You are on page 1of 1

Insp. Ref.

#: _____________
[PROJECT NAME]
Inspection Checklist - Tiling (Floor & Wall)

Main Contractor (MC): PIC/Supervisor:


Sub-Contractor: PIC/Supervisor:
Resident Staff (RS): Unit #:

Inspection criteria (2) Pre & Post Screeding Post-Installation of Floor & Wall Tiles

Hollow, Holes at Joints


completed and tested.

Consistency of Colour

RS Re-Verification (3)
Gradient at Wet Area)

Gradient at Wet Area)

Positioning of Fixings

RS Accepted Works
Water Ponding Test
Free from Damage,
CWP Pressure test

Floor Flatness (2%

Floor Flatness (2%

MC Rectification (3)
MC Rectification (3)
RS Verification (3)

RS Verification (3)
Floor Level Pegs

Tile Setting Out

RS Approval to
Wall Alignment
Water proofing

proceed works
Remarks

Tones & Sizes


completed

Location (1)

1 Living, Dining N/A NA NA


2 Bedroom 4 N/A NA NA
3 Bathroom 4
NA
4 Kitchen N/A NA
5 Staircase N/A NA NA
6 Family Hall N/A NA NA
7 Master
N/A
Bedroom NA NA
8 Bathroom 1

9 Bedroom 2 N/A NA NA
10 Bathroom 2

11 Bedroom 3 N/A NA NA
12 Bathroom 3
13

Checked/Verified by: MC RS MC RS MC RS MC RS

Signature
&
Date

Tiling Quality KPI = Nos. of location accepted by RS after Re-Verification @ Post-Inst. / Total locations x 100% =

Notes:
(1) Change the location in this checklist according to the product layout. For high-rise project, to attach a copy of the layout.
(2) See below for acceptance tolerance. MC to mark 'a' in respective location only if workmanship is acceptable (NA if not applicable), then inform RS to verify.
Inspection stage Inspection criteria Acceptance tolerance Tools used
Pre-Screeding Floor level pegs 1 along the wall, intermediate at < 1600mm interval Measuring
Wall alignment (base plaster) 3mm / 1.2m for verticality, horizontality & squareness tape
Cross line
Water ponding testing completed 24hrs Water ponding test passed before proceed with floor screeding. laser
Visual
Post Screeding Floor flatness (2% gradient at wet area) 3mm / 1.2m for flatness Spirit level

Tiles setting out At every 1 to 3 columns & rows Cross line


Post Installation of Floor & Wall Floor flatness (2% gradient at wet area) 3mm / 1.2m for flatness. No warpage laser
Spirit level
Tiles Consistency of colour tone & sizes No butting; Joint size: 2-4mm or otherwise stated by SO; Consistent colour of infill, preferably light Visual.
grey at wet area Measuring
tape
Free from damage, hollow, holes at joints No hollow sound when tapped; No crack & chip edges of tiles; Proper infill at tile joints: no holes; Ball bearing
Flat bedding at 5' wall tile termination rod. Visual
Positioning of fittings At required height & position = drawing & Plumbing & Sanitary Work Checklist Visual
Water ponding test ( for bathrooms) Test for 24 hours after completion of floor tiling Visual
(3) RS to mark 'a' if acceptable, 'x' if reject (& circle the respective item) or '-' if not check (not for Post-Installation). MC to rectify if any reject & RS to re-verify.

Filename: Q:\QA\TQM\cm_iso\Insp_CL\502195398.xls Version amended on 28/06/06

You might also like