Professional Documents
Culture Documents
2. The no-load equivalent circuit of a 1-ph transformer as shown between terminal 1 and 2.
Its power factor is _____________ lag.
3. A 4 kVA, 400/200 V, 1-phase transformer has leakage impedance of 0.02 + j0.04 per unit.
This leakage impedance in ohms, when referred to hv side is x + jy the value of x is ________.
4. Magnetic flux densities for HR steel laminations and CRGO are 1.2 T and 1.6 T respectively
then ratio of weight of CRGO laminations and hot rolled laminations is _______________ .
(Assuming same densities for two type of core material and total flux remains the same.)
6. A 500 kVA transformer has 95% efficiency at full load and also at 60% of full load both at
unity p.f. Sum of iron loss and copper loss at full load is _____________ kW.
7. A 3-phase transformer has it primary connected in delta and secondary in star. It has an
equivalent resistance of 1% and equivalent reactance of 6%. The primary applied voltage is
6600 V. ______________ be the ratio of transformation in order that it will deliver 4800 V at full
load current and 0.8 power factor lag.
9. A 500 kVA, 11 kV/0.43 kV, 3-phase delta/star connected transformer has HV copper loss of
2.5 kW and LV copper loss of 2kW on rated load. The ohmic value of the equivalent
resistance on the delta side is ____________ /ph.
10. A 500 kVA transformer has 95% efficiency at full load and also at 60% of full load both at
unity p.f. Transformer efficiency at 75% full load and unity power factor is ____________ %.
11. A 20 kVA, single phase transformer has iron loss of 250 W and full load Cu-loss of 500 W
respectively. The value of maximum efficiency at unity power factor will be equal to
12. A 100 MVA, 230/115 kV - 3- power transformer has a per unit resistance of 0.02 pu
and a per unit reactance of 0.055 pu. The transformer supplies a load of 80 MVA at 0.85 PF
lagging. What is the percentage voltage regulation of the transformer?
13. Two transformers with leakage impedance Z1 = 0.1+j0.4, and Z2 = 0.05+j0.2 are
S
connected in parallel. The ratio of load shared 1 will
S
2
14. A voltage V=200sin314t is applied to the transformer winding in a no load test. The
resulting current is found to be i 3sin 314t 60o . Find the core loss and rms value of the
exciting current.
15. The series equivalent impedance of a single phase transformer referred to its secondary
side is Z a2 R a2 jX a2 . The voltage regulation of this transformer will be zero when the
power factor if load is
Xa2
(a) Unit (b) leading
Za2
Xa2 Ra2
(c) lagging (d) leading
Za2 Za2
16. If a three phase step down transformer is connected to 6600 V mains and takes 10A,
then the secondary line voltage and line current for Y/ connection respectively are (Three
ratio of turns per phase 12 and neglect losses).
(a) 28
(b) 30
(c) 30
(d) 28
18. Turns ratio = 1 for transformer 1 & 1.1 for transformer 2. (Voltages and current at the
same frequency) With I = 0, it is given that I1 = I2 = 10o A. When I = 5A, Ip = _____________A.
19. A 3-winding, 50Hz single-phase transformer has primary, secondary and tertiary turns
equal to 100, 50 and 40 respectively. Resistances, leakage reactances, and core losses are
neglected. Rated primary voltage is 400V and at that voltage, the primary draws a
magnetizing current of 1A. If the secondary delivers a load current of 4-j4 A. The value of
the capacitance to be connected to the tertiary to improve the primary power factor to unity
is _______________F.
(a) 149.4
(b) 23.9
(c) Capacitance has to be connected at the primary terminals only
(d) 934
20. For considering the effects of lighting surges, the hv winding of a single-phase
transformer is represented by the following circuit. (C1 is the inter coil capacitance and C2 is
the coil to earth capacitance) At an instant when the surge voltage across 1 and 2 is Vs ;V1
and V2 are, respectively.
V V
(a) s , s
2 2
C1 C2
(b) Vs , Vs
C1 C2 C1 C2
C2 C1
(c) Vs , Vs
C1 C2 C1 V2
C1 C2 C1
(d) Vs , Vs
2C1 C2 2C1 C2
21. A transformer has 2% resistance and 5% reactance, find its voltage regulation at full load
0.8 power factor lagging.
