+ Surchg + Water Wt. + Eq Empty

(D) Equipment Empty with Seismic condition

D1 Self + Add Self + Soil Wt.+ x + x + Eq Empty Seis X +Soil Seis.X


D2 Self + Add Self + Soil Wt.+ x + x + Eq Empty Seis Y +Soil Seis.Y
D3 Self + Add Self + Soil Wt.+ Surchg + x + Eq Empty Seis X +Soil Seis Y
D4 Self + Add Self + Soil Wt.+ Surchg + x + Eq Empty Seis Y +Soil Seis Y
D5 Self + Add Self + Soil Wt.+ x + Water Wt. + Eq Empty.Seis X +Soil Seis. X
D6 Self + Add Self + Soil Wt.+ x + Water Wt. + Eq Empty.Seis X +Soil Seis. X
D7 Self + Add Self + Soil Wt.+ Surchg + Water Wt. + Eq Empty.Seis X +Soil Seis. X
D8 Self + Add Self + Soil Wt.+ Surchg + Water Wt. + Eq Empty.Seis Y +Soil Seis. Y

Tabular statement for Bearing Pressure Check


Add. Platf. Water Empty
Self Wt. Soil Wt. Surch. Wt. Seis. Soil X Seis. Soil Y
Wt. Wt. Wt.
A1 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 0.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 0.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 0.00
A2 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 0.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 0.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 0.00
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

A3 1.00 1.00 1.00 1.00


V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 0.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 0.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 0.00
A4 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 0.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 0.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 0.00
B1 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 0.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 0.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 0.00
B2 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 0.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 0.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 0.00
B3 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 0.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 0.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 0.00
B4 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 0.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 0.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 0.00
B5 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 0.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 0.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 0.00
B6 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 0.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 0.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 0.00
B7 1.00 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 0.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 0.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 0.00
B8 1.00 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 0.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 0.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 0.00
C1 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 340.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 1105.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 -2006.00
C2 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 340.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 1105.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 -2006.00
C3 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 340.00
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 1105.00


My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 -2006.00
C4 1.00 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 340.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 1105.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 -2006.00
D1 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 340.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 1105.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 -2006.00
D2 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 340.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 1105.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 -2006.00
D3 1.00 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 340.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 1105.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 -2006.00
D4 1.00 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 340.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 1105.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 -2006.00
D5 1.00 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 340.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 1105.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 -2006.00
D6 1.00 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 340.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 1105.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 -2006.00
D7 1.00 1.00 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 340.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 1105.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 -2006.00
D8 1.00 1.00 1.00 1.00 1.00 1.00 1.00
V kN 2377.03 40.00 0.00 0.00 0.00 0.00 0.00 340.00
Mx kNm 4852.49 80.00 0.00 0.00 0.00 0.00 0.00 1105.00
My kNm -14713.93 -248.00 0.00 0.00 0.00 0.00 0.00 -2006.00
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

Final Bearing Pressure Calculation

V Mx My ex ey Mx My Pa ex'
Loa
d Effective
Co Total Total moment From X
Total Vertical Effective moment @ y V / base raft
mbi load at centre
Moment @ Moment @ y From X axis From y axis @ x axis
axis through Cg of raft area
axis
nati x axis axis through through Cg
Cg of raft
on
A1 3729.03 9196.49 -22702.73 2.466 6.088 -1738.44 417.23 75.18 0.12
A2 3729.03 9196.49 -22702.73 2.466 6.088 -4287.32 417.23 75.18 0.12
A3 3729.03 9196.49 -22702.73 2.466 6.088 10583.81 417.23 75.18 0.12
A4 3729.03 9196.49 -22702.73 2.466 6.088 0.00 417.23 75.18 0.12
B1 3827.53 9516.61 -22599.38 2.486 5.904 -1813.66 1131.28 77.17 0.12
B2 3821.53 9689.11 -23218.48 2.535 6.076 -4923.84 474.98 77.05 0.13
B3 3827.53 9516.61 -22599.38 2.486 5.904 11041.74 1131.28 77.17 0.12
B4 3821.53 9689.11 -23218.48 2.535 6.076 0.00 474.98 77.05 0.13
B5 3827.53 9516.61 -22599.38 2.486 5.904 -1813.66 1131.28 77.17 0.12
B6 3821.53 9689.11 -23218.48 2.535 6.076 -4923.84 474.98 77.05 0.13
B7 3827.53 9516.61 -22599.38 2.486 5.904 11041.74 1131.28 77.17 0.12
B8 3821.53 9689.11 -23218.48 2.535 6.076 0.00 474.98 77.05 0.13
C1 2757.03 6037.49 -16967.93 2.190 6.154 -707.98 125.63 55.59 0.05
C2 2757.03 6037.49 -16967.93 2.190 6.154 -1746.01 125.63 55.59 0.05
C3 2757.03 6037.49 -16967.93 2.190 6.154 4310.25 125.63 55.59 0.05
C4 2757.03 6037.49 -16967.93 2.190 6.154 0.00 125.63 55.59 0.05
D1 2783.03 6121.99 -16941.33 2.200 6.087 -764.59 313.42 56.11 0.05
D2 2783.03 6171.99 -17121.33 2.218 6.152 -2072.02 133.43 56.11 0.05
D3 2783.03 6121.99 -16941.33 2.200 6.087 4514.46 313.42 56.11 0.05
D4 2783.03 6171.99 -17121.33 2.218 6.152 0.00 133.43 56.11 0.05
D5 2783.03 6121.99 -16941.33 2.200 6.087 -763.39 313.42 56.11 0.05
D6 2783.03 6171.99 -17121.33 2.218 6.152 -2109.57 133.43 56.11 0.05
D7 2783.03 6121.99 -16941.33 2.200 6.087 4638.13 313.42 56.11 0.05
D8 2783.03 6171.99 -17121.33 2.218 6.152 0.00 133.43 56.11 0.05
Maximum Pressure in all c
Max pressure in non-Seism
Max pressure in Seismic c

Gross Allowable bearing pressure without increase factor.:


=50 kN/m2+ ( 6.5 m+ 0.25 m) x 18 kN/m3
Maximum Gross pressure .:
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

(D) Analysis of Base Slab for various critical conditions

Case A1 Assuming there is no equipment mounted on pedestal or its empty weight is negligible but transferri
through wall with full height water thus created critical upward bending for base slab and wall are loa
water Also checked above condition without water Since side wall moments reduces the sagging m

Weight of Wall = 2 x (3.5 + 0.25 + 11.9 + 0.25) x (6.5 + 0.2 ) x 0.25 x 35 kN/m3
Platform load .:
Total Vertical Load =

Plan Area of footing = ( 3.5 + 2 x (0.25+ 0 )) x ( 11.9 + 2 x (0.25+ 0 ))

Upward Bearing Pressure due to tank .: =1904.275 / 49.6


Full height water upward pressure ( 6.5m + 0.25 ) x 10kN/m3

1056.25250121 kNm/m

Short Side
Base Slab 3.75 m -109.08 kNm/m

Long Side
Tank

12.15 m
Soil

-95.33 kNm/m 245.15326 kNm/m

ly/ lx = 12.15 m / 3.75 m = 3.24

Analysis in short Direction

Support Bending Moment (-ve) along short direction


Long wall base moment for (soil + water + surcharge +Seismic)
327.802 + 63.593 + 79.05 +585.808 kNm/m
1056.253 kNm/m

Midspan Bending Moment (+ve) along short direction


midspan bending coefficient due to upward soil+water pressure.:
asx= 0.1238759

Ms.:asx *r *lx 2
=0.124 x 105.89 kN/m2 x 3.75m ^2
184.4655 kNm /m
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

Minimum Support moment in long wall due to soil and water alone
=327.802 + 63.593 kN/m2
391.3948 kNm /m

Net midspan bending Moment .:


184.465 - 0.75 x 391.395 ( Only 75% is considered t
-109.081 kNm /m

midspan bending coefficient due to upward soil pressure only .:


asx= 0.1238759

Ms.:asx *r *lx 2
=0.124 x 38.39 kN/m2 x 3.75m ^2
66.88016 kNm /m

Minimum Support moment in long wall due to soil only


327.8016 kNm /m

Net midspan bending Moment .:


66.88 - 0.75 x 327.802 ( Only 75% is considered t
-178.971 kNm /m Negative sign indicates sa

Critical Midspan Moment in short direction =MAX ( -109.081 , -178.971 )


-109.08 kNm /m
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

Analysis in long Direction

Support Bending Moment (-ve) along long direction


Short wall base moment for (soil + water + surcharge +Seismic)
126.078 + 24.459 + 17.371 +77.245 kNm/m
245.1533 kNm/m

Midspan Bending Moment (+ve) along long direction


midspan bending coefficient due to upward soil+water pressure.:
asy= 0.0118004

Ms.:asy *r *lx 2
=0.012 x 105.89 kN/m2 x 3.75m ^2
17.57216 kNm /m

Minimum Support moment in short wall due to soil and water alone
=126.078 + 24.459 kN/m2
150.5365 kN/m2

Net midspan bending Moment .:


17.572 - 0.75 x 150.536 ( Only 75% is considered t
-95.3302 kNm

Negative Sigh indicates effective Sagging will not occure

midspan bending coefficient due to upward soil pressure only .:


asy= 0.0118004

Ms.:asy *r *lx 2
=0.012 x 38.39 kN/m2 x 3.75m ^2
6.370996 kNm /m

Minimum Support moment in short wall due to soil and water alone
126.0776 kN/m2

Net midspan bending Moment .:


6.371 - 0.75 x 126.078 ( Only 75% is considered t
-88.1872 kNm

Negative Sigh indicates effective Sagging will not occure

Critical Midspan Moment in long direction =MAX (-95.33 , -88.187 )


-88.19 kNm

Case B a Seismic Operating Case with Soil,water,Surcharge pressure

Va
Ma
0.125 1.125
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

Pa

Va : Weight of wall in running meter = ( 6.5 + 0.2 ) x 0.25 x 35kN/m3


Ma .: Moment caused by Soil weight, =126.08 + 24.46 + 77.25
surcharge,water,Seismic
Pa.: Max Upward Soil Pressure = Gross pressure - unit wt of base slab + full upward w
= 158.194 - 0.25 mx 35 kN/m3 + ( 6.5 m +0.25m - 0 m

Vas : Weight of soil above projection = 0 m x 6.5 mx 18 kN/m3

Bm at Section .:
=216.944 kN/m2 x ( 1.125 m +0.125 m) ^2 / 2 + 245.153 kNm - 58.625 kN x 1.125 m -0 kN/mx ( 0.5 x 0

Shear at Section .: =216.944 kN/m2 x (1.125+0.125) m - 58.625 kNn - 0 kN


Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

Case B b Operating Case with Soil,water with I/3 m of height of tank or height of ground water table whicheve
Also side wall moment (due to soil alone) causes diminishing effect on sagging moment between th
is not considered

1.50 10 Pedestal

Pb

Pb.: Max upward Pressure = Gross Pressure - wt of base slab + min ( 1/3 rd water ht, water lev
= 158.194kN/m2 - 0.25 mx 35kN/m3+ min( ( 6.5 + 0.25 ) / 3 , (6.5 +
171.94408 kN/m2

Mb at Midspan .: 171.944 kN/m2x10 m^ 2 / 8 - 0.80 x171.944 kN/m2 x 1.5 m^ 2 / 2


1994.5513 kNm

Please add Sagging design section


Please add Sagging design section
( Please note that in case of unlikely scenario of shallow wall height in above case negative moment under pede

Case C Seismic Operating Case with Soil, water, Surcharge pressure on long wall

Vc
Mc
0.125 1.625 Pedestal

Pc

Vc : Weight of wall in running meter = ( 6.5 + 0.2 ) x 0.25 x 35kN/m3


Mc .: Moment caused by Soil weight, = 327.8 + 79.05 + 63.59 + 585.81
surcharge,water,Seismic
Pc.: Max Soil Pressure = Gross pressure - unit wt of base slab + full upward w
= 158.194 - 0.25 mx 35 kN/m3 + ( 6.5 m +0.25m - 0 m

Vcs : Weight of soil above projection = 0 m x 6.5 mx 18 kN/m3

Bm at Section .:
=216.944 kN/m2 x ( 1.625 m +0.125 m) ^2 / 2 + 1056.253 kNm - 58.625 kN x 1.625 m - 0 kN/mx ( 0.5 x

Shear at Section .: =216.944 kN/m2 x (1.625+0.125) m - 58.625 kN - 0 kN

(E) Check for buoyancy

Upward Trust of water due to buoyancy


= ( 3.5 + 2 x 0.25 ) x ( 11.9 + 2 x 0.25 ) x 6.75 m x 10 kN/m2
Client ETCHO
Project BURRIAL TAK FOUNDATION
Subject DESIGN OF BURIAL TANK FOUNDATION

Total downward weight


Neglecting platform as critical
Base Slab Weight = ( 3.5 + 0.25 x 2 +2 x 0) x ( 11.9 + 0.25 x 2 + 2 x 0 ) x 0.25 x 35
Weight of Wall = 2 x ( 3.5 + 0.25 + 11.9 + 0.25 ) x (6.5 + 0.2 ) x0.25 x 35
Weight of pedestal 2 x ( 3 x 0.5 x 0.75 ) x 35
Additional Soil around Base slab projection
Total Vertical Load =

Factor Of Safety against Buoyancy .: 2377.03 kN / 3348


Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

10.000 X axis

4.000 m

12.400 m

Foundation Plan

0.20

6.500 Sheet Limitation For full


height of water only

1.00

Ref. Soil Mech. & F Engg.


