PENYALURAN DAN PUSAT PENGATUR BEBAN JAWA BALI
Berlaku Efektif Juni 2010
Cinere 16514 – Jakarta Selatan
DISTURBANCE FAULT RECORDER SPESIFICATIONS

A. Signal Digital Input (1 DFR untuk 2 Bay).

DFR dengan Fasilitas 16 Digital Input Tiap bay line 150 kV (One & A Half Breaker) minimal
harus terdiri dari :

No Nama Lengkap Digital Input Nama Digital di DFR Contoh *)


1 Main Protection Operated LP OPRT [Nama Bay] LP OPRT GNDUL1
2 CB 5Ax/Bx open CB 5Ax/Bx OPEN CB 5A1 OPEN
3 CB 5ABx open CB 5ABx OPEN CB 5AB1 OPEN
4 OLS Operated OLS OPRT [Nama Bay] OLS OPRT GNDUL1
5 Back 2 Protection Operated (OCR Back Up) OCR OPRT [Nama Bay] OCR OPRT GNDUL1
6 A/R In Progress A/R OPRT [Nama Bay] A/R OPRT GNDUL1
7 Carrier Send from Distance LP SEND [Nama Bay] LP SEND GNDUL1
8 Carrier Receive to Distance LP RCV [Nama Bay] LP RCV GNDUL1
9 CCP operated CCP OPRT [Nama Bay] CCP OPRT GNDUL1
10 Send DTT DTT SEND [Nama Bay] DTT SEND GNDUL1
11 Receive DTT. DTT RCV [Nama Bay] DTT RCV GNDUL1
12 SF6 Low Stage 2 150 kV Operated SF6 2ND 150 OPRT SF6 2ND 150 OPRT
13 CBF/SZP 5Ax/5Bx Trip CBF/SZP 5Ax/5Bx OPRT CBF/SZP 5A1 OPRT
14 CBF/SZP 5ABx Trip CBF/SZP 5ABx OPRT CBF/SZP 5AB1 OPRT
15 UFR UFR OPRT [Nama Bay] UFR OPRT GNDUL1
16 SPARE SPARE SPARE

- DFR dengan Fasilitas 16 Digital Input untuk 2 bay Line 150 kV (Double Bus) minimal harus
terdiri dari :

No Nama Lengkap Digital Input Nama Digital di DFR Contoh *)


1 Main Protection Operated LP OPRT [Nama Bay] LP OPRT GNDUL1
2 CB OPEN CB [Nama Bay] OPEN CB GNDUL1 OPEN
3 OLS Operated OLS OPRT [Nama Bay] OLS OPRT GNDUL1
4 Back 2 Protection Operated (OCR OCR OPRT [Nama Bay] OCR OPRT GNDUL1
Back Up)
5 A/R In Progress A/R OPRT [Nama Bay] A/R OPRT GNDUL1
6 Carrier Send from Distance LP SEND [Nama Bay] LP SEND GNDUL1
7 Carrier Receive to Distance LP RCV [Nama Bay] LP RCV GNDUL1
8 CCP operated CCP OPRT [Nama Bay] CCP OPRT GNDUL1
9 CBF Trip CBF OPRT [Nama Bay] CBF OPRT GNDUL1
10 Send DTT DTT SEND [Nama Bay] DTT SEND GNDUL1
11 Receive DTT. DTT RCV [Nama Bay] DTT RCV GNDUL1
12 SF6 Low Stage 2 150 kV Operated SF6 2ND 150 OPRT SF6 2ND 150 OPRT
13 UFR UFR OPRT [Nama Bay] UFR OPRT GNDUL1
14 SPARE SPARE SPARE
15 SPARE SPARE SPARE
16 SPARE SPARE SPARE

Edisi : 00 Revisi : 00 Halaman : 1 – 4


RUANG LINGKUP SERTIFIKASI ISO 9001:2000
PENGEMBANGAN DAN PEMBINAAN INSTALASI PENYALURAN TENAGA LISTRIK
SISTEM JAWA BALI DI PT PLN (PERSERO) P3B JAWA BALI
PT PLN (PERSERO) No. Dokumen P3BJB-TEK/04/90/2007/032
PENYALURAN DAN PUSAT PENGATUR BEBAN JAWA BALI
Berlaku Efektif Juni 2010
Cinere 16514 – Jakarta Selatan
DISTURBANCE FAULT RECORDER SPESIFICATIONS

- DFR dengan Fasilitas 16 Digital Input untuk bay IBT 150/70 kV (One & A Half Breaker) minimal
harus terdiri dari :

No Nama Lengkap Digital Input Nama Digital di DFR Contoh *)


