Professional Documents
Culture Documents
FIREALARMSYSTEM
FMS-3000
Technical Documentation
modification level
Version Date Author approved remarks
0.5.2 30.12.04 STO HN revises
0.5.3 21.04.05 STO HN One man testing
0.5.4 09.08.05 STO HN Configurationstool
0.5.5 31.10.05 STO HN Software Version 1.7
0.5.6 05.03.06 STO HN Software Version 2.1
0.5.7 18.10.07 STO DOE Software version 3.X.X
0.5.7 26.06.08 STO DOE Installation Instructions
Table of contents
1. Structure of the plant 3-4
Trafo module
(nessesary for every system)
Output module
(nessesary for every system)
(nessesary for every system with 16 Loops) (nessesary for every system with 24 Loops)
Page 3 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Trafo module
(nessesary for every system)
Output module
(nessesary for every system)
(nessesary for every system with 16 Loops) (nessesary for every system with 24 Loops)
Page 4 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Contains input for main- and emergency supply, 230VAC or alternatively 115V AC
Contains fuses for supply, 230VAC/ 115V AC and for the internal 24V DC
Generally
The Transformer module are fitted with a transformer which can be switched from 230V AC to 115V
AC.
The selection of the Power Supply will be made by turning the voltage selector and changing the
relays 230VAC or 115 V AC for power input.
Terminals
Page 5 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Contains Main Processor for the whole Fire alarm system, Power Supply unit 24V DC and battery
charger for the external 24V DC stand-by battery.
Charging unit for the stand-by batteries 24V DC up to 12Ah depending upon load of the entire plant.
Generally
The power supply module represents the communication master in the RS485 communication system.
Apart from the power distribution for the remaining modules contain the power supply module the
emergency power supply (with external accumulators), a charging circuit, safety circuit and an energy
management system. Further the power supply module possesses a real-time clock, a History
memory and a static text memory for the keeping of reporting places and causes of malfunction. The
power pack has 9 connection boards for modules, for which altogether for a currant 10A can be
supplied.
Page 6 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
8x potential free relay outputs max of 250V 2A for the following possibilities programmable:
Fire alarm, Fault alarm, Power Supply failure and delayed Firealarm.
2x 24V DC outputs for fire bells max 1A for each output fire alarm programmable.
Quiescent current supervised by an end of line resistor. 3 KOhm
Tone sequence selectable, steady tone or intermitted tone.
1x 24V DC output for door magnet, max 1A disconnection with fire alarm, programmable for the
selection of the fire loops.
1x input for external Push button in order to activate manually the 24V of bell outputs.
General
The Output module contains eight relays, as well as three 24V outputs and an input for an external
Push button or switch.
A micro CONTROLLER activate the relays, the 24V outputs, the push button input and communicates
with the Power Supply module.
Voltage supply
The 24V input voltage is led across a polarity protection diode, a throttle and filter capacitors on an
electrically isolating DC/DC transducer. The transducer supplies 5V for the micro CONTROLLER and
the control and monitoring of the OPC exits. The 24V supply voltage is connected with the +5V output
of the DC/DC transducer. The digital ground of the circuit rests upon thereby - 5V related to the 24V
Operation voltage. The RS485 driver and the associated circuit are supplied via a step down
automatic controller with 5V.
RS485-Driver
The communication is made by a RS485 driver. The driver lies with its mass on 24v-gnd and is
therefore galvanically over opto couplers from the micro CONTROLLER and the other circuits
separate.
Page 7 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Relays
Terminals JR1 and JR2
The relays are normal open contact with 2A permanent current and a rated voltage of 220V and are
programmable for fire alarm, fault alarm, voltage failure and/or general alarm (2min delayed).
Output interfaces
Terminals JOC1 and JOC 2
The 24V DC outputs are design as a short circuit proof output with a maximal currant of 1A and are
programmable for fire alarm, fault alarm, voltage failure and/or general alarm (2min delayed).
Two outputs (1 and 2) are assign for Firearm which are connected to the Push button input and can
activated by this input.
One output ( 3) are assign for Door magnets and has no connection with the push button input.
In case of an short circuit the loop will be disconnected for up to 3 sec and then automatically
reconnected.
