DATA SHEET

FIRE ALARM SYSTEM


MAIN CONTROL PANEL
Fire Control Panels
UL, ULC, CSFM Listed; Automatic Extinguishing, Deluge and Preaction
FM, NYC Fire Dept Approved* Sprinkler System Releasing Control

Features
Actuator
Releasing control using the Simplex® 4010ES Agent Agent
Fire Alarm Control Panel to provide: source discharge
 Coverage for multiple areas of Automatic Extinguishing Actuator path
Control
Release and/or Deluge and Preaction Sprinkler System Circuit
Release including audible escalation of events Coil supervisory
module
 Control of compatible Listed/Approved 24 VDC automatic
control actuators, one per circuit; or two 12 VDC actuators in
COILSUPERVISIONMODULE( 2AMP) 2081 - 9046
RED INST ALLATION INSTRUCT IONS574- 437 REV YEL
NAC+ MAINTAIN1/4 " SEPARATION
BETW EENPOW ERLIMIT ED
( RED/BLK) ANDNONPOW ER S
LIMIT ED( YEL/BLK) W IRING
DATECODE: 519- 9 58
BLK
NAC-
BLK S IMP L E X T IM E R E C O RD E R CO .G A R D N E R MA .U S A

series per circuit


 Releasing appliance circuits (RACs) by connecting
Release
Notification appliance circuits (NACs) to Suppression appliance circuit
Release Peripherals for actuator supervision and control
 Four, 3 Amp Notification Appliance Circuits (NACs) in the Maintenance
panel for use with Suppression Release Peripherals (SRP)
NORMAL

Disconnect Switch
0

DISC./
1
DISABLE

and required notification appliances (with indicator lamp)


FIRE SUPPRESSION
DISCONNECT / DISABLE

Power for
 Additional actuator circuit control and additional NACs are indicator lamp
available using 4009 IDNet Addressable NAC Extenders (if required)
FIRE
and Suppression Release Peripherals RELEASING
Suppression
Audible Escalation of Events: Release Peripheral
DEVICE
 Temporal or 20 bpm March Time pattern for first
cross-zone alarm
 120 bpm March Time pattern indicates releasing timer active Typical addressable
initiating devices
 On steady indicates releasing timer expired and actuator is IDNet
activated communications
FIRE SUPPRESSION


SYSTEM ABORT

NOTE: Requires NACs dedicated to conventional horn - I DN ET


+ ID NET
IN +
IN -

Dedicated
PUSH AND HOLD

control (not SmartSync operation) with strobes controlled


MANUAL
RELEASE

NAC circuit
on separate NACs
4009 IDNet NAC Extenders provide:
 Up to eight NACs for notification requirements and for
NAC input to Suppression Release Peripherals
 Control is via IDNet addressable communications SUPPRESSION RELEASE PANEL

4090-9005/-9006 Suppression Release Peripheral


CAUTION: This Control Unit has been arranged for releasing
service. Disable all releasing device circuits prior to servicing.

(SRP) with Dual Command Control:


 Dual command control requires that both IDNet
communications commands and an activated NAC are
present to initiate the desired release 4010ES Control Panel with
Suppression Release Appliqué
 NAC provides wiring supervision to the actuator including
monitoring of coil continuity and short circuit supervision 4010ES Release Control Simplified Block Diagram
to the coil supervision module
Suppression Release Peripheral control features: Introduction
 An on-board DC-DC regulator compensates for voltage When combined with Suppression Release Peripherals, the
drops to the peripheral and ensures proper control circuit 4010ES series fire alarm control panel provides actuator
voltage over a wide operating range supervision and control for use in automatic extinguishing,
 Provides a single RAC for control of actuators for up to 2 and deluge or preaction releasing systems. Hazard area
A using a 3 A NAC input (1 A using a 2 A NAC input) initiating and notification devices are controlled using either
Related system components: conventional or addressable circuits per standard 4010ES
 4010ES Series control panel with Releasing Appliqué capabilities. The necessary releasing system logic is
 Dedicated NAC output from 4010ES (or compatible NAC implemented within the 4010ES control panel as required for
Extender) the local application.
 Coil supervision module, one per RAC * This product has been approved by the California State Fire Marshal (CSFM) pursuant to
 Maintenance Switch, one per RAC Section 13144.1 of the California Health and Safety Code. See CSFM Listings
7165-0026:0369 and 7300-0026:313 (SRP) for allowable values and/or conditions
 Abort Switch connected via an addressable interface module concerning material presented in this document. It is subject to re-examination, revision,
and possible cancellation. NYC Fire Dept COA #6095. Additional listings may be applicable;
UL listed to Standard 864 contact your local Simplex product supplier for the latest status. Listings and approvals
under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
S4010-0005-3 2/2012
Automatic Extinguishing Release Systems Releasing System Requirements (Continued)
These systems automatically activate electrically 5. FM Approved Automatic Extinguishing Release
controlled actuators for the release of a fire extinguishing requires secondary standby to be a minimum of
agent (such as dry chemical, water spray, foam, CO2, or 24 hours with 5 minutes of alarm. Actuators must be
clean agent) in response to fire detection device inputs as electrically compatible.
determined by programming of the host fire alarm control 6. FM Approved Deluge and Preaction Sprinkler
panel. operation requires that: initiating device circuits be
Automatic Extinguishing Release System Panels Class A and wired to Listed/Approved devices;
are required to have a minimum of 24 hours of standby standby power capacity must be a minimum of 90
power. Initiating devices must be Listed/Approved for the hours with 10 minutes of alarm; and that compatible
application, and may be wired either Class A or B. Automatic Water Control Valves must be used. (Refer
Control actuators must be electrically compatible with the to actuator list on page 7.)
control panel circuits and power supplies, and are wired 7. Maintenance Switches, one per RAC, are required
Class B to provide coil supervision. per NFPA 72, the National Fire Alarm and Signaling
Code (2002 Edition, Chapter 6) to allow the system to
Deluge or Preaction Sprinkler Systems be tested or serviced without actuating the fire
suppression systems. Their use may not be allowed in
These systems automatically activate water control
some jurisdictions, always confirm local
actuators in response to fire detection device inputs.
requirements. When used, Simplex Maintenance
Deluge Sprinkler Systems employ open sprinkler Switches are required to ensure that operation initiates
heads and provide water flow when the fire detection a supervisory condition.
system activates a common automatic water control
8. Abort Switches are available when abort operation is
actuator. They are used to deliver water simultaneously
required. When used, connect to an addressable
through all of the system sprinkler heads. This type of
Supervised IAM model 4090-9001 or similar
system is applicable where the immediate application of
addressable adapter module. The Simplex abort switch
large quantities of water over large areas is the proper fire
and the IAM mount in a single gang box, 2-1/2”
response.
minimum depth.
Preaction Sprinkler Systems are similar to deluge
9. Addressable Manual Releasing Stations are used to
systems except that normally closed sprinkler heads are
initiate activation of the releasing actuators with the
used and supervisory air pressure is maintained in the
appropriate time delay implemented by the fire alarm
pipe. Operation requires both an activated sprinkler head
control panel.
and an activated fire alarm initiating device with specific
programming determined at the host fire alarm control 10. Notification Requirements. Each hazard area
panel. typically requires general audible and visible fire
alarm notification and additional dedicated NACs for
Releasing System Requirements area releasing status notification. Suppression
releasing is compatible with conventional panel
1. Releasing actuators are controlled from a mounted NAC modules as well as for use with the
Suppression Release Peripheral (4090-9005 or 4009 IDNet NAC Extender.
4090-9006). Connections are 2-wire, Class B releasing
circuits with only one 24 VDC actuator per circuit. 11. Additional Suppression Release Peripheral
Where applicable, two, 12 VDC actuators in series, or Reference. Refer to Installation Instructions 579-385.
one 12 VDC actuator with manufacturer supplied
resistor may be used.
Additional Releasing Systems Reference
2. Coil Supervision Module 2081-9046 must be wired
electrically before the actuator and located in the For additional information, refer to Factory Mutual
actuator wiring junction box. (Refer to diagram on Research Corporation (FMRC) “FMRC Approval Guide,”
page 5.) The connected RAC provides continuity FM Approval standard “Deluge Systems and Preaction
supervision of the actuator coil and wiring and Systems.”
provides short circuit supervision to the coil
supervision module. Please note that proper operation of releasing control
systems requires that the system design, installation, and
3. Cross-zoning or other alarm initiation logic per maintenance be performed correctly and in accordance
system requirements, is to be implemented by with all applicable local and national codes, and
programming at the fire alarm control panel. equipment manufacturer’s instructions. No liability for
4. UL Listed Automatic Extinguishing Releasing total system operation is assumed or implied.
operation requires that: battery standby must be a
minimum of 24 hours with 5 minutes of alarm and that
listed actuators are used, refer to list on page 6.

2 S4010-0005-3 2/2012
Product Selection

4010ES Releasing Control System Modules


Model Description Reference
Required, one per RAC, mounts in the releasing actuator wiring
2081-9046 Coil Supervision Module
junction box; see specifications section for details
One per RAC; flush or surface mount; indicator lamp models
2080-Series* Maintenance Switches
require separate 24 VDC wiring

2080-9056* Flush mount As required, connects via an IDNet addressable interface module;
Abort Switch mounted on a single gang stainless steel plate; installation
2080-9057* Surface mount requires a single gang box, 2-1/2” (64 mm) minimum depth

* Refer to data sheet S2080-0010 for Abort and Maintenance switch details.