22. An auto transformer supplies a load of 5 kW at 115 V and at unity power factor. If the
primary voltage is 230 V, determine power conducted directly from the supply mains to the
load
23. Three single-phase transformers are connected to form a 3-φ transformer bank. The
transformer are connected in the following manner.
24. If 110% of normal voltage and 110% of normal frequency is applied to a transformer, the
percentage change in eddy current losses is _________.
25. Two transformers are to be operated in parallel such that they share load in proportion
to their KVA ratings. The rating of the first transformer is 500 KVA and its pu leakage
impedance is 0.05 pu. If the rating of second transformer is 250 KVA, its pu leakage
impedance (for the common base values of 500 MVA) is ____________.
26. A 3-φ transformer has its primary connected in delta and secondary in star. Secondary to
primary turns ratio per phase is k. If the ratio of secondary to primary line voltage is k 1, then
k1 = xk, the value of x is _______________.
27. A single-phase 3300/400 V transformer has the following winding resistances and
reactance’s: R1=0.7Ω, R2=0.011Ω, X1=3.6Ω, X2=0.045Ω the secondary is connected to a coil
having a resistance of 4.5Ω and inductive reactance 3.2Ω. Calculate the secondary terminal
voltage.
28. A 500 KVA, 33/3.3 kV 1-φ transformer with a resistance voltage drop of 1.5% and a
reactance voltage drop of 6% is connected in parallel with a 1000 KVA, 33/3.3 kV single
phase transformer with a resistance voltage drop 1% and a reactance voltage drop of 6.2%.
Find the KVA loading and operating power factor of each transformer when the load is 1200
KVA at power factor 0.8 lagging.
29. A 3-φ, 50 Hz transformer has an iron cross section of 400 cm2 (gross). If the flux density
be limited to 1.2 Wb/m2, Find the sum of number of turns per phase on high and low voltage
windings. The voltage ratio is 2200/110 V, the high voltage side being connected in star and
low voltage in mesh. Assume stacking factor to be 0.9
30. Two transformers each rated 250 kVA, 11/2 kV and 50 Hz are connected in open delta on
both the primary and secondary. A delta connected three phase load of 250 kVA, 0.8 pf, 2 kV
is connected to the low voltage terminals of this open delta transformer. __________ A is the
transformer currents on the 11 kV side of this connection.
31. The full load voltage drops in single phase transformer are 14% and 2% due respectively
to resistance and leakage reactance. The full load ohmic losses double to the iron losses. The
efficiency on full load at 0.8 lag p.f. is ___________________%.
32. A transformer has a reactance drop of 5% and a resistance drop of 2.5%. Find the
maximum voltage regulation
33. The maximum efficiency of a 500 kVA, 3300/500 V, 50 Hz, single phase transformer is
97% and occurs at 3/4 full load, unity power factor. If the impedance is 10%, calculate the
regulation at full load at 0.8 p.f. lagging?
34. A 25 kVA, 1-φ transformer, 2200 V to 220 V has a primary resistance of 10 Ω and a
secondary resistance of 0.01 Ω. Find the full load efficiency at 0.8 p.f. if the iron loss of the
transformer is 80% of the full load copper loss.
35. An iron ring of mean length 50 cm has an air gap of 1 mm and a winding of 200 turns. If
the permeability of the iron is 300 when a current of 1 A flows through the coil, find the flux
density.
36. Turns ratio = 1 for transformer 1 & 1.1 for transformer 2. (Voltages and current at the
same frequency)
With I = 0, it is given that I1 = I2 = 10o A
When I = 5A,Find the phase angle of Ip?
37. The primary winding on the central limb has 100 turns. The maximum flux through any
limb is to be 1 milli Wb, the flux varying sinusoidally with time. Rms value of the
magnetizing current is _______________ A.
