Professional Documents
Culture Documents
2
Legislative Requirement
• Refer to COP-FSI for the requirement of installation of the
FH/HR system
• Section 5.14 Fire Hydrant / Hose Reel System
• Section 5.25 Street Fire Hydrant System
• Section 5.26 Supply Tank
• Section 5.30 Water Supply
3
Hose Reel Application
• Hose reels enable first hand fire fighting by occupants
• Hose reels are provided to ensure that every location in a floor is
within the reach of the hose.
• Each hose reel has a 30m long tube (a shorter tubing is also
available in the market)
• A minimum of 6m length water jet from the hose reel nozzle has to
be provided (what is the water pressure required ???)
4
Instruction using the Hose Reel
5
Fire Hydrant Application
• Fire Hydrants are designed for firemen’s use without having to
connect the water hose from ground level during fire fighting
• Fire hydrants are installed inside every protective staircases so
that firemen can plug in their 65mm fire hose to obtain water
• Fire hydrants are sited in the approach lobby to staircase or in
the staircase enclosure.
6
• Either wet or dry riser can be used in the fire hydrant
system.
• Wet riser is permanently charged with water and water
pumping device is installed to maintained the required
pressure.
• Dry riser can only be used where there is a reliable
local fire brigade as it depends on the charging of water
into the riser by the fire brigade during fire.
• In Hong Kong, wet riser is generally used. Wet riser is
located in a protected staircase with the numbers of
hydrant outlet governed by the types of buildings served
• Please refer to FSD Circular letter No. 2/2013 7
• Occupants may pull out the hose from the hose reel to
fight the fire.
10
Hose Reel using building water supply
Water Tank
FS Pump (ON)
Water
Flow
ON THE WAY…..
Hose Heel
11
Fire Brigade Operation
• Upon arrival of the fire brigade, firemen will carry their
fire hoses into the building and connect them to the
hydrants for use
• At the same time, firemen will connect other hoses
from the street hydrant to the fire engine, and from the
fire engine to the fire service inlet to ensure a readily
available water supply
• Although the building fixed fire pump is to be used, it
may be de-energized according to fire fighting
operation and water will be pumped through the fire
service inlet into the system
12
Fire Hydrant using building water supply
Water Tank
FS Pump (ON)
Water
Flow
Connection to Street Hydrant
ON THE WAY…..
Fire Hydrant
13
Fire Hydrant using water supply from FSI
Pump Tender is a Water Tank
large diesel pump
with a water tank FS Pump (OFF)
Street Hydrant
FS Inlet
Water from Street Hydrant
ARRIVED Fire Hydrant
Water
Flow
14
Fire Services and Sprinkler Inlet –
Connection of Water Supply from Street Fire
Hydrant through Fire Engine
Fire
Service
Inlet
Sprinkler Inlet
15
Intermediate Pump Requirement
• When the building is greater than 60m in height (from the
lowest FSI to the highest FH), an intermediate booster pump is
required to booster water to the upper floors
• This is due to the insufficient pressure available from the fire
engine which is designed to provide a pumping pressure of
800kPa at the location of the Fire Service Inlet.
FS Inlet
FH
800kPa 350 – 850kPa
17
18
19
Same examples of
system arrangements
20
Same examples of
system arrangements
21
Same examples of
system arrangements
22
Fire Hydrant
• To be used by firemen
Type : Fire hydrant should incorporate with individual
control valve.
Older twin outlet with plugs type are obsolete.
• Head loss of each outlet is approximately :
25kPa at 450L/min or 60kPa at 900 L/min (some use
150kPa at 450L/min) (no actual data available!!!)
• Position : Fire hydrant should be located at the staircase
main landing or direct one half landing below.
• Mounted at not more than 1200mm AFFL and not less
than 800mm AFFL
• For pressure reduction : parity valve type and pressure
reducing fire hydrant
23
Fire Hydrant
with
Parity Valve
and
Parity Drain
Pipe
24
PRESSURE
REGULATING
TYPE FIRE
HYDRANT
FIRE HYDRANT
WITH PARITY
VALVE
25
Hose Reel
• Intended to be used by occupants
• Swing type to be used if recessed (to make
winding/unwinding of the hose easily)
• Position : No rule for the height of the hose reel drum, but it
affect the reaching distance of the hose reel.
• Nozzle and valve shall not exceed 1350mm AFFL
• If hose reel is recessed, the nozzle and valve shall be reached
within 500mm.
• Be careful to decide the positions of hose reel that point to point
distance shall not exceed 30m.
• Manual Call Point : Located at not exceeding 1200mm
AFFL (good for disabled people). The actuation of the
manual call point should automatically call upon the
activation of the fire pump even in gravity feed zone. 26
27
Break Glass Unit and Hose Reel
1,200mm
AFFL
28
Hose Reel System
• Requirement if only hose reel system is installed:
Hose reel feed tank shall be 2,000L and this estimation is based
on two numbers of hose reels each at a flow rate of 24L/min in
operation and last for 40 minutes. Supply pipe size shall be
25mm dia. for one hose reel and 40mm dia. for two.
• There are a few updates of the required tank size mainly due to
the enforcement of Fire Safety (Buildings) Ordinance (CAP752)
for existing buildings.
Reference should be made to FSD Circular Letters 5/2016
and 3/2017.