1 Main Protection (DIFF) Operated. DIFF OPRT [Nama Bay IBT] DIFF OPRT IBT1
2 Main Protection (REF HV) Operated. REF 150 OPRT REF 150 OPRT
3 Main Protection (REF LV) Operated. REF 70 OPRT REF 70 OPRT
4 CB HV 5Ax/5Bx Open. CB 150 5Ax/5Bx OPEN CB 150 5A1 OPEN
5 CB HV 5ABx Open. CB 5ABx HV OPEN CB 150 5AB1 OPEN
6 CB LV Open CB LV OPEN CB 70 OPEN
7 Back Up Protection HV Operated. OC 150 OPRT [Nama Bay IBT] OC 150 OPRT IBT1
8 Back Up Protection LV Operated. OC 70 OPRT [Nama Bay IBT] OC 70 OPRT IBT1
9 Over Voltage Operated. OV OPRT [Nama Bay IBT] OV OPRT IBT1
10 Bucholz Operated. BUCHOLZ [Nama Bay IBT] BUCHOLZ IBT1
11 Jansen Operated. JANSEN [Nama Bay IBT] JANSEN IBT1
12 Thermal Relay Operated. THERMAL [Nama Bay IBT] THERMAL IBT1
13 Suddent Pressure Operated. SUDDENT [Nama Bay IBT] SUDDENT IBT1
14 CCP Operated CCP OPRT CCP OPRT IBT1
15 CBF/SZP 5Ax/5BxTrip CBF/SZP 5Ax/5Bx OPRT CBF/SZP 5A1 OPRT
16 CBF/SZP 5ABxTrip CBF/SZP 5ABx OPRT CBF/SZP 5AB1 OPRT

- DFR dengan Fasilitas 16 Digital Input untuk bay IBT 150/70 kV (Double Bus) minimal harus
terdiri dari :

No Nama Lengkap Digital Input Nama Digital di DFR Contoh *)


1 Main Protection (DIFF) Operated. DIFF OPRT [Nama Bay IBT] DIFF OPRT IBT1
2 Main Protection (REF HV) Operated. REF 150 OPRT [Nama Bay IBT] REF 150 OPRT IBT1
3 Main Protection (REF LV) Operated. REF 70 OPRT [Nama Bay IBT] REF 70 OPRT IBT1
4 CB HV Open. CB 150 OPEN CB 150 OPEN
5 CB HV Close CB 150 CLOSE CB 150 CLOSE
6 CB LV Open CB 70 OPEN CB 70 OPEN
7 CB LV Close CB 70 CLOSE CB 70 CLOSE
8 Back Up Protection HV Operated. OC HV OPRT [Nama Bay IBT] OC 150 OPRT IBT1
9 Back Up Protection LV Operated. OC LV OPRT [Nama Bay IBT] OC 70 OPRT IBT1
10 Over Voltage Operated. OV OPRT [Nama Bay IBT] OV OPRT IBT1
11 Bucholz Operated. BUCHOLZ [Nama Bay IBT] BUCHOLZ IBT1
12 Jansen Operated. JANSEN [Nama Bay IBT] JANSEN IBT1
13 Thermal Relay Operated. THERMAL [Nama Bay IBT] THERMAL IBT1
14 Suddent Pressure Operated. SUDDENT [Nama Bay IBT] SUDDENT IBT1
15 CBF Trip CBF OPRT CBF OPRT IBT1
16 SPARE SPARE SPARE

Edisi : 00 Revisi : 00 Halaman : 2 – 4


RUANG LINGKUP SERTIFIKASI ISO 9001:2000
PENGEMBANGAN DAN PEMBINAAN INSTALASI PENYALURAN TENAGA LISTRIK
SISTEM JAWA BALI DI PT PLN (PERSERO) P3B JAWA BALI
PT PLN (PERSERO) No. Dokumen P3BJB-TEK/04/90/2007/032
PENYALURAN DAN PUSAT PENGATUR BEBAN JAWA BALI
Berlaku Efektif Juni 2010
Cinere 16514 – Jakarta Selatan
DISTURBANCE FAULT RECORDER SPESIFICATIONS

- DFR dengan Fasilitas 16 Digital Input untuk bay Trafo 150/20 kV (One & A Half Breaker) minimal
harus terdiri dari :

No Nama Lengkap Digital Input Nama Digital di DFR Contoh *)