(a) 1.77 (b) 2.77
(c) 1.95 (d) 2.99
38. An ac source Vs = 100o V having an internal impedance of 1k is applied to the primary
of a single-phase transformer. If the secondary is connected to a purely resistive load of
10, then the maximum power dissipated in the load will be
39. Three single phase transformers are connected as shown . V ____________ volts.
(b) V0o
(c) V180o
40. An ideal audio frequency transformer couples a 60 ohm resistive load to an electronic
circuit which is represented by a constant voltage source of 5V in series with an internal
resistance of 3000. Find the transformer turns ratio so that maximum power transfer takes
place from source to the load.
2
(a) 1 (b)
10
(c) 2 (d) 50
41. The regulation curve of a 1- transformer is shown below. Which point represents the
regulation of a lightly capacitive load.
(a) X
(b) Y
(c) Z
42. An auto transformer has a coil with total number of turns NDC = 200 between terminal C
& D. It has got one tapping at A such that NAC = 80 and another tapping at B such that
NBA = 40. The current in the section BD when 400V supply is connected across AC and two
resistive loads of 60 and 40 are connected across BC and DC respectively is
(a) 20 A
(b) 23 A
(c) 25 A
(d) 27 A
43. Two single-phase transformers operating in parallel have the following data:
Transformer A : Zea = 0.2 + j0.6, Ea = 208 V
Transformer B : Zeb = 0.25 + j0.55, Eb = 205 V
Load impedance Z = 3 + j2
The load current and voltage across the load are respectively.
44. A 50 Hz 3-phase core type star-delta transformer has a line voltage ratio of 11,000/440
volts. The cross-section of the core is square with a circumscribing circle of 0.4 m diameter.
Find the number of turns per phase on high-voltage windings for a maximum flux density of
1.20 Wb/m2. Assume that the insulation occupies 10% of the total core area.
45. A 220/115 V, 25 Hz single phase transformer has eddy current loss of 100W, which is half
of the no-load loss at rated applied voltage. If the transformer is used with primary 50 Hz,
440V, the total no-load loss would be
46. A 500 kVA transformer has an efficiency of 95% at full load and also at 60% of full load;
both at upf then which of the following is true?
48. A three phase transformer can be built as a single unit or as a bank of three single-phase
units. From the view point of
49. A transformer has circular turns on a core of approximately circular cross-section. The
magnetic field can be assumed to be along the axis of the turns. The force experience by a
turn is
50. Secondary’s of three similar single-phase transformers are shown in figure. These are
connected in delta by joining terminals 2 to 3; 4 to 5; and 6 to 1. The voltage observed
across terminals 1 and 2 (in volts) is
(a)(20sint + 30sin3t)
(a) 90sin3t
(b) 200 sint
(c) 30 sin3t
51. The open – circuit test data on the low voltage side of a single phase transformer is as
follows:
(a)200, 200
53. When compared with air (1.0), modern electric steels have permeability’s in the order of
56. Two transformers operating in parallel having impedances of 3% and 5%. If the total
load supplied by the combinations is 100A, then the current supplied by each is
57. If the OC test data on delta side of a three phase star-Delta transformer is 33kV, 5.5A,
21kW, the magnetizing component of current will be ______________A.
58. Which of the following three phase transformer gives more output voltage?
59. The amount of flux linkage of a coil having 100 turns and in a time varying flux of 1.2 Wb
is ____________ Wb-turns.
61. A two winding three phase transformer has delta connected primary and star connected
secondary. The phase shift produced by the above combination will be
62. The no-load voltage of a transformer is 440V and its load current is 10A. If the
equivalent resistance, reactance’s are 0.12 and 2.42 and is operating at a power factor of
0.8 lag, then the voltage regulation of transformer is _______________ %.
(a)Small transformers
(a) Medium transformers
(b) Large transformers
(c) None of these
64. Which of the following parallel operation of transformers leads to circulating currents?
65. A 220/110 V transformer has an iron loss of 450W when excited from high voltage side
under no load condition. If the no load current is 5A, then the no load power factor is
_________________.
66. A 220/2200V transformer having 100/1000 turns on primary and secondary is connected
as auto transformer with additive polarity. The low voltage and high voltage of auto
transformer are
67. A 100 kVA transformer has resistance of 0.5% and its maximum efficiency occurring at 50
kVA load. The efficiency at full load and 0.8 pf is ____________ %.
