Detail design of column

GRADE OF CONCRETE = M25


GRADE OF STEEL = Fe500
Fck = 25 N/mm2
Fy = 500 N/mm2
Depth(D) = 600 mm
Bredth(B)= 600 mm
Length(L)= 3200 mm
clear cover= 40 mm
ties dia= 8 mm
long bar = 20 mm
Check for member size
B/D= 1 >0.45 OK
IS 13920-2016, CL. 7.1.2
Effective length of the column
L effective = 0.65*l = 2080 mm (IS 456:2000, Table 28)
Check for slenderness ratio
Leff/D = 3.466666667 < 12 (IS 456:2000, cl.25.1.2)
Leff/B = 3.466666667 <12
Hence, SHORT COLUMN
Ast min = 1492.992 mm^2 Minimum reinforcement=0.8% of BD
Ast max= 7464.96 mm^3 Maximum reinforcement = 4% of BD
Ast ext= 11197.44 mm^4 but in extreme case= 6% of BD

Minumum eccentricity
ex= lx/500+D/30 = 26.4 (IS 456:2000, cl.25.4)
ey= ly/500+B/30 = 26.4
emin= 0.05*D= or 20 which ever is greater
so, ex = 30
ey= 30
FROM ETABS
Pu= 3996.996 KN
Mux= 426.9121 KNm
Muy= 345.5963 KNm
Hence,
Moment due to eccentricity about x ,
Muex = Pu*ex = 119.90988 KNm
Muey = Pu*ey = 119.9098 KNm
The design moment is greater of moment due to eccentricity and
moment obtained from analysis

Mux = 426.9121 KNm


Muy = 345.5963 KNm
assuming X% of steeel
P%= 2
d'=clear cover+ dia of ties + dia of long bar/2
d' = 58
d'/D= 0.096666667
Along x axis
Pu/Fckbd = 0.444110667
P/Fck= 0.16

FROM SP-16 CHART


Mux1/fckBD^2= 0.2
Mux1= 1080
d'/B=0.096666667
Along y axis
Pu/Fckbd = 0.444111
P/Fck= 0.16
FROM SP-16 CHART
Muy1/fckDB^2= 0.2
Muy1=1080
Puz=0.45*Fck*Ac+0.75*Fy*Asc, in KN
Puz= 6930.9 KN
Pu/Puz= 0.576692204
αn = 1.22
Check for safety of design
(Mux/Mux1)^αn+(Muy/Muy1)^αn = 0.59 < 1 ok
Hence,
column passed
confirmed p% = 2
Req longitidinal reinforcement
Ast req =7200

Bar size (mm) Area (mm2) nos


8 50.264 0
12 113.09 0
16 201.06 0
20 314.15 0
25 490.86 16
total area= 7853.8

total area= 7853.75 mm^2


Ast provided = 7853.75 mm2

Design for shear


Design shear force(Vu) = 305.1286 KN
Design shear Stress(τ) = Vu/BD = 0.8475 N/mm2
τc= 0.64 N/mm2 (IS 456:2000 TABLE 19&20
τc,max = 3.1 N/mm2
Pu = 3996.996kN
For member subjected to axial compression Pu, the design shear
strength of concrete(τc) shall be multiplied by the following factor: (IS
456:2000 Cl.40.2.2)

δ = 1+3*Pu/(Ag*fck) = 1<1.5
so,
δ=1.5
Design shear strength of concrete = δ*τc = 0.96 N/mm2
Shear capacity of section, ( Vuc ) = 312.192 KN
As Vuc>Vu , minimum shear reinforcement is to be provided in the
form of lateral ties.

Design of lateral Ties


Diameter of ties should not be less than:
i)max. diameter of bar/4 = 5 mm
ii) 6mm
provide 8mm diameter ties.
Pitch should not be greater than: (IS 456:2000 Cl.26.5.3.2 C)

i) least lateral diameter = 600 mm


ii)16 times diameter of bar = 320 mm
iii)300mm
hence, adopt pitch =300 mm
Hence,provide 8mm Ø ties @300mm C/C.
Spacing between longitudinal bars = (600-40*2-8*2-25)/4 = 119.75 >75mm
Additional ties need to be provided.
Special Confining Reinforcement
Design of link near support:
Area of cross sectional of bar forming rectangular hoop to be used as confining
links:
Ash = 0.18sDkFck/Fy(Ag/Ak-1)
where, Ak=area of confined concrete core in the rectangular hoop measured to
its outer dimension

Dk= 536 mm
Ash= 490.8594 mm2
Ak = 22527.36 mm
Ag= 600^2 mm2

Ash = 0.18sDkFck/Fy(Ag/Ak-1)
Or, 490.8594 = 0.18*S*536*(25/500)*(600^2/22527.36-1)
or, S = 175.65 mm>100mm
Spacing of hoop should be less than 100mm and minimum of 1/4 of B or D
whichever is less. But, the spacing need not be less than 75mm. (IS 13920:2000
Cl. 7.4.6)

Adopt 8 mm @ 100 mm as special confining ties at a distance Lo.


(from IS 13920:2002 Cl.7.4.1)
Lo is given by larger of followings:
a) Larger lateral dimension = 600mm
b) 1/6 of clear span =2750/6 = 458.33mm c)450mm"

Hence, provide 8mm diameter links @ 100mm c/c for a distance 600 mm on
either side from the joint and 8 mm diameter lateral ties @300mm c/c in
central portion.

Splicing of Longitudinal Reinforcement

Maximum 50 % of the bars is to be spliced at one section.


Splicing should be done in the middle half of the column height.Transverse
reinforcement in lap length should have spacing not exceeding 150mm c/c.i.e
providing 100 mm c-c
(IS 456:2000Cl.26.2.5.1)
Clear Length of Lap = Development Length or 24ϕ, whichever is greater
We have adopted 50ϕ
Ld = 0.87fyϕ/4τbd = 0.87*500*25/4*(1.4*1.6*1.25)
.= 971 mm
Ld = 971 mm

DESIGN OF COLUMN REINFORCEMENT


DESIGN OF COLUMN REINFORCEMENT

FLOOR P% COLUMN REQUIRED LONGITUDINAL PROVIDED PROVIDED


AREA REINFORCEMENT REINFORCEMENT AREA ( mm2) P%
(mm2) AREA (mm2)
BASEMMEN 2 360000 7200 16-25Ø 7853.92 2.11
T

GROUND 2 360000 7201 16-25Ø 7853.92 2.11

FIRST 2 360000 7202 16-25Ø 7853.92 2.11

SECOND 2 360000 7203 16-25Ø 7853.92 2.11

THIRD 1 360000 3600 8-25Ø 3927 1.08

FOURTH 0.85 360000 3600 8-25Ø 3927 1.08

ROOF 0.8 360000 3600 8-25Ø 3927 1.08