Additional each loop has a switchable connection max 8mA to check the 3 K Ohm end of line resistor.
The module contains an input for the connection an external push button.
The voltage supply for the input becomes secured against short-circuits.
The voltage amounts to in the no-load operation 24V.
The input switches the bell outputs on manually. With pressed key the bell outputs are switched on.
After disconnection of the button the outputs are again turned off.
Page 8 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
General
The module contains eight fire detection loops and eight pot. free outputs which can be programmed
for fire- fault alarm or both.
Two micro CONTROLLERS operate and supervise the fire detection loops and outputs and
communicate with the Power supply module.
Voltage supply
The 24V input voltage is led across a polarity protection diode, a throttle and filter capacitors on an
electrically isolating DC/DC transducer. The transducer supplies ±5V for the micro CONTROLLER,
the controlling, current measurement and monitoring of the fire detecting loops and OPC outputs.
The 24V supply voltage is connected with the ground connection of the DC/DC transducer.
The digital ground of the circuit lies thereby on the 24V-supply voltage.
The tensions, related to 24V GND, are 19V for the -5V-supply and 29V for the +5V-supply.
The RS485 driver and the associated circuit are supplied via a step down automatic controller with 5V.
RS485-Driver
The communication is made by a RS485 driver. The driver lies with its measures on 24v-gnd and is
therefore galvanically separately over opto couplers from the micro CONTROLLER and the other
circuits separate.
Page 9 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
In normal operation the quiescent currant will be measured the in the last detector installed 3 K Ohm
end of line resistor and in case of failure will be report this to the power supply module.
In case of a fire alarm on one connected detector the system measure the 470 Ohm alarm resistor of
this depending detector and will report the fire alarm to the power supply module.
All detection loops will be protected against short circuit. In case of a short circuit the loop will be
disconnected and after 30 sec reconnected. The maximal currant on each loop is 400mA.
The sum of all detection loops do not exceed more than 1,6A. If the currant is higher than 1,6A the
controller will be disconnect the loop with the highest currant and report this to the power supply
module.
Relay outputs
The relays are normal open contact with 0,5A permanent current and a rated voltage of 24V DC and
each 4 outputs are connected with the common line together.
Outputs are programmable for fire alarm, fault alarm or both.
Page 10 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Interface module for the connection of a Centronics of printer that the messages, as in the display are
indicated, prints.
Alarm text, time, date, status
General
Example:
Voltage supply
The 24V input voltage is led across a polarity protection diode, a throttle and filter capacitors on an
electrically isolating DC/DC transducer. The transducer supplies 5V for the micro CONTROLLER and
the drivers of the printer exits. The 24V GND connection is connected with the 5V-GND connection of
the DC/DC transducer. The digital mass of the circuit lies thereby on 24v-gnd.
Printer drivers
The printer drivers are implemented as CMOS LINE Driver. RC filters in the connecting cables protect
the drivers. A micro CONTROLLER (ATmega16) receives the printer data over the RS485 interface
and heads for the printer drivers.
Page 11 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Output card laid out for communication interface for TS35 mounting rail assembly
Output for VDR over a RS422 interface.
The VDR module sends data over RS485 or RS232 to a VDR (Voyage DATA recorders).
The module is alternatively configured with drivers for RS485 or RS232.
The communication profile of the VDR interface depends on the following specification:
IEC 61162-1 part 1 single of talker and multiple listeners
IEC 61162-100 extra requirement for the UAIS
IEC 61162-102 extra requirement for the Voyage DATA recorder
Voltage supply
The 24V input voltage is led across a polarity protection diode, a throttle and filter capacitors on an
electrically isolating DC/DC transducer. The transducer supplies 5V for the micro CONTROLLER and
the drivers of the VDR outputs. The 24V GND connection is connected with the 5V-GND connection
of the DC/DC transducer. The digital mass of the circuit lies thereby on 24V-gnd.
VDR Output
The micro CONTROLLERS an ATmega162 with two serial interfaces, communicates over one of the
interfaces with the control Panel and with the other one over one of the two alternatively equipped
drivers for RS485 or RS232.
