Calculate Size of Contactor, Fuse, C.B, Over Load Relay of DOL Starter
Calculate Size of Contactor, Fuse, C.B, Over Load Relay of DOL Starter
Motor
Calculate Voltage drop in Transformer ,1000KVA,11/0.480KV,impedance 5.75%, due to
starting of 300KW,460V,0.8 Power Factor, Motor code D(kva/hp).Motor Start 2 times
per Hour and The allowable Voltage drop at Transformer Secondary terminal is 10%.
Transformer:
Transformer Full Load Current= Kva/(1.732xVolt)
Transformer Full Load Current=1000/(1.732×480)=1203 Amp.
Short Circuit Current at TC Secondary (Isc) =Transformer Full Load Current /
Impedance.
Short Circuit Current at TC Secondary= 1203/5.75= 20919 Amp
Maximum Kva of TC at rated Short Circuit Current (Q1) = (Volt x Iscx1.732)/1000.
Maximum Kva of TC at rated Short Circuit Current (Q1)=480x20919x1.732/1000=
17391 Kva.
Voltage Drop at Transformer secondary due to Motor Inrush (Vd)= (Irsm) / Q1
Voltage Drop at Transformer secondary due to Motor Inrush (Vd) =1688/17391 =10%
Voltage Drop at Transformer Secondary is 10% which is within permissible Limit.
Motor Full Load Current<=65% of Transformer Full Load Current
471 Amp <=65%x1203 amp = 471 Amp<= 781 Amp
Here Voltage Drop is within Limit and Motor Full Load Current<=TC Full Load Current.
Size of Transformer is Adequate.