You are on page 1of 2

Subsynchronous

resonances studies
Analyzing the risk of torsional oscillations
on multi-mass generator rotor shafts
Figure 1: Series compensated line and mode
shape diagram of generator-turbine rotor shaft

At a glance The challenge


Series compensation on transmission In a power system which includes
lines is a cost-effective method to series-compensated transmission lines,
increase the transmission capacity as resonance conditions may arise in the
well as enhance angle stability, but electrical circuit consisting of an
imposes relevant risks for the power inductance and a capacitance as
plants connected nearby in the trans- depicted in Figure 1. The shaft struc-
mission system. In such cases, Sub- ture of a turbine-generator unit has a
Synchronous Resonances (SSR) may number of inherent resonance fre-
arise, leading to oscillatory phenome- quencies, so-called natural frequen-
Figure 2: Electrical and shaft torque after a
na on the multi-mass shaft of genera- cies, which correspond to the eigen-
disturbance in the electrical network
tors which could be poorly damped, values or modes of the shaft system.
undamped or even amplified. Increas- Our solution
A system fault or sudden load change
ing torsional oscillation creates risk of There are four study techniques that
may excite transient power oscillations
fatigue and damage to the rotor shaft can be applied to analyze SSR phe-
at subsynchronous frequencies as
assembly of turbine-generator sets. nomena, they are:
shown in the electrical torque of
In conclusion “SSR is a transmission- Figure 2. The resonance frequency ∂ Passive frequency scan;
system-based problem that may depends on the degree of line com-
adversely affect turbine-generator sets pensation and typically ranges be- ∂ Transfer function analysis;
on that system”. For the investigation tween 10 and 45 Hz. If the frequency ∂ Eigenvalue analysis;
of this phenomenon Siemens PTI can corresponds to an undamped natural
provide expert power system consult- frequency of a generator shaft, the ∂ Simulation in time domain.
ing services including: electrical power system may interact The passive frequency scan method is
with the shaft and cause most widely used for preliminary
∂ Complete SSR investigation from
subsynchronous resonance.
preliminary analysis based on pas- investigation of SSR. It evaluates the
sive frequency scan up to detail This condition can be seen in the frequency-dependent impedance of
time domain simulations to confirm growing oscillation of the shaft torque the passive network in the frequency
the risks. in Figure 2 after the disturbance. range of interest as viewed from the
Whether or not SSR occurs depends on investigated generator.
∂ When necessary, recommendation
the system conditions after the dis- The transfer function analysis is based
of countermeasures as avoidance of
turbance. on small perturbation theory and
certain topology, bypass capacitors,
reduced power, generator trip, etc. determines the complex synchronizing
coefficients and damping torques of
the electrical system as seen from the
investigated generator.

siemens.com/power-technologies
Eigenvalue analysis is based upon the shows that the 33.6 Hz mode is within also to provide a technical solution to
calculation of the natural frequencies the range of excited rotor shaft fre- the SSR phenomenon that could
(modes) of the coupled electric system quencies so there is a potential risk of possibly arise. The key questions to be
and mechanical multi-mass-spring Torsional interaction between the rotor answered were:
system. shaft and the electrical network at this
∂ Considering the price is a TCSC
frequency.
Time-domain simulation uses full (Thyristor-Controlled Series Ca-
three-phase electrical representation pacitor) needed, or would per-
of network and generators, and per- haps an FSC suffice?
mits detailed modeling of the multi-
∂ Would an FSC solution cause
mass shaft systems. Detailed represen-
subsynchronous resonance?
tation of nonlinear effects is also
possible. SSR can be identified by ∂ Would a TCSC solution cause
observing the time response of the subsynchronous resonance?
torques at a particular shaft system. If
∂ How much better is a TCSC solu-
they persist or grow in time, then the
tion over an FSC solution regard-
system almost surely has an SSR
ing SSR?
problem as shown in Figure 3.
The analysis has been carried out for
Figure 4: Frequency scan with series
resonances
closest power plant to the proposed
location of the FSC.
In order to gain more insight of the
particular behavior of the Torsional It could be shown that the electrical
interaction, Transfer Function Analysis network may contribute to torsional
has been carried out. This analysis instability at the generator units if FSCs
evaluates the damping characteristics are installed. By contrast, the TCSC
of the electrical network and answers solution provides a far superior damp-
whether subsynchronous torsional ing of torsional oscillations especially
oscillations would damp out or possi- of the higher frequency shaft modes.
bly grow with time. Growing oscilla- For lower frequency shaft modes, say
Figure 3: Time-domain simulation tions would represent a below 10Hz, both the FSC solution and
subsynchronous resonance condition TCSC solution provide approx. equal
Application example 1 with the risk of fatigue and damage to torsional oscillation damping for the
The upgrade of a 230 kV transmission the rotor shaft assembly of a machine. generator units.
line by fixed series compensation (FSC)
The analysis for this generator unit has
to allow transfer of more power
shown that there is negative damping
motivates the analysis of SSR for 4
different nearby connected power for the 33.6 Hz-mode. The electrical
network has a strong negative damp-
plants. The analysis is performed based
ing component at this frequency, so
on passive frequency scan which
that the mechanical damping would
shows that contingencies with 4 or
not be sufficient to damp out
more line outages have a high poten-
subsynchronous torsional oscillations.
tial to exhibit a subsynchronous
Therefore, a likelihood of
resonance frequency in the electrical
network as seen from the analyzed subsynchronous resonance must be
expected at this unit. Published by
generator unit. An excitation of this
Siemens AG 2018
frequency would have a corresponding This generator unit should be
rotor shaft excitation frequency which equipped with an SSR relay to trip the Energy Management Division
is the system frequency (60 Hz in this unit in the event of growing torsional Freyeslebenstrasse 1
case) minus the network resonance oscillations and to protect it from 91058 Erlangen, Germany
frequency. Rotor shafts that possess experiencing fatigue or severe dam-
natural torsional frequencies in the age. Furthermore, means of mitigation For more information, please contact
ranges are likely to response to an should be studied such as bypassing power-technologies.energy@siemens.com
excitation from the network side. For the series capacitors in the event of a AL=N, ECCN=N
one generation unit of power plant No. high number of simultaneous equip- Subject to changes and errors. The infor-
4 the electrical network resonance ment outages. mation given in this document only
range is 25.0 Hz – 30.9 Hz (Figure 4)
contains general descriptions and/or
and the excited frequency range at the Application example 2 performance features which may not
rotor shaft is 29.1 Hz – 35.0 Hz. The During a tender request for 400kV always specifically reflect those described,
natural torsional rotor shaft frequen- series compensation equipment (35% or which may undergo modification in the
cies of the generation unit are 18.9 Hz, compensation level), Siemens offered course of further development of the
33.6 Hz, 42.6 Hz and 43.9 Hz. A suitable equipment not only to meet products. The requested performance
comparison with the above range the specification requirements, but features are binding only when they are
expressly agreed upon in the concluded
contract.

You might also like