68. A 50Hz, 250 kVA, 6600/600V 1-phase transformer has maximum efficiency of 96% occurs
at 70% full-load unity p.f. The percentage regulation at full load 0.8 p.f lagging when the
impedance is 15% is __________________.
69. A transformer has it maximum efficiency of 0.97 at 10 kVA, U.P.F. The loading during the
day is:
71. In a three phase / Y transformer shown in the figure, the phase displacement of
secondary line voltages with corresponding primary line voltages will be
(a) 15o
(d) 180o
72. The primary winding of a single phase transformer having 200 turns is excited with a
voltage V(t) = 15.5 sin120t + 15.5 sin 360t V. Neglecting the leakage, the rms value of flux
is _____________ mWb.
73. For determination of losses a transformer having 400V, 50Hz the total iron losses were
found to be 2000W at normal V&F. The iron losses were found to be 750W when the
applied voltage and frequency were 200V, 25 Hz. The hysteresis loss (in kW) at normal
voltage and frequency will be _____________.
74. A single phase transformer has 500 primary turns & 1000 secondary turns. Area of cross-
section of core is 80 cm2. If primary applied voltage is 1000V, maximum flux density in
wb/m2 will be ______________________.
75. An impedance Zo=(1+j4) is connected in series with the secondary winding of an ideal
transformer as shown in the figure.
Solutions
1. Ans: 0.80 to 0.82
1/2
Solution: I0 rms 0.8 0.2 0.8246 0.82
2 2
2. Ans: 20.8
Solution: Consider the circuit and corresponding phasor diagram
2 2
V V 5V
I
3 4 12
Shown from the phasor diagram
v
3 12
cos 0.8
5V 15
12
R
Current lagging the voltage power factor is not here
R X
2 2
3. Ans: 0.8
400 400 400
Solution: Base Impedance = 40
4000 4000
400
Leakage impedance referred to hv side= (0.02 + j 0.04) 40= 0.8 + j1.6
4. Ans: 0.75
1
Solution: Weight of laminations
Bm
WCRGO
B
m HR
1.2
0.75
WHR Laminations B
m CRGO
1.6
6. Ans: 26 to 27
500
Solution: 0.95
500 Pi PcuFL
500
500 Pi PcuFL =26.315 ................ (i)
0.95
500 0.6
0.95
500 0.6 Pi 0.36PcuFL
500
500 0.6 Pi 0.36Pcu
0.95
Pi 0.36Pcu 15.79 ...... (ii)
Solving equations (i) and (ii)
Pcu 16.45 kW
Pi 9.87 kW
Hence Pcu+Pi 16.45 +9.87 = 26.32kW
8. Ans: (d)
Solution: Supply voltage V1 = 250 V
Primary turns N1 = 1250
Secondary turns N2 = 800
N 800
Secondary voltage v 2 V 2 250 160 V
N1 1250
500
I
phase
3 11
15.2 A
2500
R 1.85 103
3 671.34
LV ph 2
2500
R 3.6
3 15.2
HV ph 2
500
500 0.6 Pi 0.36Pcu
0.95
Pi 0.36Pcu 15.79 ...... (ii)
Solving equations (i) and (ii)
Pcu 16.45 kW
Pi 9.87 kW
kVA cos
kVA cos Pi Pcu
500 0.75
100 95.15%
500 0.75 9.87 16.45 0.75
2
In doing this, the turns ratios, given location of dots, and chosen reference directions for the
currents.
In figure Ip by KCL
Ip 10 5 30o 10 5.5 30o 20 0.5 30o A
Ip2 22 0.52 2 2 0.5 cos30 4.25 3
Ip 1.59
Note: In a transformer, for Ampere-turn balance, if the following rule is applicable. “If one
current leaves its winding at dot, and the other current enters its winding at dot, the two
current must be in phase”. Whether current enter their windings at dots or leave their
windings at dots is decided by our arbitrarily chosen reference directions.
24. Ans: 21
Solution: Eddy current losses We B2f 2
V
B
f
V2 2
We f V2
f 2
V2 1.1V1
We We V22 V12
Percentage Change in Eddy Current Losses, 2 1
100 100
We V12
1
1.1V V
2 2
1 1
100 21%
V12
25. Ans: 0.10
Solution: Since Load must be shared proportional to KVA Ratings
S1 Z 2 KVA1 500
S2 Z1 KVA2 250
Since, both are to be measured on common base
Z 2 Z 2 pu
2
Z1 Z1 pu
Z2 pu 2 Z1 pu 2 0.05 0.10pu
Solution:
V Line Y
k1 =>
3Vph Y
k1
V Line
Vph
3.