V.N.S.Murthy-Eq. 14.22
Design Basis

14 / 180 ) ) x 18 kN/mm3

Design Basis
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

e perpendicular walls .

d by the passive pressure on the

aken on the projected portion.

xcept earth press for which it shall be 1.2

above ground level

against self weight of concrete element only


Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

m
m

(apporx. a/b = 1)

N/m3 x(6.625-0)m x(1-0.741) =0.268 x 314.436kN/m2


kN/m2 re =84.2081 kN/m2
d) Due to Earthquake All Bending / Shear
pressure Coefficients from
"Moments & Reactions
for Rectang'r Plates
By W. T. Moody
Top edge free
Resr 3 edges fixed
=0.24 x 7.41 kN/m2 x 6.625m ^2 79.050 kNm /m

=0.08 x 88.39 kN/m2 x 6.625m ^2 327.802 kNm /m

=0.08 x 17.15 kN/m2 x 6.625m ^2 63.593 kNm /m

=0.16 x 84.21 kN/m2 x 6.625m ^2 585.808 kNm /m

585.808 x 1.2

Since wall is cantilever action


=0.85 x 7.41 kN/m2 x 6.625m 41.492 kN / m Shear = 1.0 for udl
& 0.5 for triang load
=0.46 x 88.39 kN/m2 x 6.625m 268.419 kN / m

=0.46 x 17.15 kN/m2 x 6.625m 52.073 kN / m


Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

=0.39 x 84.21 kN/m2 x 6.625m 215.676 kN / m

+ 215.676 x 1.2

=0.12 x 7.41 kN/m2 x 6.625m ^2 40.078 kNm /m

=0.04 x 88.39 kN/m2 x 6.625m ^2 172.241 kNm / m

=0.04 x 17.15 kN/m2 x 6.625m ^2 33.415 kNm / m

=0.08 x 84.21 kN/m2 x 6.625m ^2 291.241 kNm / m

+ 291.241 x 1.2

536.975 kNm /m

Soil

MySupport 1056.253 kNm /m


577.6601 kN /m
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

=0.26 x 7.41 kN/m2 x 6.625m ^2 85.003 kNm /m

=0.06 x 88.39 kN/m2 x 6.625m ^2 249.828 kNm / m

=0.06 x 17.15 kN/m2 x 6.625m ^2 48.466 kNm / m

=0.2 x 84.21 kN/m2 x 6.625m ^2 727.732 kNm / m

+ 727.732 x 1.2

=1.21 x 7.41 kN/m2 x 6.625m 59.489 kN / m

=0.2 x 88.39 kN/m2 x 6.625m 116.233 kN / m

=0.2 x 17.15 kN/m2 x 6.625m 22.549 kN / m

=1.01 x 84.21 kN/m2 x 6.625m 565.131 kN / m

+ 565.131 x 1.2

=0.1 x 7.41 kN/m2 x 6.625m ^2 32.791 kNm /m

=0.0276 x 88.39 kN/m2 x 6.625m ^2 107.069 kNm / m

=0.0276 x 17.15 kN/m2 x 6.625m ^2 20.771 kNm / m

=0.0732 x 84.21 kN/m2 x 6.625m ^2 270.543 kNm / m

+ 270.543 x 1.2

Inside Tank
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

Rx:
763.402
kN / m
Mxmidspan
431.175 kNm / m
UnFactored Values
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

m
m

m
m

(apporx. a/b = 0.5)

N/m3 x(6.625-0)m x(1-0.741) =0.268 x 314.436kN/m2


kN/m 2
re = 84.208 kN/m2
d) Due to Earthquake
pressure All Bending / Shear
Coefficients from
"Moments & Reactions
for Rectang'r Plates
By W. T. Moody
Top edge free
=0.05 x 7.41 kN/m2 x 6.625m ^2 17.371 kNm /m Resr 3 edges fixed

=0.03 x 88.39 kN/m2 x 6.625m ^2 126.078 kNm /m

=0.03 x 17.15 kN/m2 x 6.625m ^2 24.459 kNm /m

=0.02 x 84.21 kN/m2 x 6.625m ^2 77.245 kNm /m

+ 77.245 x 1.2

=0.46 x 7.41 kN/m2 x 6.625m 22.450 kN / m

=0.32 x 88.39 kN/m2 x 6.625m 189.486 kN / m


Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

=0.32 x 17.15 kN/m2 x 6.625m 36.760 kN / m

=0.13 x 84.21 kN/m2 x 6.625m 74.533 kN / m

74.533 x 1.2

=0.01 x 7.41 kN/m2 x 6.625m ^2 4.359 kNm /m

=0.01 x 88.39 kN/m2 x 6.625m ^2 33.750 kNm / m

=0.01 x 17.15 kN/m2 x 6.625m ^2 6.547 kNm / m

=0 x 84.21 kN/m2 x 6.625m ^2 17.371 kNm / m

62.028 kNm /m

Soil

MySupport 245.153 kNm /m


323.229 kN /m
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

=0.09 x 7.41 kN/m2 x 6.625m ^2 27.716 kNm /m

=0.02 x 88.39 kN/m2 x 6.625m ^2 58.578 kNm / m

=0.02 x 17.15 kN/m2 x 6.625m ^2 11.364 kNm / m

=0.07 x 84.21 kN/m2 x 6.625m ^2 259.086 kNm / m

259.086 x 1.2

=0.51 x 7.41 kN/m2 x 6.625m 25.048 kN / m

=0.03 x 88.39 kN/m2 x 6.625m 19.089 kN / m

=0.03 x 17.15 kN/m2 x 6.625m 3.703 kN / m

=0.48 x 84.21 kN/m2 x 6.625m 266.387 kN / m

266.387 x 1.2

=0.04 x 7.41 kN/m2 x 6.625m ^2 14.053 kNm /m

=0.097 x 88.39 kN/m2 x 6.625m ^2 376.293 kNm / m

=0.0097 x 17.15 kN/m2 x 6.625m ^2 7.300 kNm / m

=0.0335 x 84.21 kN/m2 x 6.625m ^2 123.814 kNm / m

23.814 x 1.2

Inside Tank
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

Rx:
314.227
kN / m

521.461 kNm / m
UnFactored Values
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

Base Slab

0.625 3.125
0.13 0.13
-0.875 3
Transverse Section through Pit

Empty / Oper / Empty / Oper /


Empty
Oper Wt Test Wt. Seis-X Seis-X Seis-Y Seis-Y Remark
Wt.
Wt. Wt Wt. Wt
8 9 10 11 12 13 14
Short
wall near
axis
Short
wall far
axis
Long
wall near
axis
Long
wall far
axis
170 656 678.5 26 98.5 13 49.25
0 0 0 25 96
Fixed
0 0 0 50 192 Saddle
0 0 0 0 0 0 0
0 0 0 0 0 0 0
170 656 678.5 0 0 13 43.25
0 0 0 25 96
Sliding
0 0 0 0 0
Saddle
0 0 0 0 0 0 0
0 0 0 0 0 0 0
Soil on V1
Soil on V2
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

Soil on V3
Soil on V4
Base Slab
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

Empty / Oper / Empty / Oper /


Empty Sum of
Oper Wt Test Wt. Seis-X Seis-X Seis-Y Seis-Y
Wt. Forces
Wt. Wt Wt. Wt
1.00
0.00 1312.00 0.00 0.00 0.00 0.00 0.00 3729.03
0.00 4264.00 0.00 0.00 0.00 0.00 0.00 9196.49
0.00 -7740.80 0.00 0.00 0.00 0.00 0.00 -22702.73
1.00
0.00 1312.00 0.00 0.00 0.00 0.00 0.00 3729.03
0.00 4264.00 0.00 0.00 0.00 0.00 0.00 9196.49
0.00 -7740.80 0.00 0.00 0.00 0.00 0.00 -22702.73
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

1.00
0.00 1312.00 0.00 0.00 0.00 0.00 0.00 3729.03
0.00 4264.00 0.00 0.00 0.00 0.00 0.00 9196.49
0.00 -7740.80 0.00 0.00 0.00 0.00 0.00 -22702.73
1.00
0.00 1312.00 0.00 0.00 0.00 0.00 0.00 3729.03
0.00 4264.00 0.00 0.00 0.00 0.00 0.00 9196.49
0.00 -7740.80 0.00 0.00 0.00 0.00 0.00 -22702.73
1.00 1.00
0.00 1312.00 0.00 0.00 98.50 0.00 0.00 3827.53
0.00 4264.00 0.00 0.00 320.13 0.00 0.00 9516.61
0.00 -7740.80 0.00 0.00 103.35 0.00 0.00 -22599.38
1.00 1.00
0.00 1312.00 0.00 0.00 0.00 0.00 92.50 3821.53
0.00 4264.00 0.00 0.00 0.00 0.00 492.63 9689.11
0.00 -7740.80 0.00 0.00 0.00 0.00 -515.75 -23218.48
1.00 1.00
0.00 1312.00 0.00 0.00 98.50 0.00 0.00 3827.53
0.00 4264.00 0.00 0.00 320.13 0.00 0.00 9516.61
0.00 -7740.80 0.00 0.00 103.35 0.00 0.00 -22599.38
1.00 1.00
0.00 1312.00 0.00 0.00 0.00 0.00 92.50 3821.53
0.00 4264.00 0.00 0.00 0.00 0.00 492.63 9689.11
0.00 -7740.80 0.00 0.00 0.00 0.00 -515.75 -23218.48
1.00 1.00
0.00 1312.00 0.00 0.00 98.50 0.00 0.00 3827.53
0.00 4264.00 0.00 0.00 320.13 0.00 0.00 9516.61
0.00 -7740.80 0.00 0.00 103.35 0.00 0.00 -22599.38
1.00 1.00
0.00 1312.00 0.00 0.00 0.00 0.00 92.50 3821.53
0.00 4264.00 0.00 0.00 0.00 0.00 492.63 9689.11
0.00 -7740.80 0.00 0.00 0.00 0.00 -515.75 -23218.48
1.00 1.00
0.00 1312.00 0.00 0.00 98.50 0.00 0.00 3827.53
0.00 4264.00 0.00 0.00 320.13 0.00 0.00 9516.61
0.00 -7740.80 0.00 0.00 103.35 0.00 0.00 -22599.38
1.00 1.00
0.00 1312.00 0.00 0.00 0.00 0.00 92.50 3821.53
0.00 4264.00 0.00 0.00 0.00 0.00 492.63 9689.11
0.00 -7740.80 0.00 0.00 0.00 0.00 -515.75 -23218.48
1.00
340.00 0.00 0.00 0.00 0.00 0.00 0.00 2757.03
1105.00 0.00 0.00 0.00 0.00 0.00 0.00 6037.49
-2006.00 0.00 0.00 0.00 0.00 0.00 0.00 -16967.93
1.00
340.00 0.00 0.00 0.00 0.00 0.00 0.00 2757.03
1105.00 0.00 0.00 0.00 0.00 0.00 0.00 6037.49
-2006.00 0.00 0.00 0.00 0.00 0.00 0.00 -16967.93
1.00
340.00 0.00 0.00 0.00 0.00 0.00 0.00 2757.03
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

1105.00 0.00 0.00 0.00 0.00 0.00 0.00 6037.49


-2006.00 0.00 0.00 0.00 0.00 0.00 0.00 -16967.93
1.00
340.00 0.00 0.00 0.00 0.00 0.00 0.00 2757.03
1105.00 0.00 0.00 0.00 0.00 0.00 0.00 6037.49
-2006.00 0.00 0.00 0.00 0.00 0.00 0.00 -16967.93
1.00 1.00
340.00 0.00 0.00 26.00 0.00 0.00 0.00 2783.03
1105.00 0.00 0.00 84.50 0.00 0.00 0.00 6121.99
-2006.00 0.00 0.00 26.60 0.00 0.00 0.00 -16941.33
1.00 1.00
340.00 0.00 0.00 0.00 0.00 26.00 0.00 2783.03
1105.00 0.00 0.00 0.00 0.00 134.50 0.00 6171.99
-2006.00 0.00 0.00 0.00 0.00 -153.40 0.00 -17121.33
1.00 1.00
340.00 0.00 0.00 26.00 0.00 0.00 0.00 2783.03
1105.00 0.00 0.00 84.50 0.00 0.00 0.00 6121.99
-2006.00 0.00 0.00 26.60 0.00 0.00 0.00 -16941.33
1.00 1.00
340.00 0.00 0.00 0.00 0.00 26.00 0.00 2783.03
1105.00 0.00 0.00 0.00 0.00 134.50 0.00 6171.99
-2006.00 0.00 0.00 0.00 0.00 -153.40 0.00 -17121.33
1.00 1.00
340.00 0.00 0.00 26.00 0.00 0.00 0.00 2783.03
1105.00 0.00 0.00 84.50 0.00 0.00 0.00 6121.99
-2006.00 0.00 0.00 26.60 0.00 0.00 0.00 -16941.33
1.00 1.00
340.00 0.00 0.00 0.00 0.00 26.00 0.00 2783.03
1105.00 0.00 0.00 0.00 0.00 134.50 0.00 6171.99
-2006.00 0.00 0.00 0.00 0.00 -153.40 0.00 -17121.33
1.00 1.00
340.00 0.00 0.00 26.00 0.00 0.00 0.00 2783.03
1105.00 0.00 0.00 84.50 0.00 0.00 0.00 6121.99
-2006.00 0.00 0.00 26.60 0.00 0.00 0.00 -16941.33
1.00 1.00
340.00 0.00 0.00 0.00 0.00 26.00 0.00 2783.03
1105.00 0.00 0.00 0.00 0.00 134.50 0.00 6171.99
-2006.00 0.00 0.00 0.00 0.00 -153.40 0.00 -17121.33
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

ex' ey' K
Bearing
Stress Gross
From X
From y axis increased pressure
axis = K . Pa
through Cg factor
through Cg
based on
ex' & ey'

0.12 0.02 1.75 131.57


0.12 0.02 1.75 131.57
0.12 0.02 1.75 131.57
0.12 0.02 1.75 131.57
0.12 0.05 2.05 158.19
0.13 0.02 1.98 152.55
0.12 0.05 2.05 158.19
0.13 0.02 1.98 152.55
0.12 0.05 2.05 158.19
0.13 0.02 1.98 152.55
0.12 0.05 2.05 158.19
0.13 0.02 1.98 152.55
0.05 0.01 1.30 72.26
0.05 0.01 1.30 72.26
0.05 0.01 1.30 72.26
0.05 0.01 1.30 72.26
0.05 0.02 1.40 78.55
0.05 0.01 1.38 77.43
0.05 0.02 1.40 78.55
0.05 0.01 1.38 77.43
0.05 0.02 1.40 78.55
0.05 0.01 1.38 77.43
0.05 0.02 1.40 78.55
0.05 0.01 1.38 77.43
mum Pressure in all case 158.19 kN/m2
pressure in non-Seismic case 131.57 kN/m2
pressure in Seismic case 158.19 kN/m2

171.50 kN/m2
158.19 kN/m2 Safe
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

egligible but transferring platform weight


e slab and wall are loaded with soil and
educes the sagging moment in base slab

= 1864.275 kN
= 40.00 kN
1904.28 kN

49.6 m2

38.39264 kN/m2
67.5 kN/m2
105.8926 kN/m2

ge +Seismic)

Refer BS8110-1-3.5.3.3
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

y 75% is considered to give critical effect)

Refer BS8110-1-3.5.3.3

y 75% is considered to give critical effect)


ative sign indicates sagging will not occure
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

ge +Seismic)

Refer BS8110-1-3.5.3.3

y 75% is considered to give critical effect)

Refer BS8110-1-3.5.3.3

y 75% is considered to give critical effect)

(not to be considered simultaneously)


Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

58.625 kN/m
245.153 kNm / m

e slab + full upward water pressure


( 6.5 m +0.25m - 0 m ) x 10 kN/m3
216.944 kN/m2
0 kN/m

m -0 kN/mx ( 0.5 x 0 m+ 0.5 x 0.25m +1.125 m )


348.688 kNm /m
212.555 kN/m
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

water table whichever is minimum


g moment between the pedestal is

3 rd water ht, water level)


6.5 + 0.25 ) / 3 , (6.5 + 0.25 - 0 )) m x 10kN/m2

kN/m2 x 1.5 m^ 2 / 2 80% cantilever is


considered

e moment under pedestal would govern)

58.625 kN/m
1056.25 kNm / m

e slab + full upward water pressure


( 6.5 m +0.25m - 0 m ) x 10 kN/m3
216.944 kN/m2
0 kN/m

5 m - 0 kN/mx ( 0.5 x 0 m+ 0.5 x 0.25m +1.625 m )


1293.18 kNm /m
321.027 kN/m

= 3348 kN
Job No.: ETCHO 01/2019 Page.: of :
Prep. By.: GSC Date : 30/10/2019
Ck'd. by.: GSC Date :

= 434 kN
= 1864.28 kN
= 78.75 kN
= 0 kN
Vertical Load = 2377 kN

0.70998 < 1.2 Unsafe


Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

DESIGN OF LONG WALL - BS (Cracked)


Design Basis
Design Parameter
f'c 25 N/mm 2

fs 420 N/mm2 0.2 mm for severe or very


Permisible crack width 0.3 mm severe explosure
Ec ( For cracked ) = 5.5 x (fcu / g f)^ 0.5 0.1 mm criticla asthetic
= 5.5 x ( 25 / 1.5 )^ 0.5 appearance
22.45366 kN/mm2 BS8007-1987, 2.2.3.3 a
m , Modular ratio 200 / 22.45
8.907235
Summary of Forces on long wall