29
Fixed Fire Pump
• Position : Enclosed in a pump room with 2 hours FRP solely for fire
services equipment.
• Flow rate requirement : 1,350L/min (3 x 450 L/min) for industrial
building and 900L/min (2 x 450 L/min) for other building types.
• Pump set shall be duplicated for duty and stand-by. Duty pump failed
to operate within 15 seconds the standby pump shall start to take over
the duty pump
30
Fixed Fire Pump
• Motor power : motor power should be 20% more power required at
rated flow.
• Status : Status indications required either on panel if any, or in main
entrance of building.
• Shall be started automatically once any fire call point is actuated
• Once started, must run continuously until stopped manually at the
pump control panel installed near the fixed fire pump
31
Acceptance Testing
• Refer to Appendix 5 of
the CoP for Inspection,
Testing and
Maintenance of
Installations and
Equipment (second
part of the CoP FSI)
Buildings other 33
than Industrial /
Godown Buildings
Industrial /
Godown Buildings
34
Intermediate Booster Pump
• Provided when height between the topmost
hydrant outlet and the lowest fire service inlet
> 60m
• Comprise of
• start/stop push button
• pump running light
• alarm buzzer
• Once started, it must be running continuously until
stopped manually
• Control circuit shall keep the pump running even
upon power change from normal to emergency
power supply
35
Intermediate Booster Pump
With fire engine boosting water into the FS Inlet at 800kPa (constant),
the pump shall be capable of producing the following water flow:
37
• Stand-by pump requirement : Should be 100%
stand-by or at least one identical pump as per the
pumps set (2 or 3 are allowed) and by-pass valve
must be installed.
• Control : The On/Off operation button must installed
at relevant Fire Services Inlet and the intermediate
booster pump is allowed to be assumed in
sequential start within a time delay limitation of 30
seconds.
38
Fire Services Inlet with On/Off Control
for Intermediate Booster Pump
39
DESIGN CONSIDERATION FOR
INTERMEDIATE BOOSTER PUMP
• Recommended
46
47
Statutory Requirement
49
• Where minimum standards are not possible, water
supply may have to be augmented by other means e.g.
sump tank and pumps.
• All hydrant should be installed in accordance with
WSD standard.
• At least 2 hydrants within the site
• Fixed not less than 6 meters from the building they are
intended to protect.
• Red colour for fresh water, yellow colour for salt water
50
Calculation of Hydrant Loss
• The following is a simplified calculation of the head loss of a
street fire hydrant.
51
• 1 sudden contraction,
coefficient = 0.2
• 1 spherical tee,
coefficient = 2.5 to 4.9
Head loss =
(0.2+2.5)*172/2g=
39.8mH
(Approx. 4 bar)
52
FIRE HYDRANT / HOSE REEL SYSTEM
(SYSTEM DESIGN, PUMPING CALCULATIONS)
53
Legislative Requirement
• The following clauses from the COP-FSI shall be referred to
when designing FH/HR system
• 5.11 Fire Alarm System – specifying the manual fire alarm
system including the ‘Manual Fire Alarm Call Point’
• 5.14 Fire Hydrant / Hose Reel System – specifying the
individual components of the system including pump flow rate,
pipe sizing, pressure requirements, etc.
• 5.26 Supply Tank – specifying the supply tank for the FH/HR
system
54
Technical Details (For System Design)
Hydrant
• Sited in an approach lobby to a staircase or in the
staircase enclosure
• Every escape staircase shall be provided by fire
hydrant at every floor
• In older industrial buildings, one single hydrant with FH without
two outlets had been used (but due to high pressure
parity valve
loss, they became obsolete)
• Operating pressure at the outlet of each hydrant is
between 350kPa and 850kPa
• In case of over pressure (>850kPa even at static
condition), parity valve and drain pipe will have to be
installed
• A usual assumption for head loss in the FH is 25kPa
@ 450L/min (standard flow rate)
(we never know what is the pressure drop! The local FH with 55
40mm (min)
irrespective of zoning
HR with
Manual
Alarm Call
25mm 56
Point and
(min)
Alarm Bell
Technical Details (For System Design)
Fixed Fire Pump
• Flow requirement
• Industrial / godown – 3 FH @ 450L/min (1350L/min)
• Others – 2 FH @ 450L/min (900L/min)
FS Tank
57
Technical Details (For System Design)
Intermediate Booster Pump
• Required ONLY when topmost FH is 60m higher than lowest FS Inlet
• Location will be somewhere from G/F (or even basement) to lower than 60m
• Flow requirement
• Industrial / godown – 3 FH @ 450L/min (1350L/min) for 1 rising main
• Industrial / godown – 6 FH @ 450L/min (2700L/min) for 2 rising main (double of Fixed Fire Pump)
• Domestic – 2 FH @ 450L/min (900L/min)
• Others – 2 FH @ 450L/min (900L/min) for 1 rising main
• Others – 4 FH @ 450L/min (1800L/min) for 2 rising main (double of Fixed Fire Pump)
59
Technical Details (For System Design)
Pipe Losses
• Hazen Williams formula (used in sprinkler calculation but
applies to other piping calculation also)
𝐿𝐿 × 𝑄𝑄 1.85
𝑃𝑃 = 6.05 × 105 × 1.85 4.87
𝐶𝐶 𝑑𝑑
Those figures in red are common combinations of chosen pipe size and the anticipated flowrate.