Page 12 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Usually built in the visible desk plate of the control desk of the Commando bridge.
Text display is background-lit, readable also during sun exposure, 2 lines with 20 letters each.
All buttons and Fire, fault indicators are background-lights up.
General
In direct proximity of the fire alarm system is attached the Main panel.
Hereby the FMS-3000 can be observed and operated.
The connection of maximally 2 repeater panels in up to 500 meters distance is possible.
The Main Panel contains one LC display (2 lines to ever 20 letters), 10 keys, 40 LED´s and a Buzzer
for acoustic signaling.
In order to be able to adapt the LED´s optimally to the locally dominant lighting conditions, the intensity
is adjustable.
The adjustment of the contrast and the background lighting is just as flexible in the case of the display.
Voltage supply
The 24V input voltage is led across a polarity protection diode, a throttle and filter capacitors on an
electrically isolating DC/DC transducer. The transducer supplies 5V for the micro CONTROLLER.
The 24V GND connection is connected with the 5V-GND connection of the DC/DC transducer. The
digital mass of the circuit lies thereby on 24v-gnd. The LED´s are supplied via pre-resistors and PWM
voltage regulator with 24V.
Display
The display is controlled via 8-bits a data bus as well as over R-S, RW and E (Clock) by the micro
CONTROLLER.
Page 13 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
LEDs
The LED´s are divided in two groups (alarm and normal). The groups are independent of each other
in the brightness controllable. But two PWM voltage regulator made of RC element with following
transistor switching are used. Two LED´s in the group "alarm" are in each case switched one behind
the other. Because in the group "normal" also individual LED´s are headed for, it is necessary to
operate also two LED´s parallel in order to achieve an even brightness over the dimming range.
Buttons
The button lines are over pull up resistances on digitally high. With pressed key the line is drawn on
digitally 0.
Buzzer
The Buzzer is switched over a driver transistor and over a haven line of the micro CONTROLLER.
For an external Buzzer a 24V interface is intended.
Page 14 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
3.1 Overview
The visible components of the fire alarm system is the Main panel and if necessary the repeater panel,
which have a reduced functionality. As further signaling elements serves the open Collector outputs of
the fire detecting loops, which activated LED´s from an external mimic panel.
To all inputs on the control panel applies, which must press first the “UNLOCK” button.
The activation applies until 30 second after last pressing of one button or by pressing the “UNLOCK”
button again.
The unlocking of the buttons will be signaled by a yellow LED over the button “UNLOCK”.
Page 15 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
The Main panel and the repeater panel differ in the indicating and control elements.
The repeater panel possesses only locally limited characteristics.
Confirming and resetting alarms are not made possible.
The repeater panel announces itself when switching on with the text:
…. …..
FMS-3000HIT
Only the Main panel is to be switched able the detection loops and switching outputs of the plant.
The power-up message of a main panel is:
…. …..
FMS-3000
In the case of an alarm can this exclusively by the Main panel confirmed and resettet.
The announcement of the alarm conditions takes place on all panels identically.
To the condition and alarm display are intended an acoustic signal generator (buzzer), an LCD
announcement and two lit key fields with the labels FIRE and Fault.
Occurrence an appearance of several fire alarms at the same time the red LED “ ALARM IN
SEQUENCE” shines.
Page 16 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
In a normal state only the green LEDs for background lighting the LCD announcement announces
“STATUS” and shows date and time at
STATUS 14:33:06
FMS-3000 16.12.04
24.05.05
Should several alarms fit at the same time, shines the LED “ ALARM IN SEQUENCE“ red.
The LC display changes the text for the alarm place to pressing on the key FIRE and/or the keys UP
and DOWN.
If the alarm was not confirmed after 2 minutes, the general alarm is activated automatically and the
text “ FIRE DLY.” For the delayed fire alarm in the first line of the display indicates.
By pressing of the button “Fire” the actual alarm is confirmed and the buzzer grows silent.
It takes place an appropriate entry in the History, and if connected at the alarm printer and VDR
recorder.
Page 17 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
If several alarms should indicated, then the key FIRE must be pressed for accepting the alarms
several times.
The “Fire” Led will flash as long as not all new Fire alarms was accepted, after accepting all Fire
alarms the Led change to steady light.
