You are on page 1of 4

F.A.L.

CONDUCIVE ENGINEERING REVIEW CENTER


2ND Floor, Cartimar Building, C.M. Recto Avenue, Quiapo, Manila
Contact Number/s: 0995-351-7556; 0945-734-3928

REINFORCED CONCRETE DESIGN - COLUMNS


Prepared by: Engr. Francis Arjay Pastores Luz

TYPES OF COLUMNS
Based on loading
1. Axially loaded columns – where loads are assumed
acting at the center of the column section.

2. Eccentrically loaded columns – loads are acting at a


distance e from the center of the column section.

3. Biaxially loaded columns – where the load is applied


at any point of the column section causing moments about
AXIALLY LOADED COLUMNS
the x and y-axes simultaneously.
A column subjected to pure axial loads does not exist in
concrete buildings. However, it can be assumed that axially
loaded columns are those with relatively small
Based on length
eccentricity, e, of about 0.1h or less, where h is the total
1. Short columns – where the column’s failure is due to
depth of the column and e is the eccentric distance from
crushing of concrete or the yielding of the steel bar under
the center of the column
the full load capacity of the column.

A column is considered to be axially loaded if the


2. Long columns – where buckling effect and slenderness
eccentricity of the force is less than or equal to
ratio must be taken into consideration in the design, thus
reducing the load capacity of the column relative to that of
a short column.

Also, the following must be satisfied:


a. For columns not braced against sidesway
Based on the shape
1. Square
2. Rectangular
b. For columns braced against sidesway
3. Round
4. L-shaped ( )
5. Octagonal and
6. Or any desired shape

Based on column ties where is negative if the column is bent in single


1. Tied columns – containing steel ties to confine the main curvature, and positive for double curvature.
longitudinal bars in the columns. Ties are normally spaced
uniformly along the height of the column. The radius of gyration r shall be permitted to be calculated
by (a), (b) or (c).
2. Spiral columns – containing spirals to hold the main
a. √
longitudinal reinforcement and help increase the column
ductility before failure. In general, ties and spirals prevent b. 0.30h (for rectangular columns)
the slender, highly stressed longitudinal bars from c. 0.25D (for circular columns)
buckling and bursting the concrete cover.

Ultimate nominal load capacity of the reinforced concrete


Based on frame bracings columns is obtained using the equation below:
1. Braced against sidesway – columns maybe part of a ( )
frame that is braced against sidesway. Bracing maybe
achieved by using shear walls or bracings in the building The maximum nominal axial load allowed by the code is:
frame. Columns resist mainly gravity loads, shear walls
resist lateral loads and wind loads.

2. Unbraced against sidesway – columns resist both


The ultimate axial load, :
gravity and lateral loads, which reduce the load capacity of
[ ( ) ]
the columns.
Where:
F.A.L. CONDUCIVE ENGINEERING REVIEW CENTER
2ND Floor, Cartimar Building, C.M. Recto Avenue, Quiapo, Manila
Contact Number/s: 0995-351-7556; 0945-734-3928

c.) 1 1 the maximum size of coarse aggregate


NSCP 2015 Limitations 3
1. Strength Reduction factors, :
Axially loaded columns are compression controlled PROBLEMS:
members, thus, SITUATION 1 - A reinforced concrete tied column carries a
Tied columns: dead axial load of 1000 kN and a live axial load of 1350 kN.
Spiral Columns: Use concrete strength fc’ = 27.6 MPa and yield strength of
reinforcement fy = 400 MPa
2. Longitudinal steel percentage, : 1. Determine the design axial load that the column will
carry.
2. If the size of the column is limited to 350 mm x 450mm,
what must be the number of 20 mm bars.
3. Minimum number of longitudinal bars 3. Determine the smallest dimension of the square column
Tied columns: 4 bars section if the steel ratio is 2 %.
Spiral Columns: 6 bars
For other shapes – one bar at each corner SITUATION 2 - A spiral column carries a gravity dead load
of 1200 kN and a live load of 1800 kN. The column is of
4. Minimum spiral reinforcement, average height and it will be assumed that there is no
reduction in strength due to the effects of slenderness. Use
( ) approximately 1.5% reinforcement. Using concrete
Actual spiral ratio, strength fc’ = 27.6 MPa and yield strength fy = 415 MPa
4. Determine the required diameter of the spiral column.