V
ph Y
3.
N
ph Y
3 . k = k1
V
ph N
ph
x 3 1.732
Z
A pu
0.015 j0.06 0.0618575.96o
R
B pu
0.01 ; X B pu
0.062
Z
B pu
0.062880.84o
*
ZB 0.0628 80.84o
S A LS 120036.87o
Z A ZB 0.06185 75.96 0.0628 80.84
o o
SA 605.1234.44 KVA
SB SL SA 120036.87o 605.1234.44o KVA
SB 595.9739.34o KVA
2200
HV side phase voltage, EP1 1270 V
3
LV side phase voltage, EP2 110V
Turns per phase on low voltage windings.
EP2 110
N2 11.47 12
4.44max f 4.44 0.0432 50
Turns per phase on high voltage winding.
E 12 1270
N1 N2 P1 138
EP2 110
sum 12 138 150
30. Ans: 13 to 14
Solution: The KVA load that can be supplied by two transformer, each having rating of 250
kVA = 2 kVA rating of each transformer 0.866 = 433 kVA
VA output 250 1000
secondary line current, I 72.16 A
3V 3 2000
Secondary phase current = Secondary line current = 72.16 A
Primary phase current (current on hv side)
2
= Secondary phase current transformation ratio 72 13.12 A
11
In doing this, the turns ratios, given location of dots, and chosen reference directions for the
currents.
In figure Ip by KCL
Ip 10 5 30o 10 5.5 30o 20 0.5 30o A 1.589.060
9.2
Note: This circuit is call balance 3-phase to 2-phase conversion circuit. Its advantage is that
a standard 3-phase transformer core can be used.
2
f
W e f We2 We1 2 100 4 400W
2
f1
Total no-load loss= Wh2 We2 600 W
0.95
By solving
Wi 9868.4 W; Wcu 16447.3 W
47. Ans: 6
Solution: By inspection, we see that both currents shown in the figure enter their respective
windings at dots. So, for ampere turn balance, Ib N / 3N18 30 6150o A
From the RH rule, the magnetic field will be in the direction shown. The forces on the two
diametrically opposite current elements will be as shown in fig 1, by Lorentz’s force law.
When the current is negative, figure 2 shows the currents, field and forces. Again we see that
the force is circumferential, tending to increase the radius.
It is seen that the current in the delta-loop is 30sin3t A; flowing from terminal 1 to 6
through the resistances.
68. Ans: 11 to 12
Solution: 70% load at unity p.f. 0.7 250 175 kW
max 96%; losses = 4%
175
Input Power = kW
96
175
Total losses 4 7.29 kW
96
At max , Wcu Wi
7.29
At 70% load, Wcu 3.64 kW Wi
2
%z 15%
2 2 10
2
15
2
Total Copper Loss = 0.15 12 8 4 2.622kWhr
10 10 10
output energy 164
Efficiency = 100% 100% 96.34%
output energy losses 164 3.6 2.622
For capacitive loads, load component of primary flux is little bit less than the load flux so net
flux of the transformer is decreases slightly due to demagnetization effect.
We know that core losses are directly proportional to the maximum value of flux density, so
core losses may increase or decrease depending on nature of the load.
73. Ans: 1
Solution: Wh f Wh Af
We f 2 => We Bf 2
Total iron losses, Wi Af Bf 2
Wi
A Bf
f
At f = 50 Hz
Wi 2000 W
2000
A B(50) (1)
50
At f = 25 Hz
Wi 750 W
750
A B(25) (2)
25
From (1) and (2)
B 0.4
We Bf 2 (0.4)(50)2 1000 W
Hystersis loss = 2000-1000=1000 W
We recommend you to take the Chapter Test first and then check
the Solutions.
