FIRE ALARM AND DETECTION SYSTEM INSTALLATION INSPECTION CHECK LIST.
Date o f Insfection Location: Month: October
FACTORY INFORMATION
Factory Name: Premier 1888 Ltd.
Address: Plot # 17-19, 36-38, Sector # 02, Chittagong, Bangladesh.
Representative Name: Engr. Md. Saidul Islam
Designation: (Manager-Electrical)
Phone: +88-01672745573 Fax: N/A
E-mail: N/A

INSTALLATION, SERVICE AND TESTING CONTRACTOR INFORMATION


Contractor Name: Design Consultancy & Services (DCS)
Address: 581/A,Mehedibag (Beside of National Hospital) Panchlaish, Chattogram, Bangladesh.

Inspector or Tester Name: Minhazul Islam


Qualification of Inspector or Tester: B.Sc in EEE
Phone: 01844071034 Fax: _______________
E-mail:_minhazul.dcs04@gmail.com
MANUFACTURER INFORMATION
System Manufacturer: _COOPER______________________________________________
Country of Origin: _UK_____________________________________
Address: UK
Local Agent (If any): _N/A_______________________________________________
Local Agent’s Address: ________________________________________________
Local Agent’s Representative Name: _________________________________________
Designation: _________________________________________________________
Phone: _________________ Fax: _______________
E-mail:______________________
SYSTEM INFORMATION
Type of System: Addressable
Repeater Panel (Specify Location): Panel Room GF
Number of Detectors: Smoke Detector: _168__
Heat Detector: ___16_________________
Beam Detector: _____N/A_______________
Multi Sensor Detector: N/A
Others (Specify): __________________________________________
Pull Station: _16__
Alarm Sounder (with) Flasher: __18_____________________________________
Others (Specify): ______________________________________________________
Battery- 24V Type: Led Acid
Nominal Voltage: 24V Amp/Hour Rating: 12Amh

INSPECTION CHECKLIST
General Information Comments
Sl. No Description Yes No Yes No
A copy of the Fire Alarm installation certificate and
Record of completion is properly filled out and available
1 from the installer. Yes

More than one contractor was responsible for


installation of the Fire Alarm System and each contractor
2 has filled out the Fire Alarm installation certificate and NO
Record of completion.

A copy of the as-built Fire Alarm System drawing signed


3 by a competent body is available on site. Yes
An Owner’s Manual, a copy of the Manufacturer’s
instruction, written sequence of operation are available
4 on site. Yes

For Addressable System a list of each device with the


corresponding location is provided. The device
5 addressing shall reflect actual room names or numbers Yes
that are current to the building use.

For Addressable System a copy of the specific software


6 with software revision number, software update date Yes
available on site.
Fire Alarm Control Panel (FACP)
The dedicated 220V ac branch circuit for the fire alarm
panel is labeled “Fire Alarm Circuit” on the panel
7 schedule of the electrical panel and the actual circuit Yes
breaker is colored RED as per NFPA72.

The dedicated 220V ac branch circuit shall be


mechanically protected (i.e. breaker lock) as per NFPA72.
8 Yes

Fire Alarm Control Panel is grounded properly by Earth


9 Continuity Conductor. (connection can be taken from Yes
electrical panel board’s earth bus-bar)
The location of the dedicated 220V ac branch circuit shall
10 be permanently marked inside the fire alarm control Yes
panel as per NFPA72.
A device location and zone map / Schematic Diagram
shall be provided at or beside the fire alarm control panel
and remote annunciator as per NFPA72. This Schematic
11 Diagram shall be approved by the competent body. Yes

12 Batteries are permanently marked with Month & Year of Yes


manufacture as per NFPA72.
Fire Alarm Control Panel and/or Remote Annunciator
receive the correct information when device has been
13 activated. (i.e. device location, device type, alarm type) Yes