No. Location Factored Values UnFactored Values


a) Vertical bending moment at base 1283.313 kNm / m 1056.253 kNm / m
b) Vertical bending moment at midhight 652.385 kNm / m 536.975 kNm / m
c) Shear Force at base 701.491 kN / m 577.660 kN / m
d) Horizontal bending moment at support 1350.235 kNm / m 1111.029 kNm / m
e) Horizontal bending moment at midspan 523.968 kNm / m 431.175 kNm / m
f) Shear Force at sides 927.980 kN / m 763.402 kN / m
g) Axial compression due to short wall horizontal shear 382.082 kN / m kN / m

Considered the overall thickness of wall is 250 mm

Clear Cover 50 mm

Bar Dia Assume 32 mm

Effective depth d = 250mm -50mm -32mm = 184 mm Calculated at 2nd layer

a ) Designing for Vertical bending moment at base 1283.313 kN m Factored Moment


1056.253 kN m UnFactored Moment
Considering axial compression of wall due to self weight and platform weight is < 0.1 Fcu bd and hence designing
Vertical element as slab not as a wall
Also neglecting reduction in tension steel due to effect of compressive load mentioned above

K = Md / Fcu b d 2 BS8110-Part 1 1997


= 1283.313 x 10^6 / ( 25 x 1000 x 184^ 2 ) 3.4.4.4
1.5162016 N/mm2 > 0.156 N/mm2 Doubly reinforced beam

z = min [( 0.5 + ( 0.25 - k / 0.9 )^ 0.5, 0.95 ] x d


#NUM! mm

x = ( d - z ) / 0.45
= ###
#NUM! mm

As = Md / ( 0.87 fy z )
###
#NUM! mm2
Reference S.S. Ray
Recommended Spacing of Reinforcement in tension 100 As
Clear Spac
/bd(%)
% of Steel = ### 1 or Over 160
#NUM! 0.75 210
Minimum Spacing recommended 125 mm ( refer table right side) 0.5 320
0.3 530
< 0.3 min (3d,750)
Minimum reinforcement Suspended Slab or Wall to distribute early thermal cracking Refer BS 8007 - 1987
(a) Overall depth of slab/ wall < 500 ,ast= 0.00175bD for grade 460 or 0.0032bD for grade 250 on each face Appendix A Table A.1 & Fig A.1
(b) Overall depth of slab/ wall > 500 ,ast= 0.0035b(250mm) for grade 460 or 0.0064b(250mm) for grade 250 on each face

Min Steel required 0.3500 % on each face

0.35 x 1000 mmx 250 mm / 100 = 875 mm2

Provide max vertical steel area ### = #NUM! mm2

Required 32 mm @ ### c/c

Provide 32 mm @ 100 c/c = 8042 mm2 ###

Corresponding r =( 3.14 x 32^ 2 / 4 x1000 /100 ) / ( 1000 x 184 ) = 0.043709115


Client ETCHO Job No.: ETCHO 01/2019 Page.: of : D
e
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
s
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date : i
g
n
Assessment of crack in Flexure
c
Neutral axis calculation base on percentage of tensile steel provided r
a
x = [((mp)2 +2 mp)0.5 -mp ] d ( Neglecting effect of compression steel if any) c
((( 8.91 x 0.0437 ) ^ 2 + 2 x 8.91 x 0.0437 ) ^ 0.5 - 8.91x 0.0437 ) x 184 mm k
105.82893 mm
w
z= d- x /3 i
P
=184mm - 105.83mm / 3 ld
148.72369 mm t
a
ih
n
fs = Service Stress in tensile steel
M/ As z (b
m
a
=1056.253 kN m x 10^6 / ( 8042.48 mm2 x 148.72 mm ) rm
883.07535 N/mm2 s)
###
es= Strain at tensile steel level ###
=883.075 N/mm2 / 200000 N/mm2
0.00442 -

e1= Strain in extreme concrete end ( at location h from comp side)


es * (h-x) / (d-x)
=0.00442 x ( ( 250 mm - 105.83 mm) / ( 184 mm- 105.83 mm) )
0.0081433 -

e2= Strain correction due to stiffening effect


b ( h - x )2 / 3 Es As ( d - x )
= ( ( 1000 mm x ( 250 mm - 105.83 mm) ^ 2 / ( 3 x 200000 kN/mm2 x 8042.48 mm2 x ( 184 mm - 105.83 mm) ) ) )
5.51E-05 -

em= Average strain in flexure


e1-e2
=0.00814 - 0.00006
0.00809 - > 0.00168 - UnSafe-strain is greater than 0.8 fy /Es

Cmin= 50mm +32mm + 0.5 x32mm


98.000 mm

acr= ( ( 98 mm) ^ 2 + ( 0.5 x 100 mm) ^ 2 ) ^ 0.5


110.01818 mm

Wcr= Final crack width


3 acr em / [ 1+ (2 (acr -Cmin) / (h - x ))]
= ( 3 x 110.018 mmx 0.0001 / ( ( 1 + ( 2 x ( 110.018 mm - 98 mm) / ( 250 mm - 105.829 mm )))))
2.2880727 mm > 0.3 mm UnSafe - Actual crack width > Permisible crack width
Provide min % steel on inside face of wall - ### mm2/mt ie .12 dia at 100c/c
b ) Designing for Vertical bending moment at midheight (Not Exposed to Water) 652.385 kN m Factored Moment
536.975 kN m UnFactored Moment
Considering axial compression of wall due to self weight and platform weight is < 0.1 Fcu bd and hence designing
Vertical element as slab not as a wall
Also neglecting reduction in tension steel due to effect of compressive load mentioned above

K = Md / Fcu b d 2 BS8110-Part 1 1997


= 652.385 x 10^6 / ( 25 x 1000 x 184^ 2 ) 3.4.4.4
0.7707765 N/mm2 > 0.156 N/mm2 Doubly reinforced beam

z = min [( 0.5 + ( 0.25 - k / 0.9 )^ 0.5, 0.95 ] x d


#NUM! mm

x = ( d - z ) / 0.45
= ###
#NUM! mm

As = Md / ( 0.87 fy z ) Reference S.S. Ray


### 100 As
Clear Spac
#NUM! mm2 /bd(%)
1 or Over 160
Recommended Spacing of Reinforcement in tension 0.75 210
0.5 320
% of Steel = ### 0.3 530
#NUM! < 0.3 min (3d,750)
Minimum Spacing recommended 160 mm ( refer table right side)

Minimum reinforcement Suspended Slab or Wall to distribute early thermal cracking Refer BS 8007 - 1987
(a) Overall depth of slab/ wall < 500 ,ast= 0.00175bD for grade 460 or 0.0032bD for grade 250 on each face Appendix A Table A.1 & Fig A.1
(b) Overall depth of slab/ wall > 500 ,ast= 0.0035b(250mm) for grade 460 or 0.0064b(250mm) for grade 250 on each face

Min Steel required 0.3500 % on each face

0.35 x 1000 mmx 250 mm / 100 = 875 mm2

Provide max vertical steel area ### = #NUM! mm2

Required 32 mm @ ### c/c

Provide 32 mm @ 200 c/c = 4021 mm2 ###


Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

Corresponding r =( 3.14 x 32^ 2 / 4 x1000 /200 ) / ( 1000 x 184 ) = 0.021854558


Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

Assessment of crack in Flexure

Neutral axis calculation base on percentage of tensile steel provided


x = [((mp)2 +2 mp)0.5 -mp ] d ( Neglecting effect of compression steel if any)
((( 8.91 x 0.0219 ) ^ 2 + 2 x 8.91 x 0.0219 ) ^ 0.5 - 8.91x 0.0219 ) x 184 mm
84.448275 mm

z= d- x /3
=184mm - 84.45mm / 3
155.85058 mm

fs = Service Stress in tensile steel


M/ As z
=536.975 kN m x 10^6 / ( 4021.24 mm2 x 155.85 mm )
856.81201 N/mm2
###
es= Strain at tensile steel level ###
=856.812 N/mm2 / 200000 N/mm2
0.00428 -

e1= Strain in extreme concrete end ( at location h from comp side)


es * (h-x) / (d-x)
=0.00428 x ( ( 250 mm - 84.45 mm) / ( 184 mm- 84.45 mm) )
0.0071243 -

e2= Strain correction due to stiffening effect


b ( h - x )2 / 3 Es As ( d - x )
= ( ( 1000 mm x ( 250 mm - 84.45 mm) ^ 2 / ( 3 x 200000 kN/mm2 x 4021.24 mm2 x ( 184 mm - 84.45 mm) ) ) )
0.0001141 -

em= Average strain in flexure


e1-e2
=0.00712 - 0.00011
0.00701 - > 0.00168 - UnSafe-strain is greater than 0.8 fy /Es

Cmin= 50mm +32mm + 0.5 x32mm


98.000 mm

acr= ( ( 98 mm) ^ 2 + ( 0.5 x 200 mm) ^ 2 ) ^ 0.5


140.01428 mm

Wcr= Final crack width


3 acr em / [ 1+ (2 (acr -Cmin) / (h - x ))]
= ( 3 x 140.014 mmx 0.0001 / ( ( 1 + ( 2 x ( 140.014 mm - 98 mm) / ( 250 mm - 84.448 mm )))))
1.9531937 mm > 0.3 mm UnSafe - Actual crack width > Permisible crack width

c ) Designing for Vertical wall for horizontal base shear 701.491 kN Factored Shear
577.660 kN UnFactored Shear
Percentage of tensile steel provided 4.3709115 %

vc= 0.79 [ (min (pt , 3 )) 0.333 x (max (400/d) , 1 )0.25 x (min( 40 ,fcu)/25) 0.333 ] / ym
=0.79 x MIN ( 4.371 , 3 ) ^ (1/3) x MAX ( 400 / 184 ) ^ 0.25 x ( MIN (40, 25 ) / 25 ) ^(1/3) /1.25
1.1067972 N/mm2
Since Vc < 0.8*SqrtFcu & 5N/mm2, enhanced shear = =(2*deff*Vc)/((TAN30*3.14/180)*deff) =' 3.8364 N/mm2
vc x b x d
3.84 x 1000 x 184
Vc= 705899.303637 N
705.8993 kN > 701.491 kN Safe

d ) Designing for Horizontal bending moment at side support 1350.235 kN m Factored Moment
1111.029 kN m UnFactored Moment
Considering axial compression of wall due to self weight and platform weight is < 0.1 Fcu bd and hence designing
Vertical element as slab not as a wall
Also neglecting reduction in tension steel due to effect of compressive load mentioned above

K = Md / Fcu b d 2 BS8110-Part 1 1997


= 1350.235 x 10^6 / ( 25 x 1000 x 184^ 2 ) 3.4.4.4
1.5952687 N/mm2 > 0.156 N/mm2 Doubly reinforced beam

z = min [( 0.5 + ( 0.25 - k / 0.9 )^ 0.5, 0.95 ] x d


#NUM! mm

x = ( d - z ) / 0.45
= ###
#NUM! mm

As = Md / ( 0.87 fy z )
###
#NUM! mm2
Reference S.S. Ray
Recommended Spacing of Reinforcement in tension 100 As
Clear Spac
/bd(%)
% of Steel = ### 1 or Over 160
#NUM! 0.75 210
Minimum Spacing recommended 160 mm ( refer table right side) 0.5 320
0.3 530
Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

< 0.3 min (3d,750)


Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

Minimum reinforcement Suspended Slab or Wall to distribute early thermal cracking Refer BS 8007 - 1987
(a) Overall depth of slab/ wall < 500 ,ast= 0.00175bD for grade 460 or 0.0032bD for grade 250 on each face Appendix A Table A.1 & Fig A.1
(b) Overall depth of slab/ wall > 500 ,ast= 0.0035b(250mm) for grade 460 or 0.0064b(250mm) for grade 250 on each face

Min Steel required 0.3500 % on each face

0.35 x 1000 mmx 250 mm / 100 = 875 mm2

Provide max vertical steel area ### = #NUM! mm2

Required 32 mm @ ### c/c

Provide 32 mm @ 100 c/c = 8042 mm2 ###

Corresponding r =( 3.14 x 32^ 2 / 4 x1000 /100 ) / ( 1000 x 184 ) = 0.043709115

Assessment of crack in Flexure

Neutral axis calculation base on percentage of tensile steel provided


x = [((mp)2 +2 mp)0.5 -mp ] d ( Neglecting effect of compression steel if any)
((( 8.91 x 0.0437 ) ^ 2 + 2 x 8.91 x 0.0437 ) ^ 0.5 - 8.91x 0.0437 ) x 184 mm
105.82893 mm

z= d- x /3
=184mm - 105.83mm / 3
148.72369 mm

fs = Service Stress in tensile steel


M/ As z
=1111.029 kN m x 10^6 / ( 8042.48 mm2 x 148.72 mm )
928.87101 N/mm2
###
es= Strain at tensile steel level ###
=928.871 N/mm2 / 200000 N/mm2
0.00464 -

e1= Strain in extreme concrete end ( at location h from comp side)


es * (h-x) / (d-x)
=0.00464 x ( ( 250 mm - 105.83 mm) / ( 184 mm- 105.83 mm) )
0.0085656 -

e2= Strain correction due to stiffening effect


b ( h - x )2 / 3 Es As ( d - x )
= ( ( 1000 mm x ( 250 mm - 105.83 mm) ^ 2 / ( 3 x 200000 kN/mm2 x 8042.48 mm2 x ( 184 mm - 105.83 mm) ) ) )
5.51E-05 -

em= Average strain in flexure


e1-e2

=0.00857 - 0.00006
0.00851 - > 0.00168 - UnSafe-strain is greater than 0.8 fy /Es

Cmin= 50mm +32mm + 0.5 x32mm


98.000 mm

acr= ( ( 98 mm) ^ 2 + ( 0.5 x 100 mm) ^ 2 ) ^ 0.5


110.01818 mm

Wcr= Final crack width


3 acr em / [ 1+ (2 (acr -Cmin) / (h - x ))]
= ( 3 x 110.018 mmx 0.0001 / ( ( 1 + ( 2 x ( 110.018 mm - 98 mm) / ( 250 mm - 105.829 mm )))))
2.408 mm > 0.3 mm UnSafe - Actual crack width > Permisible crack width

e ) Designing for Horizontal bending moment at midspan 523.968 kN m Factored Moment


431.175 kN m UnFactored Moment
Considering axial compression of wall due to self weight and platform weight is < 0.1 Fcu bd and hence designing
Vertical element as slab not as a wall
Also neglecting reduction in tension steel due to effect of compressive load mentioned above

K = Md / Fcu b d 2 BS8110-Part 1 1997


= 523.968 x 10^6 / ( 25 x 1000 x 184^ 2 ) 3.4.4.4
0.6190546 N/mm2 > 0.156 N/mm2 Doubly reinforced beam

z = min [( 0.5 + ( 0.25 - k / 0.9 )^ 0.5, 0.95 ] x d


#NUM! mm

x = ( d - z ) / 0.45
= ###
#NUM! mm

As = Md / ( 0.87 fy z )
###
#NUM! mm2
Reference S.S. Ray
Recommended Spacing of Reinforcement in tension 100 As
Clear Spac
/bd(%)
% of Steel = ### 1 or Over 160
#NUM! 0.75 210
Minimum Spacing recommended 160 mm ( refer table right side) 0.5 320
Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

0.3 530
< 0.3 min (3d,750)
Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

Minimum reinforcement Suspended Slab or Wall to distribute early thermal cracking Refer BS 8007 - 1987
(a) Overall depth of slab/ wall < 500 ,ast= 0.00175bD for grade 460 or 0.0032bD for grade 250 on each face Appendix A Table A.1 & Fig A.1
(b) Overall depth of slab/ wall > 500 ,ast= 0.0035b(250mm) for grade 460 or 0.0064b(250mm) for grade 250 on each face

