Sounder Base ULCAS380, ULMAS850, ULFXN538LBS Effective April 2019

Installation Instructions
Model No. Brand
ULCAS380 Eaton Cooper 2. Sounder Assembly
ULMAS850 Eaton Menvier Clip sounder onto base. If sounder needs to be removed use a
ULFXN538LBS Eaton JSB small screwdriver to unclip.

Installation
1. Fit the box in position using the mounting details below. 50
2. Connect the unit according to the diagram below. 60
70
3. Recommended Loop Cable Type: FIRETUF, FP200
80
1. Mounting Base

I. Knock-out the required fixing holes.


II. Fix to mounting surface using two suitable screws

If the base deforms on an uneven surface. Loosen the screws or


move to a more flat position.
50 50
When used with a detector, the installation and spacing shall be
in accordance
60 60 with the requirements for smoke detectors (NFPA
72, Chapter 17).
70 70
80 80 with the blank cover,the installation and spacing
When installed 3. Locking Tab (optional)
shall be in accordance50notification appliances
Fit the locking tab into the square
(NFPA 72, Chapter 18.)60
hole on the shoulder.
70 50
Finish assembly as stage 5.
80 60
70 Remove by inserting a suitable tool
80 (e.g. A thin screwdriver) into the hole
in the detector or cover, then rotate
detector or cover anti-clockwise.

4. Fitting Detector or Cover

ø 102

50 Locking tab
release hole
60
70
43

80 Locking tab
release holetab
Locking
Locking tab
release hole
release hole Sounder and Cover
ø 102

ø 102 5. Standard Connections (see diagram overleaf)


Warning: Do NOT use high voltage tester if ANY equipment is
ø 102 connected to the system.
61-71

ø 102 ø 102 All connections are Power Limited.


ø 102
43

When the base is used with the blank cover: Multiple tone
ø 102 ø 102 appliances which produce the three pulse temporal pattern for
61-71

the international evacuation signal [NFPA 72 (National Fire Alarm


Sounder and Cover Sounder and Detector Code)], shall be used for evacuation use only. The base must not
61-71
43

61-71

be used for evacuation when used with a detector head.


ompatible Analogue

Terminate the screen as a floating


Addressable Panel

Loop Start

joint to the rear ofNthe


ote: base within theof the interface is required. See control
43

No addressing S+panel
43

Sounder and Cover Sounder and Detector


cable termination
operation box
for details.
S-
Terminate the screen as a floating
Sounder and Cover Sounder and Detector joint to the rear of the base within the
Sounder and Cover Sounder and Detector Do not usecable
this termination box
op Finish

Terminate the screen as a floating F-


connection
in out joint tothe
Terminate thescreen
rear of the
as abase within
in out
floating the Locking tab
61-71
Installation Instructions

43
Effective April 2019

Sounder and Cover Sounder and Detector

Terminate the screen as a floating


joint to the rear of the base within the
cable termination box

Do not use this


connection
in out in out
- + - + - + - +
2 2
Compatible Analogue

3 3
Addressable Panel

Loop Start

S+
S-
E E
Loop Finish

F- 4
4 1 1
F+

Do not use this


connection

ULCAS380, ULMAS850, ULFXN538LBS This model is restricted for use


Sounder base Specification with the following UL Listed Panels Panel Compatibility
Voltage 21-32Vdc Cooper ULCF30002G, ULCF30004G, ULCF30002GP,
ULCF30004GP, ULCF30002GNC, ULCF30004GNC,
Current (Nominal) 388 μA ULCF30002GPNC, ULCF30004GPNC, ULCF30002GRM,
UL 464 Sound Output (dBA) ULCF30004GRM, ULCF30002GPRM, ULCF30004GPRM,
ULCF30002GNCRM, ULCF30004GNCRM,
Settings Continuous Tone@3m Three Tone Temporal @3m ULCF30002GPNCRM, ULCF30004GPNCRM, ULR3000L2,
High 79.0 75.4 ULR3000L4, ULR3000L2NC, ULR3000L4NC
Medium 77.2 74.0 Menvier ULDF60002G, ULDF60004G, ULDF60002GNC,
ULDF60004GNC, ULDF60002GP,
Low 71.7 71.3 ULDF60004GP,ULDF60002GPNC,
ULDF60004GPNC, ULDF60002RM, ULDF60004RM,
Volume Tone
(Ratings were obtained with the ULDF60002NCRM,ULDF60004NCRM,
blank cover ULCASC and do not Three Tone Temporal Three Tone Temporal @3m ULDF60004NCRM, ULDF60002PRM, ULDF60004PRM,
apply when used with a Tone (mA) ULDF60002PNCRM,ULDF60004PNCRM, ULR6000L2,
detector head.)
ULR6000L4, ULR6000L2NC, ULR6000L4NC
Low 13.24 13.68 JSB ULFX60002G, ULFX60004G, ULFX60002GNC,
Medium 13.52 13.60 ULFX60004GNC, ULFX60002GP,
High 13.96 13.92 ULFX60004GP,ULFX60002GPNC,
ULFX60004GPNC, ULFX60002RM, ULFX60004RM,
Environmental ULFX60002NCRM,ULFX60004NCRM, ULFX60002PRM,
ULFX60004PRM, ULFX60002PNCRM,
Max Ambient Temperature 37.8°C (100F) ULFX60004PNCRM,ULFXR6000L2, ULFXR6000L4,
Humidity 0-93%RH ULFXR6000L2NC, ULFXR6000L4NC
(Non Condensing)
This model is suitable for use with
the following detector heads Detector Head Compatibility
Standards
Cooper ULCAP320, ULCAH330, ULCAPT340
Approved to UL464, UL521, UL268
Menvier ULMAP320, ULMAH330, ULMAP340
Physical
JSB ULFX320, ULFX330, ULFX340
Weight 206g
Ingress Protection Type A (IP21C) Order Codes Product Brand
ULCAS380 Addressable Sounder Base Cooper
Field Wiring SLC Circuit (input)
ULMAS850 Addressable Sounder Base Menvier
Wiring Gauge 12 Max AWG
ULFXN538LBS Addressable Sounder Base JSB
Wiring Class Class A Style 7
ULCASC Lid for Sounder Base -
Ground Fault Impedance 0.1 Ohm
Supervised, power limited Yes

Eaton © 2019 Eaton


EMEA Headquarters All Rights Reserved
Route de la Longeraie 7 Eaton is a registered trademark.
Eaton Electrical Systems Ltd. 1110 Morges, Switzerland
Wheatley Hall Road Eaton.eu All trademarks are property
Doncaster TEL: +44 (0) 1302 321541 of their respective owners.
DN2 4NB FAX: +44 (0) 1302 303220 www.Eaton.com
TEL: +44 (0) 1302 303303 Firesales@eaton.com
FAX: +44 (0) 1302 367155 Firetechsupport@eaton.com Installation Instructions 25-10822-B April 2019