In order to show all Fire alarms in the display you can scroll with the arrow “Up- Down buttons or by
pressing the “FIRE” button serval times.
LCD-Announcement after releasing the delayed fire alarm ( after 2 min delay):
LCD announcement after confirming a fire alarm (with the key ' FIRE '):
The fire alarm will be finally reset if the button reset will be pressed. In this case the voltage on the depending
loop wills shortly disconnected and the detector reset.
Each individual fire alarm has to be accepted individually by pressing the “Fire” button, only after the accepting it
can be reset.
Only the Fire/ Fault alarm can be reset with are actual indicated in the display.
A common rest of all alarms is not possible.
If the fire alarm are announcing again the detector are actual in alarm case.
Page 18 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
By pressures of the keys “Unlock” and afterwards “Fault” by the operator, which the fault signal were
recognized, confirms.
Thereupon the buzzer grows silent and the yellow light emitting diode (Fault) change in the steady
light.
The display shows:
Page 19 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
During all inputs on the main or repeater panel applies, the buttons must be unlocked for operation
with the key “Unlock”.
This function discontinued after 30 sec from the last input or can discontinued by pressing the ”Unlock”
again.
This is a prescribed protective function against unplanned inputs.
An overview of the possible alarm and error messages of the FMS-3000 supplies appendix A-4.
“Overview error and fire messages “
With this button “Loop OFF-ON” fire detection loops can be deactivated.
The deactivated loops do not announce a fire!
After the manipulation display appears to this button a request for input, in order to be able to select
those loops which can be switched on the LCD.
Depending upon activation status of the fire reporting loop the text appears:
These selections of the loop which can be switched are selectable by the UP/DOWN buttons right
beside the display. Out switching on effected via repeated operates the button “loop off-on”.
After switching a loop off remains the lit key field actively (yellow), until all loops were again activated.
To leave this menu item by pressing the “Unlock” button.
The deactivated loops can be shown on the Display without pressing the “Unlock” button by pressing
st nd
“Loop ON-OFF”. By pressing the button 1 it will indicate loop 1-8 by pressing the button 2 it will
rd
indicate the loop 9.16 by pressing the button 3 it will indicate the loop 17-24, buy pressing the button
again the Display will change to normal State.
LOOP SET: YYYYYYYY “Set” is indication the normal condition of the loop
1-8 Actual: YNYYNYYY “Actual” will indicate the actual condition.
Example: Loops 2 and 5 are disconnected.
Page 20 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
After the manipulation of this button display appears a request for input, in order to be able to select
that output which can be switched on the LCD.
Depending upon activation status of the output the text appears:
This selection of the outputs which can be switched does not take place actively with UP/DOWN the
buttons right beside the display.
Out switching on takes place via repeated operates the button “output off-on”.
After disconnecting an output, the led field remains active (yellow), until all outputs were again
activated.
To leave this menu by pressing the “Unlock” button.
The deactivated outputs can be shown on the Display without pressing the “Unlock” button by pressing
st nd
“Output OFF-ON”. By pressing the button 1 it will indicate output 1-8 by pressing the button 2 it will
indicate the output 9-11 (24V DC), buy pressing the button again the Display will change to normal
State.
Output SET: YYYYYYYY “Set” is indication the normal condition of the output and
1-8 Actual: YNYYNYYY “Actual” will indicate the actual condition.
Example: Output 2 and 5 are disconnected.
Page 21 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
3.3.3 DIMMER
Please note: This function is not possible with an not acknowledged fire alarm!
To leave this menu by pressing the “Unlock” button.
The lamp test, which is dark under normal conditions (no announced error).
Further the signal outputs of the attached loop maps are activated for 5 seconds.
Please note: This function is not possible with a not acknowledged fire alarm!
Page 22 of 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
STATUS 14.33.08
FMS-3000 16:12:04
24.05.05
Please note: The menu functions cannot be used with a not acknowledged fire alarm!
To storing the adjustment is to be pressure at that corresponding menu option the UP key.