Min Steel required 0.3500 % on each face

0.35 x 1000 mmx 250 mm / 100 = 875 mm2

Provide max vertical steel area ### = #NUM! mm2

Required 20 mm @ ### c/c

Provide 20 mm @ 200 c/c = 1571 mm2 ###

Corresponding r =( 3.14 x 20^ 2 / 4 x1000 /200 ) / ( 1000 x 184 ) = 0.008536937

Assessment of crack in Flexure

Neutral axis calculation base on percentage of tensile steel provided


x = [((mp)2 +2 mp)0.5 -mp ] d ( Neglecting effect of compression steel if any)
((( 8.91 x 0.0085 ) ^ 2 + 2 x 8.91 x 0.0085 ) ^ 0.5 - 8.91x 0.0085 ) x 184 mm
59.115423 mm

z= d- x /3
=184mm - 59.12mm / 3
164.29486 mm

fs = Service Stress in tensile steel


M/ As z
=431.175 kN m x 10^6 / ( 1570.8 mm2 x 164.29 mm )
1670.742 N/mm2
###
es= Strain at tensile steel level ###
=1670.742 N/mm2 / 200000 N/mm2
0.00835 -

e1= Strain in extreme concrete end ( at location h from comp side)


es * (h-x) / (d-x)
=0.00835 x ( ( 250 mm - 59.12 mm) / ( 184 mm- 59.12 mm) )
0.0127685 -

e2= Strain correction due to stiffening effect


b ( h - x )2 / 3 Es As ( d - x )
= ( ( 1000 mm x ( 250 mm - 59.12 mm) ^ 2 / ( 3 x 200000 kN/mm2 x 1570.8 mm2 x ( 184 mm - 59.12 mm) ) ) )
0.0003096 -

em= Average strain in flexure


e1-e2
=0.01277 - 0.00031
0.01246 - > 0.00168 - UnSafe - Actual crack width > Permisible crack width

Cmin= 50mm +20mm + 0.5 x20mm


80.000 mm

acr= ( ( 80 mm) ^ 2 + ( 0.5 x 200 mm) ^ 2 ) ^ 0.5


128.06248 mm

Wcr= Final crack width


3 acr em / [ 1+ (2 (acr -Cmin) / (h - x ))]
= ( 3 x 128.062 mmx 0.0003 / ( ( 1 + ( 2 x ( 128.062 mm - 80 mm) / ( 250 mm - 59.115 mm )))))
3.1834639 mm > 0.3 mm UnSafe - Actual crack width > Permisible crack width

f) Designing wall for horizontal base shear 43.357 kN Factored Shear


29.288 kN UnFactored Shear
Percentage of tensile steel provided 4.3709115 %

vc= 0.79 [ (min (pt , 3 )) 0.333 x (max (400/d) , 1 )0.25 x (min( 40 ,fcu)/25) 0.333 ] / ym
=0.79 x MIN ( 4.371 , 3 ) ^ (1/3) x MAX ( 400 / 184 ) ^ 0.25 x ( MIN (40, 25 ) / 25 ) ^(1/3) /1.25
1.1067972 N/mm2
Vc= vc x b x d
1.107 x 1000 x 184
203650.678619 N
203.65068 kN > 43.357 kN Safe
Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :
Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

DESIGN OF SHORT WALL - BS (Cracked)


Design Basis
Design Parameter
f'c 25 N/mm2
fs 420 N/mm2 0.2 mm for severe or very
Permisible crack width 0.3 mm severe explosure
Ec ( For Uncracked ) =0.5 x 5.5 x (fcu / g f)^ 0.5 0.1 mm criticla asthetic
= 0.5 x 5.5 x ( 25 / 1.5 )^ 0.5 appearance
11.226827988 kN/mm2 BS8007-1987, 2.2.3.3 a
m , Modular ratio 200 / 11.23
17.814470857
Summary of Forces on short wall

No. Location Factored Values UnFactored Values


a) Vertical bending moment at base support 298 kNm / m 245.153 kNm / m
b) Vertical bending moment at midhight 75.305 kNm / m 62.028 kNm / m
c) Shear Force at base 392.364 kN / m 323.229 kN / m
d) Horizontal bending moment at support 433.636 kNm / m 356.744 kNm / m
e) Horizontal bending moment at midspan 628.563 kNm / m 521.461 kNm / m
f) Shear Force at sides 382.082 kN / m 314.227 kN / m
g) Axial compression due to long wall horizontal shear 927.980 kN / m kN / m

Considered the overall thickness of wall is 250 mm

Clear Cover 60 mm
0
Bar Dia Assume 16 mm

Effective depth d = 250mm -60mm - 0.5 x16mm = 182 mm Calculated at 2nd layer

a ) Designing for Vertical bending moment at base 297.658 kN m Factored Moment


245.153 kN m UnFactored Moment
Considering axial compression of wall due to self weight and platform weight is < 0.1 Fcu bd and hence designing
Vertical element as slab not as a wall
Also neglecting reduction in tension steel due to effect of compressive load mentioned above

K = Md / Fcu b d 2 BS8110-Part 1 1997


= 297.658 x 10^6 / ( 25 x 1000 x 182^ 2 ) 3.4.4.4
0.35945 N/mm2 > 0.156 N/mm 2
Doubly reinforced beam

z = min [( 0.5 + ( 0.25 - k / 0.9 )^ 0.5, 0.95 ] x d


#NUM! mm

x = ( d - z ) / 0.45
= ###
#NUM! mm

As = Md / ( 0.87 fy z )
###
#NUM! mm2
Reference S.S. Ray
Recommended Spacing of Reinforcement in tension 100 As
Clear Spac
/bd(%)
% of Steel = ### 1 or Over 160
#NUM! 0.75 210
Minimum Spacing recommended 160 mm ( refer table right side) 0.5 320
0.3 530
< 0.3 min (3d,750)
Minimum reinforcement Suspended Slab or Wall to distribute early thermal cracking Refer BS 8007 - 1987
(a) Overall depth of slab/ wall < 500 ,ast= 0.00175bD for grade 460 or 0.0032bD for grade 250 on each face Appendix A Table A.1 & Fig A.1
(b) Overall depth of slab/ wall > 500 ,ast= 0.0035b(250mm) for grade 460 or 0.0064b(250mm) for grade 250 on each face

Min Steel required 0.3500 % on each face

= 910 mm2
0
Provide max vertical steel area ### = #NUM! mm2

Required 16 mm @ #NUM! c/c

Provide 16 mm @ 125 c/c = 1608 mm2 ###

Corresponding r =( 3.14 x 16^ 2 / 4 x1000 /125 ) / ( 1000 x 182 ) = 0.0088379


Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

Assessment of crack in Flexure

Neutral axis calculation base on percentage of tensile steel provided


x = [((mp)2 +2 mp)0.5 -mp ] d ( Neglecting effect of compression steel if any)
((( 17.81 x 0.0088 ) ^ 2 + 2 x 17.81 x 0.0088 ) ^ 0.5 - 17.81x 0.0088 ) x 182 mm
77.4177270361 mm

z= d- x /3
=182mm - 77.42mm / 3
156.194090988 mm

fs = Service Stress in tensile steel


M/ As z
=245.153 kN m x 10^6 / ( 1608.5 mm2 x 156.19 mm )
975.78298265 N/mm2

es= Strain at tensile steel level


=975.783 N/mm2 / 200000 N/mm2
0.00488 -

e1= Strain in extreme concrete end ( at location h from comp side)


es * (h-x) / (d-x)
=0.00488 x ( ( 250 mm - 77.42 mm) / ( 182 mm- 77.42 mm) )
0.00805121367 -

e2= Strain correction due to stiffening effect


b ( h - x )2 / 3 Es As ( d - x )
= ( ( 1000 mm x ( 250 mm - 77.42 mm) ^ 2 / ( 3 x 200000 kN/mm2 x 1608.5 mm2 x ( 182 mm - 77.42 mm) ) ) )
0.00029509592 -

em= Average strain in flexure


e1-e2
=0.00805 - 0.0003
0.00776 - > 0.00168 - UnSafe-strain is greater than 0.8 fy /Es

Cmin= 60mm +16mm + 0.5 x16mm


84.000 mm

acr= ( ( 84 mm) ^ 2 + ( 0.5 x 125 mm) ^ 2 ) ^ 0.5


104.700764085 mm

Wcr= Final crack width


3 acr em / [ 1+ (2 (acr -Cmin) / (h - x ))]
= ( 3 x 104.701 mmx 0.0003 / ( ( 1 + ( 2 x ( 104.701 mm - 84 mm) / ( 250 mm - 77.418 mm )))))
1.96485626411 mm > 0.3 mm UnSafe - Actual crack width > Permisible crack width

b ) Designing for Vertical bending moment at midheight 75.305 kN m Factored Moment


62.028 kN m UnFactored Moment
Considering axial compression of wall due to self weight and platform weight is < 0.1 Fcu bd and hence designing
Vertical element as slab not as a wall
Also neglecting reduction in tension steel due to effect of compressive load mentioned above

K = Md / Fcu b d 2 BS8110-Part 1 1997


= 75.305 x 10^6 / ( 25 x 1000 x 182^ 2 ) 3.4.4.4
0.09094 N/mm2 < 0.156 N/mm2 Singly reinforced beam

z = min [( 0.5 + ( 0.25 - k / 0.9 )^ 0.5, 0.95 ] x d


161.243 mm

x = ( d - z ) / 0.45
= ( 182 - 161.24 ) / 0.45
46.1261 mm

As = Md / ( 0.87 fy z ) Reference S.S. Ray


75.3 x 10^6 / ( 0.87 x 420 x 161.24 ) 100 As
Clear Spac
1278.12 mm2 /bd(%)
1 or Over 160
Recommended Spacing of Reinforcement in tension 0.75 210
0.5 320
% of Steel = ( 1278.12 x 100 ) / ( 1000 x 182) 0.3 530
0.70227 < 0.3 min (3d,750)
Minimum Spacing recommended 160 mm ( refer table right side)
Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

Minimum reinforcement Suspended Slab or Wall to distribute early thermal cracking Refer BS 8007 - 1987
(a) Overall depth of slab/ wall < 500 ,ast= 0.00175bD for grade 460 or 0.0032bD for grade 250 on each face Appendix A Table A.1 & Fig A.1
(b) Overall depth of slab/ wall > 500 ,ast= 0.0035b(250mm) for grade 460 or 0.0064b(250mm) for grade 250 on each face

Min Steel required 0.3500 % on each face

0.35 x 1000 mmx 250 mm / 100 = 875 mm2

Provide max vertical steel area =MAX ( 1278 , 875 ) = 1278 mm2

Required 16 mm @ 157.31018 c/c

Provide 16 mm @ 125 c/c = 1608 mm2 Ok

Corresponding r =( 3.14 x 16^ 2 / 4 x1000 /125 ) / ( 1000 x 182 ) = 0.0088379

Assessment of crack in Flexure

Neutral axis calculation base on percentage of tensile steel provided


x = [((mp)2 +2 mp)0.5 -mp ] d ( Neglecting effect of compression steel if any)
((( 17.81 x 0.0088 ) ^ 2 + 2 x 17.81 x 0.0088 ) ^ 0.5 - 17.81x 0.0088 ) x 182 mm
77.4177270361 mm

z= d- x /3
=182mm - 77.42mm / 3
156.194090988 mm

fs = Service Stress in tensile steel


M/ As z
=62.028 kN m x 10^6 / ( 1608.5 mm2 x 156.19 mm )
246.888104325 N/mm2

es= Strain at tensile steel level


=246.888 N/mm2 / 200000 N/mm2
0.00123 -

e1= Strain in extreme concrete end ( at location h from comp side)


es * (h-x) / (d-x)
=0.00123 x ( ( 250 mm - 77.42 mm) / ( 182 mm- 77.42 mm) )
0.0020370809 -

e2= Strain correction due to stiffening effect


b ( h - x )2 / 3 Es As ( d - x )
= ( ( 1000 mm x ( 250 mm - 77.42 mm) ^ 2 / ( 3 x 200000 kN/mm2 x 1608.5 mm2 x ( 182 mm - 77.42 mm) ) ) )
0.00029509592 -

em= Average strain in flexure


e1-e2
=0.00204 - 0.0003
0.00174 - > 0.00168 - UnSafe-strain is greater than 0.8 fy /Es

Cmin= 60mm +16mm + 0.5 x16mm


84.000 mm

acr= ( ( 84 mm) ^ 2 + ( 0.5 x 125 mm) ^ 2 ) ^ 0.5


104.700764085 mm

Wcr= Final crack width


3 acr em / [ 1+ (2 (acr -Cmin) / (h - x ))]
= ( 3 x 104.701 mmx 0.0003 / ( ( 1 + ( 2 x ( 104.701 mm - 84 mm) / ( 250 mm - 77.418 mm )))))
0.44129682072 mm > 0.3 mm UnSafe - Actual crack width > Permisible crack width

c ) Designing for Vertical wall for horizontal base shear 392.364 kN Factored Shear
323.229 kN UnFactored Shear
Percentage of tensile steel provided 0.8837887 %

vc= 0.79 [ (min (pt , 3 )) 0.333 x (max (400/d) , 1 )0.25 x (min( 40 ,fcu)/25) 0.333 ] / ym
=0.79 x MIN ( 0.884 , 3 ) ^ (1/3) x MAX ( 400 / 182 ) ^ 0.25 x ( MIN (40, 25 ) / 25 ) ^(1/3) /1.25
0.73846578421 N/mm2
Vc= vc x b x d
0.738 x 1000 x 182
134400.77272601 N
134.400772726 kN < 392.364 kN Unsafe
Since Vc < 0.8*SqrtFcu & 5N/mm2, enhanced shear = =(2*Q34*E223)/((TAN30*31.4/180)*Q34) =' 2.5597 N/mm2
Vc= vc x b x d
Vc= 2.56 x 1000 x 182
465863.47 N
465.863470325 kN > 392.364 kN Safe
Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

d ) Designing for Horizontal bending moment at side support 433.636 kN m Factored Moment
356.744 kN m UnFactored Moment
Considering axial compression of wall due to self weight and platform weight is < 0.1 Fcu bd and hence designing
Vertical element as slab not as a wall
Also neglecting reduction in tension steel due to effect of compressive load mentioned above

K = Md / Fcu b d 2 BS8110-Part 1 1997


= 433.636 x 10^6 / ( 25 x 1000 x 182^ 2 ) 3.4.4.4
0.52365 N/mm2 > 0.156 N/mm 2
Doubly reinforced beam

z = min [( 0.5 + ( 0.25 - k / 0.9 )^ 0.5, 0.95 ] x d


#NUM! mm

x = ( d - z ) / 0.45
= ###
#NUM! mm

As = Md / ( 0.87 fy z )
###
#NUM! mm2
Reference S.S. Ray
Recommended Spacing of Reinforcement in tension 100 As
Clear Spac
/bd(%)
% of Steel = ### 1 or Over 160
#NUM! 0.75 210
Minimum Spacing recommended 160 mm ( refer table right side) 0.5 320
0.3 530
< 0.3 min (3d,750)
Minimum reinforcement Suspended Slab or Wall to distribute early thermal cracking Refer BS 8007 - 1987
(a) Overall depth of slab/ wall < 500 ,ast= 0.00175bD for grade 460 or 0.0032bD for grade 250 on each face Appendix A Table A.1 & Fig A.1
(b) Overall depth of slab/ wall > 500 ,ast= 0.0035b(250mm) for grade 460 or 0.0064b(250mm) for grade 250 on each face

