附件2

海水篩濾器之篩濾器及馬達數據規格表

附件2 海水篩濾器之篩濾器及馬達數據規格表
台灣中油
股份有限公司 海水篩濾器之篩濾器及馬達數據規格表 ITEM NO.
PROJ. NO.
SHEET NO. 1 OF 2

AUTOMATIC FILTER DATA SHEET


1 No. Req'd 4 Item No. M-224 Type Drum type and self-cleaning
2
3 PERFORMACE
4 1.Fluid Filtered: Seawater SP.GR.: 1.025 Viscosity: 1.2 cp
5 2.Temp. ℃ Max. 30.8 Min. 19.1
6 3.Filter Outlet Flow Rate m3/h Nor. 3000 Des. 3300
2
7 4.Upstream Pressure kg/cm Nor. 4.75 Max. 6.0
2
8 5.Maximum Allowable Pressure Drop kg/cm (clean) 0.15
9 6.Pressure Drop Access Filter kg/cm2 (50% clogged) 0.5
10 7.Backwash Design Flow Rate: m3/h
11 8.Sludge Capacity: m3
12 9.Description of Backwash Cycle Control:
13
Backwash of filter shall be controlled by timed automatically-operated control valve. A high differential
14
pressure and high high differential pressure switch will be activated and set alarm in CCR for the set
15 alarm in CCR for point reach 0.35 kg/cm2 and 0.5 kg/cm2 respectively.
16
17 FILTER ELEMENT DATA
18 1.Filter Element Type
19 2.No. of Filter Element Per Filter Unit
20 3.No. of Filter Element Circumferential Row
21 4.Filter Element Overall Height mm
22 5.Filter Element Outside Diameter mm
23 6.Total Filtering Area of Media m2
24 7.Total Filter Opening Area m2
25 8.Filter Slot Opening Width mm ( mesh)
2
26 9.Filter Design Press. kg/cm G
27 BACKWASH DATA
28 1.Sludge Drains Size in No. Req'd
29 2.Continuous Blow Down Size in No. Req'd
30 3.Backwash Drain Control Valve
31 4.Backwash Device Speed of Rotation rpm
32 5.Normal Backwash Time minutes"on" minutes"off"

Notes: The blanks of this data sheet shall be completely filled in and certified before completion of works.

BY CHK APPR DATE REV REV REV


台灣中油
股份有限公司 海水篩濾器之篩濾器及馬達數據規格表 ITEM NO.
PROJ. NO.
SHEET NO. 2 OF 2

INTRODUCTION MOTOR DATA SHEET(馬達數據規格表)


SERVICE/EQUIPMENT NO. Seawater Filter Motor
SPECIFICATION REQUIREMENTS VENDER'S RESPONSE
DESCRIPTION
SPECIFICTION YES NO EXPLANATION
x Salty x Chemical corrosive
Environment x Dusty x Non hazardous
Location Indoor x Outdoor
Ambient Temperature Max. 35.3 ℃, Min. 5.7 ℃
Relative Humidity Avg. 86 %
Vendor Shall Complete these sheets entering all applicable data and indicating all deviations from
Purchaser's requirements. Relative requirement is Specified in seawater filter specification(appendix
4).
hp/kW,460V,3ɸ,60Hz,
Rating
Syn. Speed: rpm
Duty x Continuous
Starting Method x Direct on line
x IP54
Enclosure
x Non-sparking
Noise Level dB(<85 dBA@1 m from major surface )
Rotor Type x Squirrel-cage
Insulation x F
Max. Temperature Rise 80 ℃
Cable entry of Junction box x NPT
Lubrication Type Grease
Finishing Painting MUNSELL NATION N6.5, LIGHT GRAY
Grounding Tap x On Frame x In terminal Box