where: 6. Determine the center to center spacing of 10 mm


fy = specified yield strength of spiral reinforcement but not more diameter spiral reinforcement on the critical section.
than 415 MPa.
fc’ = specified compressive strength of concrete shall not be less SITUATION 3 - A 350 mm x 600 mm column is to be
than 17 MPa. constructed above the ground. The vertical reinforcement
Ag = gross area of column, mm2 consists of 12-
Ach = area of core of spirally reinforced compression member Maximum size of aggregates is 27 mm.
measured to outside diameter of spiral, mm2 7. Determine the maximum spacing required for the ties.
D = diameter of column, mm 8. Determine the required cover over the ties considering
the maximum aggregate size.
Dch = diameter of concrete core (i.e. diameter of column minus
the concrete cover at both sides), mm
9. A reinforced concrete tied column is to resist the
following axial load:
5. Minimum diameter of spirals = 10mm
. The concrete used has strength of 20.7 MPa and
• Clear spacing should not be more than 75mm nor less
the yield strength of 415 MPa. Determine the number of
than 25mm
25-mm bars if the steel ratio is 1.5%.
• Splices may be provided by welding or lapping
• Lapping – 48 bar diameters (48D) or a minimum of
10. A reinforced concrete spiral column is to resist the
300mm
following axial load: PDL = 900 kN, PLL = 1200 kN and PWL =
350 kN. The concrete used has strength of 27.6 MPa and
6. Minimum diameter of ties
the reinforcement yield strength of 345 MPa. Determine
• 32mm diam. long. bars or smaller = 10mm
the number of 20-mm bars if the steel ratio is 1.25%.
• Larger diameter bars and bundled bars = 12mm

11. (PRACTICE): A 500 mm square column is reinforced


7. SPACING OF LONGITUDINAL BARS
with 12-20mmΦ distributed equally in all sides. The
In spirally reinforced or tied reinforced compression members,
concrete used has strength of 25 MPa and the re-bar yield
clear distance between longitudinal bars shall not be less than
1.5db or less than 40 mm. strength of 345 MPa. Determine the ultimate axial capacity
of column.
8. Spacing of ties shall not exceed:
12. (PRACTICE): A 450 mm diameter column is reinforced
• 48 times tie diameters
with 8 - 25mmΦ distributed equally within the 10mmΦ
• 16 times longitudinal bar diameter
spiral. The concrete used has strength of 27.6 MPa and the
• Least dimension of the column
re-bar yield strength of 275 MPa. Determine the ultimate
axial capacity of column.
9. Minimum clear cover shall not be less than the following
a.) 40 mm
b.) diameter of vertical bars
F.A.L. CONDUCIVE ENGINEERING REVIEW CENTER
2ND Floor, Cartimar Building, C.M. Recto Avenue, Quiapo, Manila
Contact Number/s: 0995-351-7556; 0945-734-3928

ECCENTRICALLY LOADED COLUMNS


Eccentricity, e 3. Balanced Condition Pb
Refer to interaction Diagram (GREEN)
A balanced condition is reached when the compression
The eccentricity, e, represents the distance from the plastic strain in the concrete reaches 0.003 and the strain in the
centroid of the section to the point of application of load. tensile reinforcement reaches εy= fy/Es simultaneously;
 Failure of concrete occurs at the same time as the
Plastic centroid is obtained by determining the location steel yields.
of the resultant force produced by the steel and the  The moment that accompanies this load is called
concrete, assuming that both are stressed in compression the balanced moment, Mb, and the relevant
to fy and 0.85f’c, respectively. balanced eccentricity is eb=Mb/Pb

4. Tension Failure:
Load-Moment Interaction Diagram Refer to interaction Diagram (YELLOW)
This is the case of a small axial load with large eccentricity,
that is, a large moment.
 Before failure, tension occurs in a large portion of
the section, causing the tension steel bars to yield
before actual crushing of the concrete.
 At failure, the strain in the tension steel is greater
than the yield strain, εy, whereas the strain in the
concrete reaches 0.003.
 The range of this case extends from the balanced
to the case of pure flexure. When tension controls,
Pn<Pb and e>eb