Tel.: +49 (0)4105 / 65 60 – 0 * DECKMA GmbH * Fax: +49 (0)4105 / 65 60 – 25
E-mail: info@deckma-gmbh.de * Internet: www.deckma-gmbh.de
Seite 23 von 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Example:
With a plant with a Main- and repeater panel precipitates the main display discontinues. This failure
report will only on the repeater panel indicated, at which it cannot be confirmed and acknowledged
however. After the main display communicates again with the master, “roll-back” mechanism
provides after some minutes for a balanced system. The announced error on the auxiliary display is
not any longer indicated.
Example: For the power supply module will be indicated the following text::
Version: N00_NM01:0100.041216
In node 0 (N00) of the power supply module (NM01) are Version 1.0 with software from 16.12.04
used.
Seite 24 von 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
- CLEAR History by pressing the “UP key” you delete you all entries in history file
press UP keys.
- exit press UNLOCK To leave this menu press the button “UNLOCK”.
The fire alarm system counts now all arriving fire alarms (independently of any detection loops).
All Fire alarms will be additional stored into the history file.
To indicate that the one man testing mode is activated, the “Fire” Led will flash and the Display will
show One-Man-Test and the counter will show the numbers of released Fire alarms.
With the activation at least one fire-detector, Sounds the buzzer on all displays (steady tone), flashes
the red light emitting diode with the inscription “ FIRE” in full brightness, the LCD announcement
announces “ NEW FIRE” and in the second line the alarm place.
After a time of 5 seconds this alarm will be automatically accepted, the buzzer grown silent and the
red light emitting diode changes in steady light. After further 5 seconds the alarm will be reset.
The number of the Fire alarms will be indicated in the Display.
The number of released alarms is indicated independently of all fire reporting loops.
Importantly: In order to terminate the One Man testing function is a RESET to all modules to
be made. See 3.4.3
Seite 25 von 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
In order to control the Smoke detection System SFMS remotely the following function are from the
FMS 3000 available.
Seite 26 von 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
The repeater panel PT01-E can be likewise several times in the plant present.
For the assignment of a node number a bridge must be put in the Sub D 15 socked.
Additional does have to be set to the last panel in each case in the RS485-Bus a terminal resistance
(120 ohms).
This resistance is activated by a bridge between the pin 12 and 4.
In the case of only one display this bridge is to be also set!
Once if several identical node numbers are present in a RS485 net, it comes to heavy communication
disturbances. A trouble free operation of the plant is not possible any longer.
Seite 27 von 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Seite 28 von 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Assembly connection box/switchgear cabinet the first shot and evaluation box which voltage supply and power
pack module, output module, printer interface, fire detection module and the output card for communication
interface contains.
This box is usually installed within the control desk on the wheelhouse and connected with one up to 3m long
interwiring plug-in with the control panel.
The dimension of this cabinet varying according the numbers of used modules.
For further information please see the attached specific system drawings.
530
500
Seitenansicht Kabeleinführung
72
64
76
72
90
10
101 101
Befestigungsabmessungen
195
Mounting Measurement
20 220 20 220 20
295
350
500
Seitenansicht Kabeleinführung
110
120
105
m
Ø 8,5 m
Seitenansicht
345
350
Kundenkabelkanal
Seite 29 von 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Seite 30 von 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
The following cables are recommended for a safe operation of the Fire whole system
For connecting the conventions detectors and Devices to one Loop module please see the
attached drawing (every Loop module is designed for 8 conventional Loops).
All terminals are lockable plug terminal
After the installation please secure all terminals.
Seite 31 von 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Introduction
The conventional Sensors SLR-EM, DCD-AE3M and DCD-CE3M can all use a Common
Mounting Base (YBN-R6M) which is electronics free.
Follow the guidelines below before installation and maintenance. Deckma cannot guarantee
a sensor's performance if these guidelines are not followed.
Caution
The CDX range sensors cannot be used to prevent fire itself, they are only intended to
detect a certain characteristic of fire. The sensor DCD-AE3M and DCD-CE3M are used to
detect conditions and changes in temperature and cannot detect smoke and other
phenomena. When installing the sensor, check that the location of each one has been
planned according to appropriate fire regulations or recommendations.
