Preliminary design of slab

lx = 11.33 ft C/C distance


3454.2683 mm
ly 14 ft C/C distance
4268.2927 mm
ly/lx = 1.2356575 two way slab
Minimum span (lx) = 3454.2683 mm
Concrete grade 20 KN/m2
Steel grade 500 KN/m2
% of steel assumed = 0.4 %
effective depth (d) = lx/αβγδλ
lx = 3454.2683 mm
α= 26 for continious slab
β= 1 for span less than 1
fs = 290 assuming area of cross section required =1 IS 456 figure 4
assuming area of cross section provided =1 IS 456 figure 4
γ= 1.4 IS 456 figure 4 IS 456 figure 4
δ= 1 assumed no compression steel
λ= 1 for no web

Minimum depth (d) = 94.897481 mm


so provide secondary beam as thickness is more than 150mm
Provide secondary beam in longest span so that one way slab is not formed from two way slab

Preliminary design of secondary beam

Maximum span of beam = 18.66 ft


5689.0244 mm
lx = 2844.5122 mm
ly = 15.33 ft
4673.7805 mm
d= 78.145939 mm
120 mm
clear cover = 40 mm
dia of bar = 20 mm
Overall depth (D) = 170 mm
250 mm
overal width (B )= 166.66667 mm

Preliminary design of main beam

Maximum span = 18.66 ft


5689.0244 mm
Take effective depth = maximum spam/12 to maximum span/15

width of beam = 1/2 * total depth to 2/3 * total depth

304.87805
25
16
337.87805 mm
Cantilever slab and beam = L/7
IS 456 figure 4
IS 456 figure 4
IS 456 figure 4 γ= tension reinforcement modification factor
δ= comprssion reinforcement modification factor

dsadsadsa

dasdasda

erwer
Preliminary design of slab
lx = 15.33 ft C/C distance
4673.7805 mm
ly 18.66 ft C/C distance
5689.0244 mm
ly/lx = 1.2172211 two way slab
Minimum span (lx) = 4673.7805 mm
Concrete grade 25 KN/m2
Steel grade 500 KN/m2
% of steel assumed = 0.4 %
effective depth (d) = lx/αβγδλ
lx = 4673.7805 mm
α= 26 for continious slab
β= 1 for span less than 1
fs = 290 assuming area of cross section required =1 IS 456 figure 4
assuming area of cross section provided =1 IS 456 figure 4
γ= 1.13 IS 456 figure 4 IS 456 figure 4
δ= 1 assumed no compression steel
λ= 1 for no web

Minimum depth (d) = 159.08034 mm


so provide secondary beam as thickness is more than 150mm
Provide secondary beam in longest span so that one way slab is not formed from two way slab

Preliminary design of secondary beam

Maximum span of beam = 18.66 ft


5689.0244 mm
lx = 2844.5122 mm
ly = 15.33 ft
4673.7805 mm
d= 96.817978 mm
120 mm
clear cover = 40 mm
dia of bar = 20 mm
Overall depth (D) = 170 mm
250 mm
overal width (B )= 166.66667 mm

Preliminary design of main beam

Maximum span = 18.66 ft


5689.0244 mm
Take effective depth = maximum spam/12 to maximum span/15

width of beam = 1/2 * total depth to 2/3 * total depth

304.87805
25
16
337.87805 mm
Cantilever slab and beam = L/7
IS 456 figure 4
IS 456 figure 4
IS 456 figure 4 γ= tension reinforcement modification factor
δ= comprssion reinforcement modification factor