1. Ans: (a)
276.5
Solution: Active area of cross-section 0.02765 / 1.2m2 cm2
1.2
276.5
So gross cross-section = 256 cm2
1.2 0.9
For a square cross-section, each side = 16 cm
2. Ans: (c)
Solution: Two winding must be connected in series with the proper so that 600 V can be
applied across the total windings.
With 20 kVA load, load current.
20 1000
I2 100A
200
20 1000
I1 33.33A
600
current in common winding = (100 - 33.33) A=66.67 A
VA rating of second winding 20k
KVA rating = 30k
1 K 200
1
600
3. Ans: (b)
100
Solution: IS(base) 502 A
3 115
Since the transformer supplies a load of 80 MVA at 0.85 pf lagging, so secondary line current
of the transformer is
80
IS 402 A
3 115
402
I
S pu
502
cos1 0.85 0.8 31.8o
4. Ans: (d)
Solution: Under Short Circuit Test rated current flows through the windings
5000
ISC 11.36 A
440
2
2
VSC ISC Zeq 11.36 0.5 2 0.2 11.36 0.5 2 0.2 j 0.6 2 0.15
2
VSC 11.36 1.3 j1.2 11.36 1.7742.70 20.1042.70 V
o o
5. Ans: (a)
Total load in kVA 1000 400 1000
Solution: Secondary line current, I= 525 A
3 line voltage 3 440
V I 440 525
kVA supplied by each transformer = 231 kVA
1000 1000
for a pf of 0.866 lag, =30o
So power delivered by one transformer,
P1 = kVA cos(30o ) = 231 cos 0o = 231 kW
And power delivered by the other transformer
P2 = kVA cos(30o + ) = 231 cos60o = 115.5 kW
6. Ans: (d)
V 400 V 200
Solution: 1 8 and 2 8
f1 50 f2 25
V1 V2
8
f1 f2
the flux density Bm remains constant
Pi
Hence, u vf
f
2400 800
u 50v and u 25v
50 25
Solving these equations, we get
u=16; v=0.64
Therefore, at 50Hz
Ph uf 16 50 800 W
Pe vf 2 0.64 50 1600W
2
7. Ans: (a)
500 36.86 2.5 j5
Solution: I1 304.516 34.068o A
4.5 j8
500 36.86 2 j3
I2 196.426 41.19o A
4.5 j8
304.5 400
(kVA) supplied by transformer-I 121.8 kVA
1000
196.426 400
(kVA) supplied by transformer-II= 78.57 kVA
1000
8. Ans: (d)
Solution: 10 kVA, 2500/250 V
OV 250V 0.8A, 50W
SC 60V 3A, 45W
Iron losses = 50 W = W1
10000
I( 4V ) 4A (rated current)
2500
Cu loss at 3A = 45 W
Cu loss at 4A = ?
2
4 16
45 45 80W
3 9
Iron loss 50
KVA at max kVAFL 10KVA 7.9 kVA
Cu loss 80
9. Ans: (a)
Solution: For conducting a heat run test economically, the transformer should have the
rated voltage core loss 30W; and the rated copper loss 40W; at the same time, without
actually loading the transformer. In a short-circuit test, a reduced voltage is applied, so core
are very small. So, the voltage should be increased to a value where the short-circuit current
is greater than the rated value, and the copper losses equal rated voltage core loss + full
load copper loss. (We are assuming that frequency is the rated value.)
Full load copper loss = I2fr req = 40 W
We want a current I where copper loss = I2req = 40 + 30 = 70 W.
I 70
1.32
Ifc 40
The short circuit current should be 132% of the rated value.
l
Reluctance =
A
0.5 106
We have R AB R CD REF AT/Wb
5000 8
4 107 20 10 4
0.25 106
R CA R CE RFD RFD AT/Wb
5000 16
4 10 20 10
7 4
We can now redraw the circuit as shown:
ouput 4
Full-load losses = output 4 4.21 4 0.21 kW
Efficiency 0.95
Efficiency of autotransformer at rated load and 0.8 p.f. lagging
output 25 0.8
100 100 98.96%
output losses 25 0.8 0.21
iron losses
kVA rating of x'mer at max efficiency condition= nominal kVA rating
full load copper losses
Wi
50 100 Wi 125 W
500
Total Loss 500 125 625 W