Min Steel required 0.1750 % on each face

0.175 x 1000 mmx 250 mm / 100 = 437.5 mm2

Provide max vertical steel area ### = #NUM! mm2

Required 16 mm @ #NUM! c/c

Provide 16 mm @ 125 c/c = 1608 mm2 ###

Corresponding r =( 3.14 x 16^ 2 / 4 x1000 /125 ) / ( 1000 x 182 ) = 0.0088379

Assessment of crack in Flexure

Neutral axis calculation base on percentage of tensile steel provided


x = [((mp)2 +2 mp)0.5 -mp ] d ( Neglecting effect of compression steel if any)
((( 17.81 x 0.0088 ) ^ 2 + 2 x 17.81 x 0.0088 ) ^ 0.5 - 17.81x 0.0088 ) x 182 mm
77.4177270361 mm

z= d- x /3
=182mm - 77.42mm / 3
156.194090988 mm

fs = Service Stress in tensile steel


M/ As z
=356.744 kN m x 10^6 / ( 1608.5 mm2 x 156.19 mm )
1419.94644136 N/mm2

es= Strain at tensile steel level


=1419.946 N/mm2 / 200000 N/mm2
0.00710 -

e1= Strain in extreme concrete end ( at location h from comp side)


es * (h-x) / (d-x)
=0.0071 x ( ( 250 mm - 77.42 mm) / ( 182 mm- 77.42 mm) )
0.01171601924 -

e2= Strain correction due to stiffening effect


b ( h - x )2 / 3 Es As ( d - x )
= ( ( 1000 mm x ( 250 mm - 77.42 mm) ^ 2 / ( 3 x 200000 kN/mm2 x 1608.5 mm2 x ( 182 mm - 77.42 mm) ) ) )
0.00029509592 -

em= Average strain in flexure


e1-e2
=0.01172 - 0.0003
0.01142 - > 0.00168 - UnSafe-strain is greater than 0.8 fy /Es

Cmin= 60mm +16mm + 0.5 x16mm


84.000 mm

acr= ( ( 84 mm) ^ 2 + ( 0.5 x 125 mm) ^ 2 ) ^ 0.5


104.700764085 mm

Wcr= Final crack width


3 acr em / [ 1+ (2 (acr -Cmin) / (h - x ))]
Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

= ( 3 x 104.701 mmx 0.0003 / ( ( 1 + ( 2 x ( 104.701 mm - 84 mm) / ( 250 mm - 77.418 mm )))))


2.89326096561 mm > 0.3 mm UnSafe - Actual crack width > Permisible crack width
Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

e ) Designing for Horizontal bending moment at midspan 628.563 kN m Factored Moment


521.461 kN m UnFactored Moment
Considering axial compression of wall due to self weight and platform weight is < 0.1 Fcu bd and hence designing
Vertical element as slab not as a wall
Also neglecting reduction in tension steel due to effect of compressive load mentioned above

K = Md / Fcu b d 2 BS8110-Part 1 1997


= 628.563 x 10^6 / ( 25 x 1000 x 182^ 2 ) 3.4.4.4
0.75904 N/mm2 > 0.156 N/mm2 Doubly reinforced beam

z = min [( 0.5 + ( 0.25 - k / 0.9 )^ 0.5, 0.95 ] x d


#NUM! mm

x = ( d - z ) / 0.45
= ###
#NUM! mm

As = Md / ( 0.87 fy z )
###
#NUM! mm2
Reference S.S. Ray
Recommended Spacing of Reinforcement in tension 100 As
Clear Spac
/bd(%)
% of Steel = ### 1 or Over 160
#NUM! 0.75 210
Minimum Spacing recommended 160 mm ( refer table right side) 0.5 320
0.3 530
< 0.3 min (3d,750)
Minimum reinforcement Suspended Slab or Wall to distribute early thermal cracking Refer BS 8007 - 1987
(a) Overall depth of slab/ wall < 500 ,ast= 0.00175bD for grade 460 or 0.0032bD for grade 250 on each face Appendix A Table A.1 & Fig A.1
(b) Overall depth of slab/ wall > 500 ,ast= 0.0035b(250mm) for grade 460 or 0.0064b(250mm) for grade 250 on each face

Min Steel required 0.3500 % on each face

0.35 x 1000 mmx 250 mm / 100 = 875 mm2

Provide max vertical steel area ### = #NUM! mm2

Required 16 mm @ #NUM! c/c

Provide 16 mm @ 100 c/c = 2011 mm2 ###

Corresponding r =( 3.14 x 16^ 2 / 4 x1000 /100 ) / ( 1000 x 182 ) = 0.0110474

Assessment of crack in Flexure

Neutral axis calculation base on percentage of tensile steel provided


x = [((mp)2 +2 mp)0.5 -mp ] d ( Neglecting effect of compression steel if any)
((( 17.81 x 0.011 ) ^ 2 + 2 x 17.81 x 0.011 ) ^ 0.5 - 17.81x 0.011 ) x 182 mm
83.8511458249 mm

z= d- x /3
=182mm - 83.85mm / 3
154.049618058 mm

fs = Service Stress in tensile steel


M/ As z
=521.461 kN m x 10^6 / ( 2010.62 mm2 x 154.05 mm )
1683.56947342 N/mm2

es= Strain at tensile steel level


=1683.569 N/mm2 / 200000 N/mm2
0.00842 -

e1= Strain in extreme concrete end ( at location h from comp side)


es * (h-x) / (d-x)
=0.00842 x ( ( 250 mm - 83.85 mm) / ( 182 mm- 83.85 mm) )
0.01424994419 -

e2= Strain correction due to stiffening effect


b ( h - x )2 / 3 Es As ( d - x )
= ( ( 1000 mm x ( 250 mm - 83.85 mm) ^ 2 / ( 3 x 200000 kN/mm2 x 2010.62 mm2 x ( 182 mm - 83.85 mm) ) ) )
0.00023314622 -
Client ETCHO Job No.: ETCHO 01/2019 Page.: of :
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

em= Average strain in flexure


e1-e2
=0.01425 - 0.00023
0.01402 - > 0.00168 - UnSafe-strain is greater than 0.8 fy /Es
neg value of em indicates that no crack is formed.
Cmin= 60mm +16mm + 0.5 x16mm
84.000 mm

acr= ( ( 84 mm) ^ 2 + ( 0.5 x 100 mm) ^ 2 ) ^ 0.5


97.7547952788 mm

Wcr= Final crack width


3 acr em / [ 1+ (2 (acr -Cmin) / (h - x ))]
= ( 3 x 97.755 mmx 0.0002 / ( ( 1 + ( 2 x ( 97.755 mm - 84 mm) / ( 250 mm - 83.851 mm )))))
3.52670432218 mm > 0.3 mm UnSafe - Actual crack width > Permisible crack width

f) Designing wall for horizontal base shear 382.082 kN Factored Shear


314.227 kN UnFactored Shear
Percentage of tensile steel provided 0.8837887 %

vc= 0.79 [ (min (pt , 3 )) 0.333 x (max (400/d) , 1 )0.25 x (min( 40 ,fcu)/25) 0.333 ] / ym
=0.79 x MIN ( 0.884 , 3 ) ^ (1/3) x MAX ( 400 / 182 ) ^ 0.25 x ( MIN (40, 25 ) / 25 ) ^(1/3) /1.25
0.73846578421 N/mm2
Vc= vc x b x d
0.738 x 1000 x 182
134400.77272601 N
134.400772726 kN < 382.082 kN Unsafe

Since Vc < 0.8*SqrtFcu & 5N/mm2, enhanced shear = =(2*deff*Vc)/((TAN30*3.14/180)*deff) =' 2.5597 N/mm2
Vc= vc x b x d
Vc= 2.56 x 1000 x 182
465863.47 N
465.863470325 kN > 382.082 kN Safe
Client AGIP Job No.: JI176 Page.: of :
Project KASHAGAN Prep. By.: ABA Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: Date :

DESIGN OF BASE SLAB - BS (Cracked)


Design Basis
Design Parameter
f'c 25 N/mm2
fs 420 N/mm2 0.2 mm for severe or very
Permisible crack width 0.3 mm severe explosure
Ec ( For cracked ) = 5.5 x (fcu / g f)^ 0.5 0.1 mm criticla asthetic
= 5.5 x ( 25 / 1.5 )^ 0.5 appearance
22.45366 kN/mm2 BS8007-1987, 2.2.3.3 a
m , Modular ratio 200 / 22.45
8.907235
Summary of Forces on base slab

No. Location Factored Values UnFactored Values


a) Support moment in short span direction Case A 1584 kNm / m 1056.253 kNm / m
b) Support moment in short span direction Case C 1940 kNm / m 1293.182 kNm / m
c) Shear Force for short span direction Case C 482 kN / m 321.027 kN / m
d) Midspan moment in short span direction Case A1 -164 kNm / m -109.081 kNm / m
e) Support moment in long span direction Case A 368 kN / m 245.153 kN / m
f) Support moment in long span direction Case B a 523 kNm / m 348.688 kNm / m
g) Shear Force for long span direction Case B a 319 kN / m 212.555 kN / m
h) Midspan moment in long span direction Case A 0 kNm / m 0.000 kNm / m

Considered the overall thickness of base slab is 250 mm

Clear Cover 50 mm

Bar Dia Assume 32 mm

Effective depth d = 250mm -50mm - 0.5 x32mm = 184 mm Calculated at 1st layer

a ) Designing for bottom reinforcement in short span direction 1939.774 kN m Factored Moment
1293.182 kN m UnFactored Moment
Considering axial compression of wall due to self weight and platform weight is < 0.1 Fcu bd and hence designing
Vertical element as slab not as a wall
Also neglecting reduction in tension steel due to effect of compressive load mentioned above

K = Md / Fcu b d 2 BS8110-Part 1 1997


= 1939.774 x 10^6 / ( 25 x 1000 x 184^ 2 ) 3.4.4.4
2.29179 N/mm2 > 0.156 N/mm2 Doubly reinforced beam

z = min [( 0.5 + ( 0.25 - k / 0.9 )^ 0.5, 0.95 ] x d


#NUM! mm

x = ( d - z ) / 0.45
= ###
#NUM! mm

As = Md / ( 0.87 fy z )
###
#NUM! mm2
Reference S.S. Ray
Recommended Spacing of Reinforcement in tension 100 As
Clear Spac
/bd(%)
% of Steel = ### 1 or Over 160
#NUM! 0.75 210
Minimum Spacing recommended 250 mm ( refer table right side) 0.5 320
0.3 530
< 0.3 min (3d,750)
Minimum reinforcement Suspended Slab or Wall to distribute early thermal cracking Refer BS 8007 - 1987
(a) Overall depth of slab/ wall < 500 ,ast= 0.00175bD for grade 460 or 0.0032bD for grade 250 on each face Appendix A Table A.1 & Fig A.1
(b) Overall depth of slab/ wall > 500 ,ast= 0.0035b(250mm) for grade 460 or 0.0064b(250mm) for grade 250 on each face

Min Steel required 0.3500 % on each face

0.35 x 1000 mmx 250 mm / 100 = 875 mm2

Provide max vertical steel area ### = #NUM! mm2

Required 32 mm @ ### c/c

Provide 32 mm @ 100 c/c = 8042 mm2 ###

Corresponding r =( 3.14 x 32^ 2 / 4 x1000 /100 ) / ( 1000 x 184 ) = 0.043709


Client AGIP Job No.: JI176 Page.: of :
Project KASHAGAN Prep. By.: ABA Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: Date :

Assessment of crack in Flexure

Neutral axis calculation base on percentage of tensile steel provided


x = [((mp)2 +2 mp)0.5 -mp ] d ( Neglecting effect of compression steel if any)
((( 8.91 x 0.0437 ) ^ 2 + 2 x 8.91 x 0.0437 ) ^ 0.5 - 8.91x 0.0437 ) x 184 mm
105.829 mm

z= d- x /3
=184mm - 105.83mm / 3
148.724 mm

fs = Service Stress in tensile steel


M/ As z
=1293.182 kN m x 10^6 / ( 8042.48 mm2 x 148.72 mm )
1081.16 N/mm2

es= Strain at tensile steel level


=1081.16 N/mm2 / 200000 N/mm2
0.00541 -

e1= Strain in extreme concrete end ( at location h from comp side)


es * (h-x) / (d-x)
=0.00541 x ( ( 250 mm - 105.83 mm) / ( 184 mm- 105.83 mm) )
0.00997 -

e2= Strain correction due to stiffening effect


b ( h - x )2 / 3 Es As ( d - x )
= ( ( 1000 mm x ( 250 mm - 105.83 mm) ^ 2 / ( 3 x 200000 kN/mm2 x 8042.48 mm2 x ( 184 mm - 105.83 mm) ) ) )
6E-05 -

em= Average strain in flexure


e1-e2
=0.00997 - 0.00006
0.00991 - > 0.00168 - UnSafe-strain is greater than 0.8 fy /Es

Cmin= 50mm +32mm + 0.5 x32mm


98.000 mm

acr= ( ( 98 mm) ^ 2 + ( 0.5 x 100 mm) ^ 2 ) ^ 0.5


110.018 mm

Wcr= Final crack width


3 acr em / [ 1+ (2 (acr -Cmin) / (h - x ))]
= ( 3 x 110.018 mmx 0.0001 / ( ( 1 + ( 2 x ( 110.018 mm - 98 mm) / ( 250 mm - 105.829 mm )))))
2.8 mm > 0.3 mm UnSafe - Actual crack width > Permisible crack width

b ) Designing for top reinforcement in short span direction -163.621 kN m Factored Moment
-109.081 kN m UnFactored Moment
Considering axial compression of wall due to self weight and platform weight is < 0.1 Fcu bd and hence designing
Vertical element as slab not as a wall
Also neglecting reduction in tension steel due to effect of compressive load mentioned above

K = Md / Fcu b d 2 BS8110-Part 1 1997


= -163.621 x 10^6 / ( 25 x 1000 x 184^ 2 ) 3.4.4.4
-0.1933 N/mm2 < 0.156 N/mm2 Singly reinforced beam

z = min [( 0.5 + ( 0.25 - k / 0.9 )^ 0.5, 0.95 ] x d


174.8 mm

x = ( d - z ) / 0.45
= ( 184 - 174.8 ) / 0.45
20.4444 mm
Reference S.S. Ray
As = Md / ( 0.87 fy z ) 100 As
Clear Spac
-163.62 x 10^6 / ( 0.87 x 420 x 174.8 ) /bd(%)
-2561.7 mm2 1 or Over 160
0.75 210
Client AGIP Job No.: JI176 Page.: of :
Project KASHAGAN Prep. By.: ABA Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: Date :

Recommended Spacing of Reinforcement in tension 0.5 320


0.3 530
% of Steel = ( -2561.7 x 100 ) / ( 1000 x 184) < 0.3 min (3d,750)
-1.3922
Minimum Spacing recommended 530 mm ( refer table right side)

Minimum reinforcement Suspended Slab or Wall to distribute early thermal cracking Refer BS 8007 - 1987
(a) Overall depth of slab/ wall < 500 ,ast= 0.00175bD for grade 460 or 0.0032bD for grade 250 on each face Appendix A Table A.1 & Fig A.1
(b) Overall depth of slab/ wall > 500 ,ast= 0.0035b(250mm) for grade 460 or 0.0064b(250mm) for grade 250 on each face

