LƯU ĐỒ SHUTDOWN HỆ THỐNG ĐÓNG CÁC VAN

SDV CHO HỆ THỐNG TANK FARM #3

1. LƯU ĐỒ SHUTDOWN HỆ THỐNG (ĐÓNG CÁC SDV) - GAS DETECTOR

 SHUTDOWN HỆ THỐNG KHI 2 TRONG 7 ĐẦU DÒ GAS KÍCH HOẠT MỨC HIGH HIGH ĐỒNG
THỜI MỞ VAN DELUGE CẤP NƯỚC CHỮA CHÁY TỚI CÁC ĐẦU PHUN SƯƠNG CHO 3 BỒN
CHỨA LPG

GD 3001 GD 3011
ACTIVE HIGH HIGH ALARM ACTIVE HIGH HIGH ALARM
SETPOINT: ………. SETPOINT: ……….

(AND)
Cả 2 đầu dò kích hoạt

XV-1031
SDV-1003 XV-1001 SDV-1013 XV-1011 SDV-1023 XV-1021 ACTION :
ACTION : ACTION : ACTION : ACTION : ACTION : ACTION : CLOSE VALVE
CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE (ĐÓNG VAN)
(ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) VAN NƯỚC
CỨU HỎA
2. LƯU ĐỒ SHUTDOWN HỆ THỐNG (ĐÓNG CÁC SDV )- FLAME DETECTOR

 SHUTDOWN HỆ THỐNG KHI 2 TRONG 6 ĐẦU DÒ LỬA KÍCH HOẠT MỨC HIGH HIGH ĐỒNG
THỜI MỞ VAN DELUGE CẤP NƯỚC CHỮA CHÁY TỚI CÁC ĐẦU PHUN SƯƠNG CHO 3 BỒN
CHỨA LPG

FD 3001 FD 3011
ACTIVE HIGH HIGH ALARM ACTIVE HIGH HIGH ALARM
SETPOINT: ………. SETPOINT: ……….

(AND)
Cả 2 đầu dò kích hoạt

XV-1031
SDV-1003 XV-1001 SDV-1013 XV-1011 SDV-1023 XV-1021 ACTION :
ACTION : ACTION : ACTION : ACTION : ACTION : ACTION : CLOSE VALVE
CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE (ĐÓNG VAN)
(ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) VAN NƯỚC
CỨU HỎA

3. LƯU ĐỒ SHUTDOWN HỆ THỐNG (ĐÓNG CÁC SDV) – EMERGENCY


SHUDOWN

 SHUTDOWN HỆ THỐNG KHI 1 TRONG 2 NÚT NHẤN ESD KÍCH HOẠT ĐỒNG THỜI MỞ VAN
DELUGE CẤP NƯỚC CHỮA CHÁY TỚI CÁC ĐẦU PHUN SƯƠNG CHO 3 BỒN CHỨA LPG

ESD 3001 ESD 3002


NÚT NHẤN KHẨN CẤP GẦN CỬA NÚT NHẤN KHẨN CẤP GẦN CỬA
RA VÀO RA VÀO

(OR)
1 trong 2 nút nhấnkích hoạt

XV-1031
SDV-1003 XV-1001 SDV-1013 XV-1011 SDV-1023 XV-1021 ACTION:
ACTION: ACTION: ACTION: ACTION: ACTION: ACTION: CLOSE VALVE
CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE (ĐÓNG VAN)
(ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) VAN NƯỚC
CỨU HỎA
4. LƯU ĐỒ SHUTDOWN HỆ THỐNG (ĐÓNG CÁC SDV) – MANUAL CALL
POINT

 SHUTDOWN HỆ THỐNG KHI 1 TRONG 2 MAC KÍCH HOẠT (ĐẬP VỠ KÍNH CỦA THIẾT BỊ)
ĐỒNG THỜI MỞ VAN DELUGE CẤP NƯỚC CHỮA CHÁY TỚI CÁC ĐẦU PHUN SƯƠNG CHO 3
BỒN CHỨA LPG

MAC 3001 MAC 3002


ĐƯỢC LẮP Ở GẦN CỬA RA VÀO
ĐƯỢC LẮP Ở GẦN CỬA RA VÀO

(OR)
1 trong 2 thiết bị kích hoạt

XV-1031
SDV-1003 XV-1001 SDV-1013 XV-1011 SDV-1023 XV-1021 ACTION :
ACTION : ACTION : ACTION : ACTION : ACTION : ACTION : CLOSE VALVE
CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE (ĐÓNG VAN)
(ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) VAN NƯỚC
CỨU HỎA

5. LƯU ĐỒ SHUTDOWN HỆ THỐNG (ĐÓNG CÁC SDV) - GAS DETECTOR

 SHUTDOWN HỆ THỐNG KHI 1 ĐẦU DÒ GAS KÍCH HOẠT MỨC HIGH HIGH TẠI LÒ ĐỐT
TRONG XƯỞNG SƠN

GD 3001
ACTIVE HIGH HIGH ALARM
SETPOINT: ……….

Cảnh báo ALARM trên SCADA


6. LIÊN ĐỘNG TRONG XƯỞNG SƠN TỚI TANK FARM

 SHUTDOWN HỆ THỐNG TANK FARM KHI CÓ TÍN HIỆU BÁO CHÁY TỪ XƯỞNG SƠN GỨI
RA

XƯỞNG SƠN
TÍN HIỆU BÁO CHÁY

SDV-1003 XV-1001 SDV-1013 XV-1011 SDV-1023 XV-1021


ACTION : ACTION : ACTION : ACTION : ACTION : ACTION :
CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE
(ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN) (ĐÓNG VAN)

7. LIÊN ĐỘNG TRONG TANK FARM TỚI XƯỞNG SƠN

TANK FARM
TÍN HIỆU BÁO CHÁY

CÒI VÀ ĐÈN
ALRM TẠI TỦ TRONG TÒA BÁO LÊN HỆ
PCCC CỦA NHÀ THỐNG GIÁM
XƯƠNG SƠN SÁT VINFAST