The sensor and base combination should be installed to the following guidelines:
- Ensure the Sensor and Base are installed in accordance with Local Standards or
Regulations.
- Sensor and Base combinations should only be installed where ambient
temperatures are between -10°C to +50°C and where the condensation and
moisture levels are between 10% to 95% RH - Non condensing (at 40°C) .
- Only install in suitable environments, the following should be avoided.
- Situations in which condensation exists.
- Situations in which corrosive gases exist.
- Situations in which dust or steam exists.
- Situations in which obstacles exist, which could impede air flow to the sensor.
- Non Ex detectors in Hazardous areas.
Do not use a high voltage tester on the Sensor or Base.
Certain actions can cause permanent damage to the sensor. If the sensor is subjected
to any of the following it should not be used:
- Dis-assembly and re-assembly.
- Impact or shock.
If damage is suspected after a fire has occurred, the sensor should be replaced. After
installation, all sensors on the fire alarm system should be tested to confirm correct
operation. Installation and maintenance should only be carried out by suitably trained
engineers. Sensor operation should not be tested with a naked flame or open fire. Operation
should only be checked by equipment that is capable of exceeding the required detection
threshold.
The sensor must be subject to periodic maintenance during regular service visits. This
period should be outlined in the appropriate standards or recommendations. If there are no
such standards existing, we recommend that the minimum period of maintenance should be
1 year and that the following should be taken into account:
- A regular operation test should be performed.
- A visual check for staining and mechanical damage should be made.
A dust cover is included with the sensor to prevent contamination during installation.
The dust cover must be removed for the sensor to operate.
Seite 32 von 40
8.1 View of main cabinet FMS 3000
Tel.: +49 (0)4105 / 65 60 – 0 * DECKMA GmbH * Fax: +49 (0)4105 / 65 60 – 25
530
72
64
72
72
84
10
101 101
Befestigungsabmessungen
195
Mounting Measurement
30 215 45 215 30
295
350
500
Seitenansicht Kabeleinführung
Side view Cable inlet
8.0 Drawings
105
110
120
Ø 8,5 mm
Seite 33 von 40
Seitenansicht
Material Stahlblech 1,5mm/ Material Steel 1,5mm
Montageplatte Stahlblech 3mm/ Monting plate steel 3mm
Lackierung Grau RAL 7035/ Color Grey RAL 7035
Deckelbefestigung mittels 4 Schrauben M6/ Cover fixed with 4 screws M6
OPERATION MANUAL
FIREALARMSYSTEM
345
350
350
Fire module Fire module Fire module
Output module Loop 1-8 Loop 9-16 Loop 17-24
FMS-3000
Kundenkabelkanal
Cable channel
Main Cabinet
S 3677 Not to scale
8.2 Transformer module TR 01-E
Seite 34 von 40
E-mail: info@deckma-gmbh.de * Internet: www.deckma-gmbh.de
FMS-3000
Not to scale
Scale
Page
1/ 1
Power Supply Card AFMS3000 NT01-E
Revision:
Date:
Date:
06.02.07
Torbeck
Checked:
Design:
Date:
Date:
Seite 35 von 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Not to scale
Scale
Page
1/ 1
Main Panel FMS3000 HT01-E
Revision:
Revision:
Date:
Date:
26.10.04
Torbeck
144
Checked:
Design:
Date:
Date:
144
Seite 36 von 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Not to scale
Scale
Page
1/ 1
Outputcard FMS3000 AM01-E
S 3460
Drawing No.:
07.02.2006
Revision: A
Revision:
Date:
Date:
26.10.04
Torbeck
Checked:
Design:
Date:
Date:
Seite 37 von 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Not to scale
1 1
Firedetector Loopcard Loop 1-8
S 3461
31.10.05
A/New
26.10.04
Torbeck
Seite 38 von 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Not to scale
1 1
Firedetector Loopcard Loop 9-16
S 3462
31.10.05
A/New
26.10.04
Torbeck
Seite 39 von 40
OPERATION MANUAL
FIREALARMSYSTEM
FMS-3000
Not to scale
1 1
Firedetector Loopcard Loop 17-24
S 3463
31.10.05
A/New
26.10.04
Torbeck
Seite 40 von 40