1 Main Protection (DIFF) Operated. DIFF OPRT [Nama Bay IBT] DIFF OPRT IBT1
2 Main Protection (REF HV) Operated. REF 150 OPRT REF 150 OPRT
3 Main Protection (REF LV) Operated. REF 20 OPRT REF 20 OPRT
4 CB HV 5Ax/5Bx Open. CB 150 5Ax/5Bx Open. CB 150 5A1 OPEN
5 CB HV 5ABx Open. CB 150 5ABx Open. CB 150 5AB1 OPEN
6 CB 150 kV 5Ax/5Bx Close CB 150 5Ax/5Bx CLOSE CB 150 5A1 CLOSE
7 CB LV Open CB 20 Open CB 20 OPEN
8 OLS OLS OPRT OLS OPRT
9 Back Up Protection HV Operated. OC 150 OPRT OC 150 OPRT
10 Back Up Protection LV Operated. OC 20 OPRT OC 20 OPRT
11 Bucholz Operated. BUCHOLZ [Nama Bay IBT] BUCHOLZ IBT1
12 Jansen Operated. JANSEN [Nama Bay IBT] JANSEN IBT1
13 Suddent Pressure Operated. SUDDENT [Nama Bay IBT] SUDDENT IBT1
14 CCP Operated CCP OPRT [Nama Bay IBT] CCP OPRT IBT1
15 CBF/SZP 5Ax/5BxTrip CBF/SZP 5Ax/5Bx OPRT CBF/SZP 5A1 OPRT
16 CBF/SZP 5ABxTrip CBF/SZP 5ABx OPRT CBF/SZP 5AB1 OPRT

- DFR dengan Fasilitas 16 Digital Input untuk bay Trafo 150/20 kV (Double Bus) minimal harus
terdiri dari :

No Nama Lengkap Digital Input Nama Digital di DFR Contoh *)


1 Main Protection (DIFF) Operated. DIFF OPRT [Nama Bay IBT] DIFF OPRT IBT1
2 Main Protection (REF HV) Operated. REF 150 OPRT [Nama Bay IBT] REF 150 OPRT IBT1
3 Main Protection (REF LV) Operated. REF 20 OPRT [Nama Bay IBT] REF 20 OPRT IBT1
4 CB HV Open. CB 150 OPEN CB 150 OPEN
5 CB HV Close CB 150 CLOSE CB 150 CLOSE
6 CB LV Open CB 20 OPEN CB 20 OPEN
7 CB LV Close CB 20 CLOSE CB 20 CLOSE
8 OLS OLS [Nama Bay IBT] OLS OPRT IBT1
9 Back Up Protection HV Operated. OC 150 OPRT [Nama Bay IBT] OC 150 OPRT IBT1
10 Back Up Protection LV Operated. OC 20 OPRT [Nama Bay IBT] OC 20 OPRT IBT1
11 Bucholz Operated. BUCHOLZ [Nama Bay IBT] BUCHOLZ IBT1
12 Jansen Operated. JANSEN [Nama Bay IBT] JANSEN IBT1
13 Thermal Relay Operated. THERMAL [Nama Bay IBT] THERMAL IBT1
14 Suddent Pressure Operated. SUDDENT [Nama Bay IBT] SUDDENT IBT1
15 CBF Trip CBF OPRT CBF OPRT IBT1
16 UFR UFR UFR OPRT

Edisi : 00 Revisi : 00 Halaman : 3 – 4


RUANG LINGKUP SERTIFIKASI ISO 9001:2000
PENGEMBANGAN DAN PEMBINAAN INSTALASI PENYALURAN TENAGA LISTRIK
SISTEM JAWA BALI DI PT PLN (PERSERO) P3B JAWA BALI
PT PLN (PERSERO) No. Dokumen P3BJB-TEK/04/90/2007/032
PENYALURAN DAN PUSAT PENGATUR BEBAN JAWA BALI
Berlaku Efektif Juni 2010
Cinere 16514 – Jakarta Selatan
DISTURBANCE FAULT RECORDER SPESIFICATIONS

- DFR dengan Fasilitas 32 Digital Input untuk bay Trafo 70/20 kV (Double Bus) minimal harus
terdiri dari :

No Nama Lengkap Digital Input Nama Digital di DFR Contoh *)


1 Main Protection (DIFF) Operated. DIFF OPRT DIFF OPRT
2 Main Protection (REF LV) Operated. REF 20 OPRT REF 20 OPRT
3 CB HV Open. CB 70 OPEN CB 70 OPEN
4 CB HV Close CB 70 CLOSE CB 70 CLOSE
5 CB LV Open CB 20 OPEN CB 20 OPEN
6 CB LV Close CB 20 CLOSE CB 20 CLOSE
7 Back Up Protection HV Operated. OC 70 OPRT OC 70 OPRT
8 Back Up Protection LV Operated. OC 20 OPRT OC 20 OPRT
9 Bucholz Operated. BUCHOLZ OPRT BUCHOLZ OPRT
10 Jansen Operated. JANSEN OPRT JANSEN OPRT
11 Thermal Relay Operated. THERMAL OPRT THERMAL OPRT
12 Suddent Pressure Operated. SUDDENT OPRT SUDDENT OPRT
13 SPARE SPARE SPARE
14 SPARE SPARE SPARE
15 SPARE SPARE SPARE
16 SPARE SPARE SPARE

Edisi : 00 Revisi : 00 Halaman : 4 – 4