SGH DUBAI EXPANSION

HEAT PUMP & CALORIFIERS FOR HOT WATER SYSTEM (TOWER-A & TOWER-B)
Volume of Electric Trimming Heat Pump Input POWER
Quantity Of Calorifier Capacity (qi) / SUPPLY
SL# TAG TYPE LOCATION REMARK
Calorifier Heating coil
Liters KW V / PH / HZ
Capacity (KW)

* For tower A (One calorifier +one Heat pump) & For


One Set In Tower A
194 KW tower B (One calorifier +one Heat pump)
Heat Pump & Calorifiers Two Nos Lower Roof
2775 35 KW (Each)
1 HPWH - 1 With 15% Electric (Two Set) 400/3/50 &
(Each) (In Each calorifiers) * Heat pump shall be water to water type
Trimming Each set 1 Nos One Set for Tower B
(2 No. Heat Pump)
Lower Roof
* At site central chilled water system available

NOTES:-

1. All Heat Pumps & Calorifiers shall be supply with complete accessories, all valves, controls, all switches, and electric control panel .

2. All Heat Pumps & Calorifiers shall be painted, fully equipped with all accessories & fully wired, factory aligned and factory assembled.

3. All Heat Pumps & Calorifiers shall be as per A.S.M.E Construction , U.L Certificate and PN-16 .

4. BMS interface required to control and monitor the system via main BMS unit.

Abbreviation
HPWH Heat Pump Water Heater
KW Kilowatts

SGH Dubai Expansion 1/1 Plumbing