Professional Documents
Culture Documents
SITUATION
Given that f’c=28 MPa and fy=275 MPa, determine the ultimate axial
SPIRAL COLUMN load capacity of the column:
1. A square tied column, 400mm on each side reinforced with 8-
㼠 䘨ྫྷ ᙉ 25mm diameter longitudinal bars.
2. A round spiral column having a diameter of 450 mm reinforced
with 6-25mm diameter longitudinal bars.
NSCP 2001/2010/2015
SITUATION
A reinforced concrete tied column carries a dead axial load of 800 kN
and live axial load of 1025 kN. Use fc’ = 28 MPa and fy = 350MPa
= Ultimate Axial Load Capacity of the column. 1. Determine the final factored load.
2. Determine the smallest dimension of the column section, using
LIMITS OF REINFORCEMENT FOR COLUMN initial value of steel ratio of 2%, using NSCP 2010/2015.
Area of longitudinal reinforcement for noncomposite compression 3. Determine the number of 28 mm bars.
members shall not be less than 0.01 or more than 0.08 times 4. Determine the spacing of 10 mm ties.
gross area Ag of section.
SITUATION
MINIMUM NUMBER OF BARS A spiral column carries a gravity factored axial dead load of 1200 kN
and factored axial live load of 2100 kN. The column is of average
Minimum number of longitudinal bars in compression members height and it will be assumed that there is no reduction in strength
shall be four (4) for bars within rectangular or circular ties, three due to the effects of slenderness. Use approximately 1.5%
(3) for bars within triangular ties, and six (6) for bars enclosed by reinforcement. Using fc’ = 27.6 MPa and fy = 415 MPa
spirals. 1. Determine the required diameter of the spiral column.
2. Determine the number of 28 mm longitudinal bars.
TIE REINFORCEMENTS FOR COMRESSION MEMBERS 3. Determine the practical center to center spacing of 10 mm
All non prestressed bars shall be enclosed by lateral ties at least diameter spiral reinforcement.
10mm diameter in size for longitudinal bars 32 mm in diameter or
smaller and 12 mm diameter in size for 36 diameter bars and
bundled longitudinal bars.
SPACING OF TIES
Vertical spacing of ties shall not exceed (a) 16 times the
longitudinal bar diameter; (b) 48 times the tie bar diameter, and;
(c) least dimension of the column.
SITUATION 3
Using the same given in Situation 3 and Using Interaction diagram,
ࢉ䘨 ࢉ determine the following.
1) Determine Pn when e=300 mm.
Case 1 Case 2 Case 3 2)Determine Pn when e=370 mm.
SITUATION 4
A spiral column having a diameter of 500 mm is reinforced with 8-22m
vertical bars. The diameter of spiral is 12mm and clear steel
covering is 40 mm. Use fc’ = 27.6 MPa and fy = 415 MPa. Consider the
ratio of the center to center reinforcement distance to the length of side
of column is equal to 0.70.
㼠
Ǥ
and
㼠
Ǥ
b Ǥ
SITUATION 6
Additional notes for Cm: (as per PCA notes on ACI) The tied column in the figure has been approximately sized to the
b Ǥ Ǥ dimensions 375mm x 300mm. It is to be used in a frame against
sidesway. The column is bent in single curvature about its stronger axis
and has an unsupported length of 5m. If k=0.8, fy=415 MPa and fc’=
b. For columns with transverse loads applied between 28MPa and factored dead load of 187.6 kN. Assume normal weight
supports. concrete.
*Calculation of
406.6.4.4.2 The critical buckling load, Pc, shall be
calculated by:
t ࢉLL
㼠
a.
Ǥ t
t ࢉLL Ǥ bbǤǤǤ䘨٫
b.
t t ࢉ
t ࢉLL Ǥ bbǤǤǤ ٫
c.
t
t ࢉLL Ǥ bbǤǤǤ ٫
Where shall be the ratio of maximum factored
sustained axial load to maximum factored axial load associated
with the same load combination and in Eq.406.6.4.4.4c is calculated
according to Table 406.6.3. l. l (b) for columns and walls.
INTERACTION DIAGRAM