5. Pure flexure:
Refer to interaction Diagram (ORANGE)
The section in this case is subjected to a bending moment,
LOAD-MOMENT INTERACTION DIAGRAM
Mn, whereas the axial load is Pn = 0.
 Failure occurs as in a beam subjected to bending
Axial Compression,
moment only.
( )
 The eccentricity is assumed to be at infinity.
This is a theoretical case assuming that a large axial load is
acting at the plastic centroid; e=0 and Mn=0. Failure of the
column occurs by crushing of the concrete and yielding of PROBLEMS:
steel bars. Problem 1: A 400mm square column is reinforced with 4-
25 mm diameter bars on its left portion 2-25mm diameter
1. Maximum Nominal Axial Load, in its right portion as shown. Steel covering = 70mm, fy =
This is the case of a normal force acting on the section with 415 MPa, fc’ = 28 MPa. Locate the plastic centroid of the
minimum eccentricity, (See interaction section from the y-axis. Neglect the volume of concrete
diagram) displaced by the main bars and assume that the concrete
NSCP 2015 Provides that, section remains square.

Failure occurs by crushing of the concrete and the yielding


of the steel bars.

2. Compression failure:
Refer to interaction Diagram (BLUE)
This is the case of a large axial load acting at a small
eccentricity. It is ranging from to a minimum of

Eccentrically Loaded Columns


Failure occurs by crushing of the concrete on the A. Analytic Method
compression side with a strain of 0.003, whereas the stress Case 1 - Balance Condition
in the steel bars (on the tension side) is less than the yield Problem 2: A 350 mm x 700 mm column is reinforced
strength, fy (fs<fy). In this case, Pn>Pb and e<eb with 6 -28mm dia. bars, three bars distributed equally in
short dimension with steel covering of 70 mm. Use
F.A.L. CONDUCIVE ENGINEERING REVIEW CENTER
2ND Floor, Cartimar Building, C.M. Recto Avenue, Quiapo, Manila
Contact Number/s: 0995-351-7556; 0945-734-3928

concrete strength of 27.6 MPa and rebar yield strength of


276 MPa.
a. Determine the nominal balanced load Pnbal
b. Determine the eccentricity ebal for balanced failure.
c. Determine the nominal moment Mnbal for balanced
failure.

Case 2 – Compression Controlled


Problem 3: A 350 mm x 700 mm column is reinforced
with 6 -28mm dia. bars, three bars distributed equally in
short dimension with steel covering of 70 mm. Use
concrete strength of 27.6 MPa and rebar yield strength of
276 MPa. If the eccentricity e = 200 mm,
a. Determine the balance eccentricity,
b. Determine the ultimate axial load that could be
placed.
c. Determine the moment load

Case 3 – Tension Controlled


Problem 4: A 350 mm x 700 mm column is reinforced
with 6 -28mm dia. bars, three bars distributed equally in
short dimension with steel covering of 70 mm. Use
concrete strength of 27.6 MPa and rebar yield strength of
276 MPa. If the eccentricity e = 450 mm,
a. Determine the balance eccentricity,
b. Determine the ultimate axial load that could be
placed.
c. Determine the moment load

Eccentrically Loaded Columns


B. Graphical Method – use of available interaction
diagrams.

Problem 5: - A tied column having the cross section of 350


mm x 700 mm is reinforced with 6 – 32 mm dia. bars
distributed equally in the 350-mm dimension. Use
concrete strength of 28 MPa and re-bar yield strength of
415 MPa. Consider the ratio of the center to center
reinforcement distance to the longer side of column is
equal to 0.70.
13. Determine the reinforcement ratio in percent.
14. Determine the ratio e/h if the eccentricity is 280 mm.
15. Determine the value of the maximum load Pn that the
column could carry using the interaction diagram.

Problem 6: A spiral column having a diameter of 500 mm


is reinforced with 8-36mm dia. vertical bars. The diameter
of spiral is 10mm dia. Use concrete strength of 28 MPa and
re-bar yield strength of 415 MPa. Consider the ratio of the
center to center reinforcement distance to the diameter of
column is equal to 0.70.
16. Determine the steel ratio in percent.
17. Determine the eccentric load Pn having an eccentricity
of 200 mm using the interaction diagram.

You might also like