Min Steel required 0.1750 % on each face

0.175 x 1000 mmx 250 mm / 100 = 437.5 mm2

Provide max vertical steel area =MAX ( -2562 , 438 ) = 438 mm2

Required 20 mm @ 718 c/c

Provide 20 mm @ 100 c/c = 3142 mm2 Ok

Corresponding r =( 3.14 x 20^ 2 / 4 x1000 /100 ) / ( 1000 x 184 ) = 0.017074

Assessment of crack in Flexure

Neutral axis calculation base on percentage of tensile steel provided


x = [((mp)2 +2 mp)0.5 -mp ] d ( Neglecting effect of compression steel if any)
((( 8.91 x 0.0171 ) ^ 2 + 2 x 8.91 x 0.0171 ) ^ 0.5 - 8.91x 0.0171 ) x 184 mm
77.2822 mm

z= d- x /3
=184mm - 77.28mm / 3
158.239 mm

fs = Service Stress in tensile steel


M/ As z
=-109.081 kN m x 10^6 / ( 3141.59 mm2 x 158.24 mm )
-219.42 N/mm2

es= Strain at tensile steel level


=-219.424 N/mm2 / 200000 N/mm2
-0.00110 -

e1= Strain in extreme concrete end ( at location h from comp side)


es * (h-x) / (d-x)
=-0.0011 x ( ( 250 mm - 77.28 mm) / ( 184 mm- 77.28 mm) )
-0.0018 -

e2= Strain correction due to stiffening effect


b ( h - x )2 / 3 Es As ( d - x )
= ( ( 1000 mm x ( 250 mm - 77.28 mm) ^ 2 / ( 3 x 200000 kN/mm2 x 3141.59 mm2 x ( 184 mm - 77.28 mm) ) ) )
0.00015 -

em= Average strain in flexure


e1-e2
=-0.00178 - 0.00015
### - < 0.00168 - Safe-strain is less than 0.8 fy /Es

Cmin= 50mm +20mm + 0.5 x20mm


80.000 mm

acr= ( ( 80 mm) ^ 2 + ( 0.5 x 100 mm) ^ 2 ) ^ 0.5


94.3398 mm

Wcr= Final crack width


3 acr em / [ 1+ (2 (acr -Cmin) / (h - x ))]
= ( 3 x 94.34 mmx 0.0001 / ( ( 1 + ( 2 x ( 94.34 mm - 80 mm) / ( 250 mm - 77.282 mm )))))
-0.467 mm < 0.3 mm Safe - Actual crack width < Permisible crack width
Client AGIP Job No.: JI176 Page.: of :
Project KASHAGAN Prep. By.: ABA Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: Date :

c ) Designing for Short Span Shear 481.541 kN Factored Shear


321.027 kN UnFactored Shear
Percentage of tensile steel provided 4.37091 %

vc= 0.79 [ (min (pt , 3 )) 0.333 x (max (400/d) , 1 )0.25 x (min( 40 ,fcu)/25) 0.333 ] / ym
=0.79 x MIN ( 4.371 , 3 ) ^ (1/3) x MAX ( 400 / 184 ) ^ 0.25 x ( MIN (40, 25 ) / 25 ) ^(1/3) /1.25
1.1068 N/mm2
Vc= vc x b x d
1.107 x 1000 x 184
203650.679 N
203.651 kN < 481.541 kN Unsafe

d ) Designing for bottom reinforcement in long span direction 523.032 kN m Factored Moment
348.688 kN m UnFactored Moment
Considering axial compression of wall due to self weight and platform weight is < 0.1 Fcu bd and hence designing
Vertical element as slab not as a wall
Also neglecting reduction in tension steel due to effect of compressive load mentioned above

K = Md / Fcu b d 2 BS8110-Part 1 1997


= 523.032 x 10^6 / ( 25 x 1000 x 184^ 2 ) 3.4.4.4
0.62 N/mm2 > 0.156 N/mm2 Doubly reinforced beam

z = min [( 0.5 + ( 0.25 - k / 0.9 )^ 0.5, 0.95 ] x d


#NUM! mm

x = ( d - z ) / 0.45
= ###
#NUM! mm

As = Md / ( 0.87 fy z )
###
#NUM! mm2
Reference S.S. Ray
Recommended Spacing of Reinforcement in tension 100 As
Clear Spac
/bd(%)
% of Steel = ### 1 or Over 160
#NUM! 0.75 210
Minimum Spacing recommended 160 mm ( refer table right side) 0.5 320
0.3 530
< 0.3 min (3d,750)
Minimum reinforcement Suspended Slab or Wall to distribute early thermal cracking Refer BS 8007 - 1987
(a) Overall depth of slab/ wall < 500 ,ast= 0.00175bD for grade 460 or 0.0032bD for grade 250 on each face Appendix A Table A.1 & Fig A.1
(b) Overall depth of slab/ wall > 500 ,ast= 0.0035b(250mm) for grade 460 or 0.0064b(250mm) for grade 250 on each face

Min Steel required 0.1750 % on each face

0.175 x 1000 mmx 250 mm / 100 = 437.5 mm2

Provide max vertical steel area ### = #NUM! mm2

Required 25 mm @ ### c/c

Provide 25 mm @ 100 c/c = 4909 mm2 ###

Corresponding r =( 3.14 x 25^ 2 / 4 x1000 /100 ) / ( 1000 x 184 ) = 0.026678

Assessment of crack in Flexure

Neutral axis calculation base on percentage of tensile steel provided


x = [((mp)2 +2 mp)0.5 -mp ] d ( Neglecting effect of compression steel if any)
((( 8.91 x 0.0267 ) ^ 2 + 2 x 8.91 x 0.0267 ) ^ 0.5 - 8.91x 0.0267 ) x 184 mm
90.4479 mm

z= d- x /3
=184mm - 90.45mm / 3
153.851 mm

fs = Service Stress in tensile steel


M/ As z
=348.688 kN m x 10^6 / ( 4908.74 mm2 x 153.85 mm )
369.366 N/mm2 (REDUCED BY 25 % CONSIDEING SESIMIC IS CONSIDERED )

es= Strain at tensile steel level


=369.366 N/mm2 / 200000 N/mm2
0.00185 -

e1= Strain in extreme concrete end ( at location h from comp side)


es * (h-x) / (d-x)
Client AGIP Job No.: JI176 Page.: of :
Project KASHAGAN Prep. By.: ABA Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: Date :

=0.00185 x ( ( 250 mm - 90.45 mm) / ( 184 mm- 90.45 mm) )


0.00315 -

e2= Strain correction due to stiffening effect


b ( h - x )2 / 3 Es As ( d - x )
= ( ( 1000 mm x ( 250 mm - 90.45 mm) ^ 2 / ( 3 x 200000 kN/mm2 x 4908.74 mm2 x ( 184 mm - 90.45 mm) ) ) )
9E-05 -

em= Average strain in flexure


e1-e2
=0.00315 - 0.00009
0.00306 - > 0.00168 - UnSafe-strain is greater than 0.8 fy /Es

Cmin= 50mm +25mm + 0.5 x25mm


62.500 mm

acr= ( ( 62.5 mm) ^ 2 + ( 0.5 x 100 mm) ^ 2 ) ^ 0.5


80.0391 mm

Wcr= Final crack width


3 acr em / [ 1+ (2 (acr -Cmin) / (h - x ))]
= ( 3 x 80.039 mmx 0.0001 / ( ( 1 + ( 2 x ( 80.039 mm - 62.5 mm) / ( 250 mm - 90.448 mm )))))
0.6 mm > 0.3 mm UnSafe - Actual crack width > Permisible crack width

e ) Designing for top reinforcement in long span direction 0.000 kN m Factored Moment
0.000 kN m UnFactored Moment
Considering axial compression of wall due to self weight and platform weight is < 0.1 Fcu bd and hence designing
Vertical element as slab not as a wall
Also neglecting reduction in tension steel due to effect of compressive load mentioned above

K = Md / Fcu b d 2 BS8110-Part 1 1997


= 0 x 10^6 / ( 25 x 1000 x 184^ 2 ) 3.4.4.4
0 N/mm2 < 0.156 N/mm2 Singly reinforced beam

z = min [( 0.5 + ( 0.25 - k / 0.9 )^ 0.5, 0.95 ] x d


174.8 mm

x = ( d - z ) / 0.45
= ( 184 - 174.8 ) / 0.45
20.4444 mm

As = Md / ( 0.87 fy z )
0 x 10^6 / ( 0.87 x 420 x 174.8 )
0 mm2
Reference S.S. Ray
Recommended Spacing of Reinforcement in tension 100 As
Clear Spac
/bd(%)
% of Steel = ( 0 x 100 ) / ( 1000 x 184) 1 or Over 160
0 0.75 210
Minimum Spacing recommended 160 mm ( refer table right side) 0.5 320
0.3 530
< 0.3 min (3d,750)
Minimum reinforcement Suspended Slab or Wall to distribute early thermal cracking Refer BS 8007 - 1987
(a) Overall depth of slab/ wall < 500 ,ast= 0.00175bD for grade 460 or 0.0032bD for grade 250 on each face Appendix A Table A.1 & Fig A.1
(b) Overall depth of slab/ wall > 500 ,ast= 0.0035b(250mm) for grade 460 or 0.0064b(250mm) for grade 250 on each face

Min Steel required 0.1750 % on each face

0.175 x 1000 mmx 250 mm / 100 = 437.5 mm2

Provide max vertical steel area =MAX ( 0 , 438 ) = 438 mm2

Required 16 mm @ 460 c/c

Provide 16 mm @ 100 c/c = 2011 mm2 Ok

Corresponding r =( 3.14 x 16^ 2 / 4 x1000 /100 ) / ( 1000 x 184 ) = 0.010927

Assessment of crack in Flexure

Neutral axis calculation base on percentage of tensile steel provided


x = [((mp)2 +2 mp)0.5 -mp ] d ( Neglecting effect of compression steel if any)
((( 8.91 x 0.0109 ) ^ 2 + 2 x 8.91 x 0.0109 ) ^ 0.5 - 8.91x 0.0109 ) x 184 mm
65.225 mm

z= d- x /3
=184mm - 65.22mm / 3
Client AGIP Job No.: JI176 Page.: of :
Project KASHAGAN Prep. By.: ABA Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: Date :

162.258 mm

fs = Service Stress in tensile steel


M/ As z
=0 kN m x 10^6 / ( 2010.62 mm2 x 162.26 mm )
0 N/mm2

es= Strain at tensile steel level


=0 N/mm2 / 200000 N/mm2
0.00000 -

e1= Strain in extreme concrete end ( at location h from comp side)


es * (h-x) / (d-x)
=0 x ( ( 250 mm - 65.22 mm) / ( 184 mm- 65.22 mm) )
0 -

e2= Strain correction due to stiffening effect


b ( h - x )2 / 3 Es As ( d - x )
= ( ( 1000 mm x ( 250 mm - 65.22 mm) ^ 2 / ( 3 x 200000 kN/mm2 x 2010.62 mm2 x ( 184 mm - 65.22 mm) ) ) )
0.00024 -

em= Average strain in flexure


e1-e2
=0 - 0.00024
-0.0002 - < 0.00168 - Safe-strain is less than 0.8 fy /Es
if em is -ve it indicates no cracks.
Cmin= 50mm +16mm + 0.5 x16mm
74.000 mm

acr= ( ( 74 mm) ^ 2 + ( 0.5 x 100 mm) ^ 2 ) ^ 0.5


89.3085 mm

Wcr= Final crack width


3 acr em / [ 1+ (2 (acr -Cmin) / (h - x ))]
= ( 3 x 89.308 mmx 0.0002 / ( ( 1 + ( 2 x ( 89.308 mm - 74 mm) / ( 250 mm - 65.225 mm )))))
-0.0548 mm < 0.3 mm Safe - Actual crack width < Permisible crack width