Emergency Voice/Alarm Communication Comments


If available check the following Yes No N/A
14 Fire Alarm System is monitored by a
monitoring station. N/A
Primary communication line is tested and monitoring
15 station receives the proper information from the fire
alarm system. N/A
Secondary communication line is tested and monitoring
16 station receives the proper information from the fire
alarm system. N/A
Notification Devices Comments
Sl. No Description Yes No

Fire Alarm signaling devices sound


17 Yes
throughout the occupancy.

The minimum sound pressure level of


15dBA above the ambient noise level or 5dBA above a
maximum sound level lasting for at least 60 seconds,
18 whichever is greater as per NFPA72. Yes

The sound level of sleeping rooms (i.e.dormitory) is at


least 15dBA above
19 Yes
average ambient sound level or 75dBA
measured at the pillow, whichever is
greater as per NFPA72.
20 If sounder with flasher used, flasher is Yes
working properly or not.

Initiating Devices

All initiating devices have been tested as per


21 manufacturer instructions. Yes
22 All the initiating devices labeled properly. Yes
23 Smoke Detectors initiate alarm throughout the fire alarm Yes
panel.
24 Heat Detectors initiates alarm throughout the fire alarm Yes
panel.
25 Pull Stations initiate alarm throughout the fire alarm Yes
panel.
26 Duct Detectors shut down HVAC unit and send a N/A
supervisory signal to the fire alarm panel.
Are Smoke Detectors are installed instead of Duct
27 Detectors and shut down all HVAC units when detectors N/A
activate.
28 Clean Agent Suppression system initiates alarm N/A
throughout the fire alarm panel.
Sprinkler System Comments
Sl. No Description Yes No Yes No
29 Sprinkler flow switch initiates alarm through the fire N/A
alarm panel.
All control valves for the sprinkler system are monitored
30 and the movement of the valve initiates a trouble signal N/A
at the fire alarm panel.
31 Low air pressure for the sprinkler system sends a trouble N/A
signal to the fire alarm panel.
For sprinkler system with a pressure tank,the high and
32 low pressure of the tank sends a supervisory signal to the N/A
fire alarm panel.
Fire Pump
33 When the fire pump is running a Yes
supervisory signal is sent to the fire alarm panel.
34 When there is a loss of any phase at the line terminals of Yes
the motor contactor of the electric driven fire pump a
supervisory signal is sent to the fire alarm panel.
Phase reversal of the electric supply to the electric driven
35 fire pump shall send a supervisory signal is sent to the Yes
fire alarm panel.
36 Yes
Pump room temperature is controlled by exhaust fan.
Other Services Comments
Sl. No Description Yes No N/A
All the notification and initiating devices wiring by FP200/
37 Fire resistant cable as per standards and size as Yes
mentioned on the approved drawings.
Smoke Detector present at Fire Alarm
38 Control Panel room. Yes

39 Emergency Light with battery/IPS backup present at Fire Yes


Alarm Control Panel room.
40 Yes
IPS/UPS used as emergency backup of fire alarm panel.
Activation of fire alarm or spot smoke
41 detector release door hold open devices. Yes

42 Exit doors equipped with door unlocking devices unlock Yes


with activation of fire alarm system.
Activation of fire alarm or spot smoke
43 detector drops fire doors. Yes
Activation of fire alarm or spot smoke
44 detector activates smoke dampers. N/A
Activation of fire alarm or spot smoke
45 detector activates smoke control/ N/A
evacuation system.

Activation of the elevator lobby smoke detector activates


46 the elevator recall and initiates an alarm signal at the fire N/A
alarm panel.
Activation of smoke/heat detectors to
47 shutdown elevator shutdown is tested. N/A
Activation of fire alarm or spot smoke
48 detector shut down HVAC system. N/A

Wiring between fire alarm panel and


49 relays for the safety equipment (i.e. door hold- N/A
open/release, door unlocking, HVAC controls etc.) shall
be monitored for integrity.

……………………………….. …………………………………………
Inspector’s Signature Factory Owner’s Signature
Date: Date: