This document summarizes the design of Column C3 for confining reinforcement. The column has a size of 800x800mm and is 9650mm long. 20 bars of 25mm diameter are provided along with ties of 10mm diameter spaced at 75mm. Calculations show the provided reinforcement of 1.54% is adequate and spacing requirements are satisfied. The minimum required length of special confining reinforcement is 1608mm which is less than the provided length of 1800mm.
This document summarizes the design of Column C3 for confining reinforcement. The column has a size of 800x800mm and is 9650mm long. 20 bars of 25mm diameter are provided along with ties of 10mm diameter spaced at 75mm. Calculations show the provided reinforcement of 1.54% is adequate and spacing requirements are satisfied. The minimum required length of special confining reinforcement is 1608mm which is less than the provided length of 1800mm.
This document summarizes the design of Column C3 for confining reinforcement. The column has a size of 800x800mm and is 9650mm long. 20 bars of 25mm diameter are provided along with ties of 10mm diameter spaced at 75mm. Calculations show the provided reinforcement of 1.54% is adequate and spacing requirements are satisfied. The minimum required length of special confining reinforcement is 1608mm which is less than the provided length of 1800mm.
Gross area of pedestal A g = 800 x 800 = 640000 mm2 Clear cover to rebar = 75 mm Details of reinforcement provided Diameter of bar = 25 mm No. of bars provided = 20 Nos. Diameter of ties = 10 mm Spacing of ties S= 75 mm c/c Concrete Grade = M-30 Comp. strength fck = 30 N/mm2 Steel Grade Fe 500D 500 N/mm 2 Yield strength ; fy = Length of column 9650 mm
Area of reinforcement required from STAAD = 8793 mm2
\ Pt Required = 8793 x 100 / 640000 = 1.38 % \ Pt Provided = ( π /4 x 252 ) x 100 / x 20 x 640000 = 1.54 % No. of bars on one face = 6 Nos. No. of bars on second face = 4 Nos.
\ Maximum spacing = (800 - 2 x 75 - 2 x 10 - 25 ) = 121 mm
5 Check for spacing between vertical bars
As per Cl. 7.4.8 of IS 13920 : 1993
The area of cross section, Ash of the bar forming rectangular hoop, to be used as special confining reinforce- ment shall not be less than
Ash = 0.18S.h.fck /fy [ Ag / Ak - 1.0]
Where; h = Longer dimension of the rectangular confining hoop measured to its outer face. ≤ 300 mm Ak = Area of confined concrete core in the rectangular hoop measured to its outside dimensions. The size of concrete core = 630 mm x 630 mm Therefore; Ak = 630 x 630 = 396900 mm2 Ash = π /4 x10 ^2 = 78.54 mm2
\h= Ash / [0.18S.fck /fy (Ag / Ak - 1.0)]
h= 78.54 = 158.31 mm 0.18 x 75 x 30 / 500 ( 640000 / 396900 - 1.0 ) > 121 mm Therefore, O.K. Special confining reinforcement shall be provided over a length L0 from each joint face, As per Cl. 7.4.1 of IS 13920:1993 Length L0 shall not be less than, a) large lateral dimension of member = 800 mm b) 1/6 of clear span of the member = 1/6 x 9650 = 1608.34 mm c) 450 mm \ Minimum length of special confining reinforcement is 1608 mm Provided length of special confining reinforcement is 1800 mm Therefore, O.K. Design of Column - C1, for confining reinforcement Data
Pedestal Size 850 mm x 850 mm
Gross area of pedestal A g = 850 x 850 = 722500 mm2 Clear cover to rebar = 50 mm Details of reinforcement provided Diameter of bar = 25 mm No. of bars provided = 24 Nos. Diameter of ties = 8 mm Spacing of ties S= 100 mm c/c Concrete Grade = Comp. strength fck = 30 N/mm2 Steel Grade Fe 500D 500 N/mm 2 Yield strength ; fy = Length of column 4500 mm
Area of reinforcement required from STAAD = 6142 mm2
\ Pt Required = 6142 x 100 / 722500 = 0.86 % \ Pt Provided = ( π /4 x 252 ) x 100 / x 24 x 722500 = 1.64 % No. of bars on one face = 8 Nos. No. of bars on second face = 6 Nos.
\ Maximum spacing = (850 - 2 x 50 - 2 x 8 - 25 ) = 101.29 mm
7 Check for spacing between vertical bars
As per Cl. 7.4.8 of IS 13920 : 1993
The area of cross section, Ash of the bar forming rectangular hoop, to be used as special confining reinforce- ment shall not be less than
Ash = 0.18S.h.fck /fy [ Ag / Ak - 1.0]
Where; h = Longer dimension of the rectangular confining hoop measured to its outer face. ≤ 300 mm Ak = Area of confined concrete core in the rectangular hoop measured to its outside dimensions. The size of concrete core = 734 mm x 734 mm Therefore; Ak = 734 x 734 = 538756 mm2 Ash = π /4 x8 ^2 = 50.27 mm2
\h= Ash / [0.18S.fck /fy (Ag / Ak - 1.0)]
h= 50.27 = 136.48 mm 0.18 x 100 x 30 / 500 ( 722500 / 538756 - 1.0 ) > 101.29 mm Therefore, O.K. Special confining reinforcement shall be provided over a length L0 from each joint face, As per Cl. 7.4.1 of IS 13920:1993 Length L0 shall not be less than, a) large lateral dimension of member = 850 mm b) 1/6 of clear span of the member = 1/6 x 4500 = 750 mm c) 450 mm \ Minimum length of special confining reinforcement is 850 mm Provided length of special confining reinforcement is 900 mm Therefore, O.K. Design of Column - C3 for confining reinforcement Data
Pedestal Size 800 mm x 800 mm
Gross area of pedestal A g = 800 x 800 = 640000 mm2 Clear cover to rebar = 75 mm Details of reinforcement provided Diameter of bar = 25 mm No. of bars provided = 20 Nos. Diameter of ties = 10 mm Spacing of ties S= 75 mm c/c Concrete Grade = M-30 Comp. strength fck = 30 N/mm2 Steel Grade Fe 500D 500 N/mm 2 Yield strength ; fy = Length of column 9650 mm
Area of reinforcement required from STAAD = 8736 mm2
\ Pt Required = 8736 x 100 / 640000 = 1.37 % \ Pt Provided = ( π /4 x 252 ) x 100 / x 20 x 640000 = 1.54 % No. of bars on one face = 6 Nos. No. of bars on second face = 4 Nos.
\ Maximum spacing = (800 - 2 x 75 - 2 x 10 - 25 ) = 121 mm
5 Check for spacing between vertical bars
As per Cl. 7.4.8 of IS 13920 : 1993
The area of cross section, Ash of the bar forming rectangular hoop, to be used as special confining reinforce- ment shall not be less than
Ash = 0.18S.h.fck /fy [ Ag / Ak - 1.0]
Where; h = Longer dimension of the rectangular confining hoop measured to its outer face. ≤ 300 mm Ak = Area of confined concrete core in the rectangular hoop measured to its outside dimensions. The size of concrete core = 630 mm x 630 mm Therefore; Ak = 630 x 630 = 396900 mm2 Ash = π /4 x10 ^2 = 78.54 mm2
\h= Ash / [0.18S.fck /fy (Ag / Ak - 1.0)]
h= 78.54 = 158.31 mm 0.18 x 75 x 30 / 500 ( 640000 / 396900 - 1.0 ) > 121 mm Therefore, O.K. Special confining reinforcement shall be provided over a length L0 from each joint face, As per Cl. 7.4.1 of IS 13920:1993 Length L0 shall not be less than, a) large lateral dimension of member = 800 mm b) 1/6 of clear span of the member = 1/6 x 9650 = 1608.34 mm c) 450 mm \ Minimum length of special confining reinforcement is 1608 mm Provided length of special confining reinforcement is 1800 mm Therefore, O.K.