f) Designing for Long Span Shear 318.833 kN Factored Shear


212.555 kN UnFactored Shear
Percentage of tensile steel provided 2.66779 %

vc= 0.79 [ (min (pt , 3 )) 0.333 x (max (400/d) , 1 )0.25 x (min( 40 ,fcu)/25) 0.333 ] / ym
=0.79 x MIN ( 2.668 , 3 ) ^ (1/3) x MAX ( 400 / 184 ) ^ 0.25 x ( MIN (40, 25 ) / 25 ) ^(1/3) /1.25
1.06433 N/mm2
Since Vc < 0.8*SqrtFcu & 5N/mm2, enhanced shear = 3.689 N/mm2
Vc= vc x b x d
Vc= 3.69 x 1000 x 184
Vc= 678817.50 N
678.817 kN > 318.833 kN Safe
Client AGIP Job No.: JI176 Page.: of :
Project KASHAGAN Prep. By.: ABA Date : 27/06/2005
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: Date :
0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11
0.00 1 1.00 1.05 1.10 1.15 1.20 1.30 1.40 1.45 1.50 1.55 1.60 1.65
0.01 2 1.05 1.10 1.15 1.23 1.30 1.38 1.45 1.50 1.55 1.60 1.65 1.70
0.02 3 1.10 1.15 1.20 1.30 1.40 1.45 1.50 1.55 1.60 1.65 1.70 1.75
0.03 4 1.15 1.23 1.30 1.38 1.45 1.50 1.55 1.60 1.65 1.70 1.75 1.83
0.04 5 1.20 1.30 1.40 1.45 1.50 1.55 1.60 1.65 1.70 1.75 1.80 1.90
0.05 6 1.30 1.38 1.45 1.50 1.55 1.60 1.65 1.70 1.75 1.83 1.90 1.98
0.06 7 1.40 1.45 1.50 1.55 1.60 1.65 1.70 1.75 1.80 1.90 2.00 2.05
0.07 8 1.45 1.50 1.55 1.60 1.65 1.70 1.75 1.83 1.90 1.98 2.05 2.10
0.08 9 1.50 1.55 1.60 1.65 1.70 1.75 1.80 1.90 2.00 2.05 2.10 2.15
0.09 10 1.55 1.60 1.65 1.70 1.75 1.83 1.90 1.98 2.05 2.10 2.15 2.20
0.10 11 1.60 1.65 1.70 1.75 1.80 1.90 2.00 2.05 2.10 2.15 2.20 2.25
0.11 12 1.65 1.70 1.75 1.83 1.90 1.98 2.05 2.10 2.15 2.20 2.25 2.33
0.12 13 1.70 1.75 1.80 1.90 2.00 2.05 2.10 2.15 2.20 2.25 2.30 2.40
0.13 14 1.75 1.83 1.90 1.98 2.05 2.10 2.15 2.20 2.25 2.33 2.40 2.48
0.14 15 1.80 1.90 2.00 2.05 2.10 2.15 2.20 2.25 2.30 2.40 2.50 2.55
0.15 16 1.90 1.98 2.05 2.10 2.15 2.20 2.25 2.33 2.40 2.48 2.55 2.63
0.16 17 2.00 2.05 2.10 2.15 2.20 2.25 2.30 2.40 2.50 2.55 2.60 2.70
0.17 18 2.05 2.10 2.15 2.20 2.25 2.33 2.40 2.48 2.55 2.63 2.70 2.80
0.18 19 2.10 2.15 2.20 2.25 2.30 2.40 2.50 2.55 2.60 2.70 2.80 2.90
0.19 20 2.15 2.23 2.30 2.35 2.40 2.50 2.60 2.65 2.70 2.80 2.90 3.00
el / lf 0.20 21 2.20 2.30 2.40 2.45 2.50 2.60 2.70 2.75 2.80 2.90 3.00 3.10
0.21 22 2.26 2.37 2.47 2.52 2.57 2.67 2.77 2.82 2.87 2.98 3.08 3.19
0.22 23 2.32 2.43 2.54 2.59 2.64 2.74 2.84 2.89 2.94 3.05 3.16 3.27
0.23 24 2.38 2.50 2.61 2.66 2.71 2.81 2.91 2.96 3.01 3.13 3.24 3.36
0.24 25 2.44 2.56 2.68 2.73 2.78 2.88 2.98 3.03 3.08 3.20 3.32 3.44
0.25 26 2.50 2.63 2.75 2.80 2.85 2.95 3.05 3.10 3.15 3.28 3.40 3.53
0.26 27 2.56 2.69 2.82 2.87 2.92 3.02 3.12 3.17 3.22 3.35 3.48 3.61
0.27 28 2.62 2.76 2.89 2.94 2.99 3.09 3.19 3.24 3.29 3.43 3.56 3.70
0.28 29 2.68 2.82 2.96 3.01 3.06 3.16 3.26 3.31 3.36 3.50 3.64 3.78
0.29 30 2.74 2.89 3.03 3.08 3.13 3.23 3.33 3.38 3.43 3.58 3.72 3.87
0.30 31 3.30 3.40 3.50 3.65 3.80 3.90 4.00 4.10 4.20 4.35 4.50 4.65
0.31 32 3.36 3.46 3.56 3.71 3.86 3.96 4.06 4.16 4.26 4.41 4.56 4.71
0.32 33 3.42 3.52 3.62 3.77 3.92 4.02 4.12 4.22 4.32 4.47 4.62 4.77
0.33 34 3.48 3.58 3.68 3.83 3.98 4.08 4.18 4.28 4.38 4.53 4.68 4.83
0.34 35 3.54 3.64 3.74 3.89 4.04 4.14 4.24 4.34 4.44 4.59 4.74 4.89
0.35 36 3.60 3.70 3.80 3.95 4.10 4.20 4.30 4.40 4.50 4.65 4.80 4.95
0.36 37 3.66 3.76 3.86 4.01 4.16 4.26 4.36 4.46 4.56 4.71 4.86 5.01
0.37 38 3.72 3.82 3.92 4.07 4.22 4.32 4.42 4.52 4.62 4.77 4.92 5.07
0.38 39 3.78 3.88 3.98 4.13 4.28 4.38 4.48 4.58 4.68 4.83 4.98 5.13
0.39 40 3.84 3.94 4.04 4.19 4.34 4.44 4.54 4.64 4.74 4.89 5.04 5.19
0.40 41 6.70 6.90 7.10 7.30 7.50 7.75 8.00 8.25 8.50 8.75 9.00 9.30
eb / bf
0.12 0.13 0.14 0.15 0.16 0.17 0.18 0.19 0.20 0.21 0.22 0.23 0.24 0.25 0.26
1.70 1.75 1.80 1.90 2.00 2.05 2.10 2.15 2.20 2.31 2.42 2.53 2.64 2.75 2.86
1.75 1.83 1.90 1.98 2.05 2.10 2.15 2.23 2.30 2.41 2.52 2.63 2.74 2.85 2.96
1.80 1.90 2.00 2.05 2.10 2.15 2.20 2.30 2.40 2.51 2.62 2.73 2.84 2.95 3.06
1.90 1.98 2.05 2.10 2.15 2.20 2.25 2.35 2.45 2.57 2.69 2.81 2.93 3.05 3.17
2.00 2.05 2.10 2.15 2.20 2.25 2.30 2.40 2.50 2.63 2.76 2.89 3.02 3.15 3.28
2.05 2.10 2.15 2.20 2.25 2.33 2.40 2.50 2.60 2.73 2.86 2.99 3.12 3.25 3.38
2.10 2.15 2.20 2.25 2.30 2.40 2.50 2.60 2.70 2.83 2.96 3.09 3.22 3.35 3.48
2.15 2.20 2.25 2.33 2.40 2.48 2.55 2.65 2.75 2.89 3.02 3.16 3.29 3.43 3.56
2.20 2.25 2.30 2.40 2.50 2.55 2.60 2.70 2.80 2.94 3.08 3.22 3.36 3.50 3.64
2.25 2.33 2.40 2.48 2.55 2.63 2.70 2.80 2.90 3.05 3.19 3.34 3.48 3.63 3.77
2.30 2.40 2.50 2.55 2.60 2.70 2.80 2.90 3.00 3.15 3.30 3.45 3.60 3.75 3.90
2.40 2.48 2.55 2.63 2.70 2.80 2.90 3.00 3.10 3.26 3.41 3.57 3.72 3.88 4.03
2.50 2.55 2.60 2.70 2.80 2.90 3.00 3.10 3.20 3.36 3.52 3.68 3.84 4.00 4.16
2.55 2.63 2.70 2.80 2.90 3.00 3.10 3.20 3.30 3.47 3.63 3.80 3.96 4.13 4.29
2.60 2.70 2.80 2.90 3.00 3.10 3.20 3.30 3.40 3.57 3.74 3.91 4.08 4.25 4.42
2.70 2.80 2.90 3.00 3.10 3.20 3.30 3.40 3.50 3.68 3.85 4.03 4.20 4.38 4.55
2.80 2.90 3.00 3.10 3.20 3.30 3.40 3.50 3.60 3.78 3.96 4.14 4.32 4.50 4.68
2.90 3.00 3.10 3.20 3.30 3.40 3.50 3.63 3.75 3.94 4.12 4.31 4.49 4.68 4.86
3.00 3.10 3.20 3.30 3.40 3.50 3.60 3.75 3.90 4.09 4.28 4.47 4.66 4.85 5.04
3.10 3.20 3.30 3.40 3.50 3.63 3.75 3.88 4.00 4.20 4.40 4.60 4.80 5.00 5.20
3.20 3.30 3.40 3.50 3.60 3.75 3.90 4.00 4.10 4.31 4.52 4.73 4.94 5.15 5.36
3.29 3.39 3.49 3.60 3.70 3.86 4.01 4.11 4.21 4.43 4.64 4.86 5.07 5.29 5.51
3.38 3.48 3.58 3.69 3.80 3.96 4.12 4.22 4.32 4.54 4.76 4.99 5.21 5.43 5.65
3.47 3.57 3.67 3.79 3.90 4.07 4.23 4.33 4.43 4.66 4.89 5.11 5.34 5.57 5.80
3.56 3.66 3.76 3.88 4.00 4.17 4.34 4.44 4.54 4.77 5.01 5.24 5.48 5.71 5.94
3.65 3.75 3.85 3.98 4.10 4.28 4.45 4.55 4.65 4.89 5.13 5.37 5.61 5.85 6.09
3.74 3.84 3.94 4.07 4.20 4.38 4.56 4.66 4.76 5.01 5.25 5.50 5.74 5.99 6.24
3.83 3.93 4.03 4.17 4.30 4.49 4.67 4.77 4.87 5.12 5.37 5.63 5.88 6.13 6.38
3.92 4.02 4.12 4.26 4.40 4.59 4.78 4.88 4.98 5.24 5.50 5.75 6.01 6.27 6.53
4.01 4.11 4.21 4.36 4.50 4.70 4.89 4.99 5.09 5.35 5.62 5.88 6.15 6.41 6.67
4.80 4.95 5.10 5.25 5.40 5.60 5.80 6.00 6.20 6.52 6.84 7.16 7.48 7.80 8.12
4.86 5.02 5.17 5.32 5.46 5.67 5.87 6.08 6.28 6.60 6.93 7.25 7.58 7.90 8.22
4.92 5.08 5.24 5.38 5.52 5.73 5.94 6.15 6.36 6.69 7.02 7.34 7.67 8.00 8.33
4.98 5.15 5.31 5.45 5.58 5.80 6.01 6.23 6.44 6.77 7.10 7.44 7.77 8.10 8.43
5.04 5.21 5.38 5.51 5.64 5.86 6.08 6.30 6.52 6.86 7.19 7.53 7.86 8.20 8.54
5.10 5.28 5.45 5.58 5.70 5.93 6.15 6.38 6.60 6.94 7.28 7.62 7.96 8.30 8.64
5.16 5.34 5.52 5.64 5.76 5.99 6.22 6.45 6.68 7.02 7.37 7.71 8.06 8.40 8.74
5.22 5.41 5.59 5.71 5.82 6.06 6.29 6.53 6.76 7.11 7.46 7.80 8.15 8.50 8.85
5.28 5.47 5.66 5.77 5.88 6.12 6.36 6.60 6.84 7.19 7.54 7.90 8.25 8.60 8.95
5.34 5.54 5.73 5.84 5.94 6.19 6.43 6.68 6.92 7.28 7.63 7.99 8.34 8.70 9.06
9.60 9.90 10.20 10.55 10.90 11.25 11.60 12.05 12.50 13.13 13.76 14.39 15.02 15.65 16.28
0.27 0.28 0.29 0.30 0.31 0.32 0.33 0.34 0.35 0.36 0.37 0.38 0.39 0.40
2.97 3.08 3.19 3.30 3.64 3.98 4.32 4.66 5.00 5.34 5.68 6.02 6.36 6.70
3.07 3.18 3.29 3.40 3.75 4.10 4.45 4.80 5.15 5.50 5.85 6.20 6.55 6.90
3.17 3.28 3.39 3.50 3.86 4.22 4.58 4.94 5.30 5.66 6.02 6.38 6.74 7.10
3.29 3.41 3.53 3.65 4.02 4.38 4.75 5.11 5.48 5.84 6.21 6.57 6.94 7.30
3.41 3.54 3.67 3.80 4.17 4.54 4.91 5.28 5.65 6.02 6.39 6.76 7.13 7.50
3.51 3.64 3.77 3.90 4.29 4.67 5.06 5.44 5.83 6.21 6.60 6.98 7.37 7.75
3.61 3.74 3.87 4.00 4.40 4.80 5.20 5.60 6.00 6.40 6.80 7.20 7.60 8.00
3.70 3.83 3.97 4.10 4.52 4.93 5.35 5.76 6.18 6.59 7.01 7.42 7.84 8.25
3.78 3.92 4.06 4.20 4.63 5.06 5.49 5.92 6.35 6.78 7.21 7.64 8.07 8.50
3.92 4.06 4.21 4.35 4.79 5.23 5.67 6.11 6.55 6.99 7.43 7.87 8.31 8.75
4.05 4.20 4.35 4.50 4.95 5.40 5.85 6.30 6.75 7.20 7.65 8.10 8.55 9.00
4.19 4.34 4.50 4.65 5.12 5.58 6.05 6.51 6.98 7.44 7.91 8.37 8.84 9.30
4.32 4.48 4.64 4.80 5.28 5.76 6.24 6.72 7.20 7.68 8.16 8.64 9.12 9.60
4.46 4.62 4.79 4.95 5.45 5.94 6.44 6.93 7.43 7.92 8.42 8.91 9.41 9.90
4.59 4.76 4.93 5.10 5.61 6.12 6.63 7.14 7.65 8.16 8.67 9.18 9.69 10.20
4.73 4.90 5.08 5.25 5.78 6.31 6.84 7.37 7.90 8.43 8.96 9.49 10.02 10.55
4.86 5.04 5.22 5.40 5.95 6.50 7.05 7.60 8.15 8.70 9.25 9.80 10.35 10.90
5.05 5.23 5.42 5.60 6.17 6.73 7.30 7.86 8.43 8.99 9.56 10.12 10.69 11.25
5.23 5.42 5.61 5.80 6.38 6.96 7.54 8.12 8.70 9.28 9.86 10.44 11.02 11.60
5.40 5.60 5.80 6.00 6.61 7.21 7.82 8.42 9.03 9.63 10.24 10.84 11.45 12.05
5.57 5.78 5.99 6.20 6.83 7.46 8.09 8.72 9.35 9.98 10.61 11.24 11.87 12.50
5.72 5.94 6.15 6.37 7.02 7.67 8.31 8.96 9.61 10.26 10.91 11.55 12.20 12.85
5.87 6.10 6.32 6.54 7.21 7.87 8.54 9.20 9.87 10.54 11.20 11.87 12.53 13.20
6.03 6.25 6.48 6.71 7.39 8.08 8.76 9.45 10.13 10.81 11.50 12.18 12.87 13.55
6.18 6.41 6.65 6.88 7.58 8.28 8.99 9.69 10.39 11.09 11.79 12.50 13.20 13.90
6.33 6.57 6.81 7.05 7.77 8.49 9.21 9.93 10.65 11.37 12.09 12.81 13.53 14.25
6.48 6.73 6.97 7.22 7.96 8.70 9.43 10.17 10.91 11.65 12.39 13.12 13.86 14.60
6.63 6.89 7.14 7.39 8.15 8.90 9.66 10.41 11.17 11.93 12.68 13.44 14.19 14.95
6.79 7.04 7.30 7.56 8.33 9.11 9.88 10.66 11.43 12.20 12.98 13.75 14.53 15.30
6.94 7.20 7.47 7.73 8.52 9.31 10.11 10.90 11.69 12.48 13.27 14.07 14.86 15.65
8.44 8.76 9.08 9.40 10.34 11.28 12.22 13.16 14.10 15.04 15.98 16.92 17.86 18.80
8.55 8.87 9.20 9.52 10.47 11.42 12.37 13.32 14.28 15.23 16.18 17.13 18.08 19.03
8.66 8.98 9.31 9.64 10.60 11.56 12.53 13.49 14.45 15.41 16.37 17.34 18.30 19.26
8.76 9.10 9.43 9.76 10.73 11.71 12.68 13.65 14.63 15.60 16.57 17.54 18.52 19.49
8.87 9.21 9.54 9.88 10.86 11.85 12.83 13.82 14.80 15.78 16.77 17.75 18.74 19.72
8.98 9.32 9.66 10.00 11.00 11.99 12.99 13.98 14.98 15.97 16.97 17.96 18.96 19.95
9.09 9.43 9.78 10.12 11.13 12.13 13.14 14.14 15.15 16.16 17.16 18.17 19.17 20.18
9.20 9.54 9.89 10.24 11.26 12.27 13.29 14.31 15.33 16.34 17.36 18.38 19.39 20.41
9.30 9.66 10.01 10.36 11.39 12.42 13.44 14.47 15.50 16.53 17.56 18.58 19.61 20.64
9.41 9.77 10.12 10.48 11.52 12.56 13.60 14.64 15.68 16.71 17.75 18.79 19.83 20.87
16.91 17.54 18.17 18.80 20.67 22.54 24.41 26.28 28.15 30.02 31.89 33.76 35.63 37.50
Client ETCHO Job No.: ETCHO 01/2019
Project BURRIAL TAK FOUNDATION Prep. By.: GSC
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC

DESIGN OF LONG WALL

Design Parameter
f'c 25 N/mm2
fs 420 N/mm2

Summary of Forces on long wall


Base slab short span moment
a) Vertical bending moment at base 1283.313 kNm / m 0.000 kNm / m 1283.313 kNm / m
b) Vertical bending moment at midhight 652.385 kNm / m 652.385 kNm / m
c) Shear Force 701.491 kN / m 701.491 kN / m
d) Horizontal bending moment at support 1350.235 kNm / m 1350.235 kNm / m
e) Horizontal bending moment at midspan 523.968 kNm / m 523.968 kNm / m
f) Shear Force 927.980 kN / m 763.402 kN / m
g) Axial compression due to short wall horizontal shear 382.082 kN / m 314.227 kN / m

Assuming the overall thickness of wall is ### mm

Clear Cover 60 mm

Bar Dia Assume 16 mm

Effective depth d = 250mm -60mm -16mm - 0.5 x16mm = 166 mm

Load factor for Strength Design = 1.6


Strength reduction factor for flexure.: 0.90
Strength reduction factor for shear.: 0.75
Strength reduction factor for tension.: 0.90

a ) Designing for Vertical bending moment at base 1283.31302 kN m

Factored max Vetical Moment 1.6 x 1283.31 kN m = 2053.296 kN m

Factor Rn 2053.3 x 10^6/ ( 0.9 x 1000 x 166 ^ 2 ) = 82.7928582 N/mm2

m = fy / (0.85 x f'c) = 420 / ( 0.85 x25 ) = 19.7647059 N/mm2

% Steel r = (1/ m)x(1-(1-(2xmxRn/fy))^0.5)

=(1 / 19.76) x ( 1-(1-(2 x 19.76 x 82.793/ 420))^0.5) = 0.14123

Ast = 0.1412 X 1000 mm X 166 mm = 23445 mm2

Min Steel required 0.15 %

0.15 x 1000 mmx 250 mm / 100 = 375 mm2

Provide max vertical steel area =MAX ( 23445 , 375 ) = 23445 mm2

Required 16 mm @ 8.576 c/c

Provide 16 mm @ 130 c/c = 1547 mm2 Not Ok

Corresponding r =( 3.14 x 16^ 2 / 4 x1000 /130 ) / ( 1000 x 166 ) = 0.00931705

b ) Designing for Vertical bending moment at midhight 652.385212 kN m

Factored max Vetical Moment 1.6 x 652.39 kN m = 1043.81634 kN m

Factor Rn 1043.82 x 10^6/ ( 0.9 x 1000 x 166 ^ 2 ) = 42.0886897 N/mm2

m = fy / (0.85 x f'c) = 420 / ( 0.85 x25 ) = 19.7647059 N/mm2

% Steel r = (1/ m)x(1-(1-(2xmxRn/fy))^0.5)

=(1 / 19.76) x ( 1-(1-(2 x 19.76 x 42.089/ 420)^0.5)) = 0.10070

Ast = 0.1007 X 1000 mm X 166 mm = 16716 mm2

Min Steel required 0.15 %

0.15 x 1000 mmx 250 mm / 100 = 375 mm2


Client ETCHO Job No.: ETCHO 01/2019
Project BURRIAL TAK FOUNDATION Prep. By.: GSC
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC

Provide max vertical steel area = 16716 mm2

Required 16 mm @ 12 c/c

Provide 16 mm @ 260 c/c = 773 mm2 Not Ok

Corresponding r =( 3.14 x 16^ 2 / 4 x1000 /260 ) / ( 1000 x 166 ) = 0.00465852

c ) Desining for vertical Shear Force at base of wall 701.490572 kN

Shear capacity of plain concrete =2 f (f'c)^0.5 *b*d

=2x 0.75x 39.37 x ( 166/25.4 ) x (25 x 145 psi ) ^ 0.5 /220 = 105.623942 kN / m

105.6239 < 701.49 Unsafe

d ) Designing for horizontal bending moment at side edge supports 1350.23545 kN m

Factored max Horizontal Moment 1.6 x 1350.24 kN m = 2160.384 kN m

Factor Rn 2160.38 x 10^6/ ( 0.9 x 1000 x 166 ^ 2 ) = 87.1108531 N/mm2

m = fy / (0.85 x f'c) = 420 / ( 0.85 x25 ) = 19.7647059 N/mm2

% Steel r = (1/ m)x(1-(1-(2xmxRn/fy))^0.5)

=(1 / 19.76) x ( 1-(1-(2 x 19.76 x 87.111/ 420)^0.5)) = 0.14487

Ast = 0.1449 X 1000 mm X 166 mm = 24049 mm2

Min Steel required 0.20 %

0.2 x 1000 mmx 250 mm / 100 = 500 mm2

Provide max steel area =max of (24049 , 500) 24049 mm2

Required 16 mm @ 8.361 c/c

Provide 16 mm @ 115 c/c 1748 mm2 Not Ok

Corresponding r =( 3.14 x 16^ 2 / 4 x1000 /115 ) / ( 1000 x 166 ) = 0.01053232

e ) Designing for horizontal bending moment at midspan 523.967829 kN m

Factored max Horizontal Moment 1.6 x 523.97 kN m = 838.352 kN m

Factor Rn 838.35 x 10^6/ (0.9x 1000 x 166 ^ 2 ) = 33.8039709 N/mm2

m = fy / (0.85 x f'c) = 420 / ( 0.85 x25 ) = 19.7647059 N/mm2

% Steel r = (1/ m)x(1-(1-(2xmxRn/fy))^0.5)

=(1 / 19.76) x ( 1-(1-(2 x 19.76 x 33.804/ 420)^0.5)) = 0.09025

Ast = 0.0902 X 1000 mm X 166 mm = 14981 mm2

Min Steel required 0.20 %

0.2 x 1000 mmx 250 mm / 100 = 500 mm2

Provide max steel area =max of (14981 + 500) 14981 mm2

Required 16 mm @ 13.42 c/c

Provide 16 mm @ 230 c/c 874 mm2 Not Ok

Corresponding r =( 3.14 x 16^ 2 / 4 x1000 /230 ) / ( 1000 x 166 ) = 0.00526616

f) Designing for Shear Force at side edge of wall 763.401748 kN

Shear capacity of plain concrete =2 f (f'c)^0.5 *b*d


Client ETCHO Job No.: ETCHO 01/2019
Project BURRIAL TAK FOUNDATION Prep. By.: GSC
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC

=2x 0.75x 39.37 x ( 166/25.4 ) x (25 x 145 psi ) ^ 0.5 /220 = 105.623942 kN / m

105.6239 < 763.40 Unsafe


Page.: of :
Date :
Date :

Design Basis
172-2-000-001 Rev-1
Cluase 14.2
Cluase 13.1.3

kNm / m
kNm / m
kN / m
kNm / m
kNm / m
kN / m
kN / m

Refer ACI-318R-02
Cluase 9.2.1
Cluase 9.3.2.
Cluase 9.3.2.
Cluase 9.3.2

Refer ACI-318R-02
Cluase 14.3.2

Not Ok

Refer ACI-318R-02
Cluase 14.3.2
Page.: of :
Date :
Date :

Not Ok

Refer ACI-318R-02
Cluase 14.3.3

Not Ok

Refer ACI-318R-02
Cluase 14.3.3

Not Ok
Page.: of :
Date :
Date :
Client ETCHO Job No.: ETCHO 01/2019 Page.:
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date :
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

DESIGN OF BASE SLAB


Design Basis
Design Parameter 172-2-000-001 Rev-1
f'c 25 N/mm2 Cluase 14.2
fs 420 N/mm2 Cluase 13.1.3
Summary of Forces on Base Slab
Long wall base moment
a) Support moment in short span direction 0.000 kNm / m ### kNm / m ### kNm / m
b) Midspan moment in short span direction 184.465 kNm / m 184.465 kNm / m
c) Shear Force for short span direction #REF! kN / m Short wall base moment #REF! kN / m
d) Support moment in long span direction #REF! kNm / m #REF! kNm / m #REF! kNm / m
e) Midspan moment in long span direction #REF! kNm / m #REF! kNm / m
f) Shear Force for long span direction #REF! kN / m #REF! kN / m
g) Axial Comp. due to long wall in short span direction 701.491 kN / m 701.491 kN / m
h) Axial Comp. due to short wall in long span direction #REF! kN / m #REF! kN / m

Assuming the overall thickness of wall is 300 mm

Clear Cover 60 mm

Bar Dia Assume 16 mm

Effective depth d = 300mm -60mm -16mm - 0.5 x16mm = ### mm


Refer ACI-318R-02
Load factor for Strength Design = 1.6 Cluase 9.2.1
Strength reduction factor for flexure.: 0.90 Cluase 9.3.2.
Strength reduction factor for shear.: 0.75 Cluase 9.3.2.
Strength reduction factor for tension.: 0.90 Cluase 9.3.2

a ) Designing for support moment in short span direction 1283.31 kN m

Factored max Vetical Moment 1.6 x 1283.31 kN m = 2053.3 kN m

Factor Rn 2053.3 x 10^6/ ( 0.9 x 1000 x 216 ^ 2 ) = 48.8992 N/mm2

m = fy / (0.85 x f'c) = 420 / ( 0.85 x25 ) = 19.7647 N/mm2

% Steel r = (1/ m)x(1-(1-(2xmxRn/fy))^0.5)

=(1 / 19.76) x ( 1-(1-(2 x 19.76 x 48.899/ 420))^0.5) = #NUM!

Ast = ### = #NUM! mm2


Refer ACI-318R-02
Min Steel required 0.18 % Cluase 7.12.2.1

0.18 x 1000 mmx 216 mm / 100 = 389 mm2

Provide max steel area #NUM! = #NUM! mm2

Required 16 mm @ ### c/c

Provide 16 mm @ ### c/c = 1547 mm2 ###

Corresponding r =( 3.14 x 16^ 2 / 4 x1000 /130 ) / ( 1000 x 216 ) = 0.00716

b ) Designing for midspan moment in short span direction 184.465 kN m

Factored max Vetical Moment 1.6 x 184.47 kN m = 295.145 kN m

Factor Rn 295.14 x 10^6/ ( 0.9 x 1000 x 216 ^ 2 ) = 7.02886 N/mm2

m = fy / (0.85 x f'c) = 420 / ( 0.85 x25 ) = 19.7647 N/mm2

% Steel r = (1/ m)x(1-(1-(2xmxRn/fy))^0.5)

=(1 / 19.76) x ( 1-(1-(2 x 19.76 x 7.029/ 420))^0.5) = 0.02116

Ast = 0.0212 X 1000 mm X 216 mm = 4571 mm2


Refer ACI-318R-02
Min Steel required 0.18 % Cluase 7.12.2.1

0.18 x 1000 mmx 216 mm / 100 = 388.8 mm2


Client ETCHO Job No.: ETCHO 01/2019 Page.:
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date :
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

Provide max steel area =Max ( 4571 , 389 ) = 4571 mm2

Required 16 mm @ 44 c/c

Provide 16 mm @ ### c/c = 838 mm2 Not Ok

Corresponding r =( 3.14 x 16^ 2 / 4 x1000 /240 ) / ( 1000 x 216 ) = 0.00388

c ) Desining for Shear Force in short span direction #REF! kN

Shear capacity of plain concrete =2 f (f'c)^0.5 *b*d

=2x 0.9x 39.37 x ( 216/25.4 ) x (25 x 145 psi ) ^ 0.5 /220 = 164.926 kN / m

164.926058 ### #REF! ###

d ) Designing for support moment in long span direction #REF! kN m

Factored max Vetical Moment #REF! = #REF! kN m

Factor Rn ### = #REF! N/mm2

m = fy / (0.85 x f'c) = 420 / ( 0.85 x25 ) = 19.7647 N/mm2

% Steel r = (1/ m)x(1-(1-(2xmxRn/fy))^0.5)

### = #REF!

Ast = ### = #REF! mm2


Refer ACI-318R-02
Min Steel required 0.18 % Cluase 7.12.2.1

0.18 x 1000 mmx 216 mm / 100 = 388.8 mm2

Provide max steel area #REF! #REF! mm2

Required 16 mm @ ### c/c

Provide 16 mm @ ### c/c 773 mm2 ###

Corresponding r =( 3.14 x 16^ 2 / 4 x1000 /260 ) / ( 1000 x 216 ) = 0.00358

e ) Designing for midspan moment in long span direction #REF! kN m

Factored max Vetical Moment #REF! = #REF! kN m

Factor Rn ### = #REF! N/mm2

m = fy / (0.85 x f'c) = 420 / ( 0.85 x25 ) = 19.7647 N/mm2

% Steel r = (1/ m)x(1-(1-(2xmxRn/fy))^0.5)

### = #REF!

Ast = ### = #REF! mm2


Refer ACI-318R-02
Min Steel required 0.18 % Cluase 7.12.2.1

0.18 x 1000 mmx 216 mm / 100 = 388.8 mm2

Provide max vertical steel area #REF! #REF! mm2

Required 16 mm @ ### c/c

Provide 16 mm @ ### c/c 773 mm2 ###

Corresponding r =( 3.14 x 16^ 2 / 4 x1000 /260 ) / ( 1000 x 216 ) = 0.00358

f) Desining for Shear Force in short span direction #REF! kN

Shear capacity of plain concrete =2 f (f'c)^0.5 *b*d


Client ETCHO Job No.: ETCHO 01/2019 Page.:
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date :
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

=2x 0.9x 39.37 x ( 216/25.4 ) x (25 x 145 psi ) ^ 0.5 /220 = 164.926 kN / m

164.926058 ### #REF! ###

g) Check for settlement of base slab:

Settlement = qo *B'(1-MU2)/Es*m*Is*If

158.19
of :

Design Basis
172-2-000-001 Rev-1
Cluase 14.2
Cluase 13.1.3

Refer ACI-318R-02
Cluase 9.2.1
Cluase 9.3.2.
Cluase 9.3.2.
Cluase 9.3.2

Refer ACI-318R-02
Cluase 7.12.2.1

Refer ACI-318R-02
Cluase 7.12.2.1
of :

Refer ACI-318R-02
Cluase 7.12.2.1

Refer ACI-318R-02
Cluase 7.12.2.1
Client ETCHO Job No.: ETCHO 01/2019 Page.:
Project BURRIAL TAK FOUNDATION Prep. By.: GSC Date :
Subject DESIGN OF BURIAL TANK FOUNDATION Ck'd. by.: GSC Date :

DESIGN OF PEDESTAL
Design Basis
Design Parameter 172-2-000-001 Rev-1
f'c 25 N/nm2 Cluase 14.2
fs 420 N/mm2 Cluase 13.1.3

Check for Pedestal as Column:l


Height of pedestal above Pit base slab 0.85 m
Least lateral dimension of pdestal 0.50 m
Since height of pdestal is < 3 x least lateral dim , it shall be traeted as pedestal and minimum reinf
of 0.15 % shall be provided

Ast = 0.15 X 3000mm X 500 mm / 100 = 7500 mm2

Required 16 mm - 37.3 bars

Provide 16 mm - 40 bars = 8042 mm2 Ok

Provide Link bars


10 @ 150 mm c/c
of :

Design Basis
172-2-000-001 Rev-1
Cluase 14.2
Cluase 13.1.3
Tensile Stress referance 350/350R-342
Severe Normal
Bor No Bar Size
Geade 40 Grade 50 Grade 60 Geade 40 Grade 50 Grade 60
3 10 20000 20000 22000 20000 20000 24000
4 12 20000 20000 22000 20000 20000 24000
5 16 20000 20000 22000 20000 20000 24000
6 18 18000 18000 18000 20000 20000 22000
6 20 18000 18000 18000 20000 20000 22000
7 22 18000 18000 18000 20000 20000 22000
8 25 18000 18000 18000 20000 20000 22000
9 28 17000 17000 17000 20000 20000 21000
10 32 17000 17000 17000 20000 20000 21000
11 36 17000 17000 17000 20000 20000 21000
End Moments Mid Moments Shear
la / lb
-Ca -Cb +Ca +Cb Wa Wb
0.5 0.086 0.006 0.037 0.002 0.940 0.060
0.55 0.084 0.007 0.035 0.003 0.920 0.080
0.6 0.081 0.010 0.034 0.004 0.890 0.110
0.65 0.077 0.014 0.032 0.006 0.850 0.150
0.7 0.074 0.017 0.030 0.007 0.810 0.190
0.75 0.069 0.022 0.028 0.009 0.760 0.240
0.8 0.065 0.027 0.026 0.011 0.710 0.290
0.85 0.060 0.031 0.024 0.012 0.660 0.340
0.9 0.055 0.037 0.022 0.014 0.600 0.400
0.95 0.050 0.041 0.020 0.016 0.550 0.450
1 0.045 0.045 0.018 0.018 0.500 0.500
Mx
a/b y/b Ra x/a 0 0.2 0.4 0.6 0.8 1
0.125 1 0.0052 0.0024 0.002 -0.0014 -0.0024 -0.0027
0.125 0.8 0.0051 0.0023 0.002 -0.0014 -0.0023 -0.0026
0.125 0.6 0.0052 0.0023 0.002 -0.0014 -0.0023 -0.0027
0.125 0.4 0.0051 0.0023 0.001 -0.0014 -0.0023 -0.0027
0.125 0.2 0.0048 0.0021 0.001 -0.0013 -0.0021 -0.0024
0.125 0 0 0.001 0.0003 0.0005 0.0006 0.0007
0.25 1
0.25 0.8
0.25 0.6
0.25 0.4
0.25 0.2
0.25 0

You might also like