Releasing Appliqués, Required for 4010ES Suppression Releasing Applications


Model Description
4010-9830 English Suppression Releasing Appliqué; field applied (same appliqué as is used on the
4010-9830CAF French Simplex model 4010 Suppression Release Panel)

Suppression Release Peripheral and Accessories


Model Description Reference
Basic Suppression Release Peripheral on
4090-9005 Requires mounting box 2975-9227, ordered separately
mounting plate
Suppression Release Peripheral mounted in
4090-9006 Includes LED indicator on front of door
red box; required for ULC listing
2975-9227 Red mounting box; required for 4090-9005
Red LED IDNet communications indicator These items are included with model 4090-9006
4090-9812
option kit; mounts on door of 2975-9227 box

Additional Product Data Sheet Reference

Subject Data Sheet Subject Data Sheet


Releasing System Abort and Maintenance
S2080-0010 Addressable Zone Adapter Modules S4090-0003
Switches
Addressable Manual Stations for Releasing
S4099-0002 TrueAlarm Sensors and Bases S4098-0019
Applications
Addressable Manual Stations for Standard
S4099-0001 TrueAlert Electronic Horns S4901-0010
Applications
4010ES Basic Control Panels S4010-0004 TrueAlert Non-Addressable Strobes (V/O) S4906-0001
Supervised IAM S4090-0001 TrueAlert Non-Addressable 4-Wire Horn/Strobes (A/V) S4903-0011

Contact your local Simplex product supplier for additional information on compatible IDNet addressable devices and TrueAlert
notification appliances.

3 S4010-0005-3 2/2012
4010ES Releasing System One-Line Connection Reference with 4009 IDNet NAC Extenders

4090-9005/-9006 Suppression Actuator Control Circuit


Release Peripheral (SRP)
Agent source
Horn and strobe NACs; Coil supervisory
4 NACs standard, up to FIRE Actuator
module
8 NACs available RELEASING NORMAL

0
(FM Approved
DEVICE
1
DISC./ RED
NAC+
COIL SUPERVISIONMODULE( 2AMP) 2081- 9 046
INSTAL LATIONINSTRUCTIONS574- 437 REV
MAINTAIN1/4" SEPARATION
YEL

DISABLE

water valves
BETW EENPOW ERLIMITED
( RED/BLK) ANDNONPOW ER S
LIMITED( YEL/BLK) W IRING
DATECODE: 519- 958 BLK
NAC-
BLK S IMP L E X T IME R E CO R D E R CO .G A R D NE R M A .U S A

FIRE SUPPRESSION
DISCONNECT / DISABLE

Group A, B, D,
E, F, G, or H)
Agent discharge path
IDNet communications
to up to 10 total 4009 Dedicated
IDNet NAC Extenders NAC

FIRE SUPPRESSION
SYSTEM ABORT

- I DNET IN +
+IDNET IN -

PUSH AND HOLD


MANUAL
RELEASE

CAUTI ON
DI SCO NNECT

4009 IDNet
PO W ER
BEFO RE
SERVI CI NG

NAC Extender 4009 IDNet NAC EXTENDER


TM 24 VDC for Maintenance Disconnect
(if required) status indicator (if required)

IDNet communications

IDNet communications
Dedicated NAC wiring To SRP, either from 4010ES
(dashed line) or from 4009 IDNet NAC Extender

FIRE SUPPRESSION
SYSTEM ABORT

- IDNET IN +

4010-9830 Suppression Release Appliqué, to be applied


+IDNET I N -

PUSH AND HOLD


MANUAL
RELEASE

in the field (also available in French with 4010-9830CAF):


Supervised IAM with
optional Abort Switch SUPPRESSION RELEASE PANEL
CAUTION: This Control Unit has been arranged for releasing
IDNet Addressable devices service. Disable all releasing device circuits prior to servicing.

NAC for horn control Use separate NACs


SUPPRESSION RELEASE PANEL
for horn and strobe
control to implement
CAUTION: This Control Unit has been arranged for releasing
service. Disable all releasing device circuits prior to servicing.

audible escalation of
events
NAC for strobe control

4010ES Control Panel with


Suppression Release Appliqué

4 S4010-0005-3 2/2012
Suppression Release Peripheral Wiring Reference

Maximum Release Appliance Circuit (RAC) Wiring Distances from Suppression Release Peripheral to
the Valve Solenoid (based on a total drop of 0.6 V)
RAC Output Current Distance Total Line
(refer to solenoid
18 AWG 16 AWG 14 AWG Resistance
rating)
0.50 A 74 ft 23 m 118 ft 36 m 188 ft 57 m 1.06 
0.75 A 50 ft 15 m 79 ft 24 m 126 ft 38 m 0.71 
1.00 A 37 ft 11 m 59 ft 18 m 94 ft 29 m 0.53 
1.25 A 30 ft 9m 47 ft 14 m 75 ft 23 m 1.06 
1.5 A 25 ft 7.6 m 39 ft 12 m 63 ft 19 m 0.71 
1.75 A 21 ft 6.4 m 34 ft 10 m 54 ft 16 m 0.53 
2.00 A 19 ft 5.8 m 30 ft 9m 47 ft 14 m 0.53 
2 2 2
Metric wire equivalents: 18 AWG = 0.82 mm ; 16 AWG = 1.31 mm ; 14 AWG = 2.08 mm

NORMAL

DISC./
1
DISABLE

FIRE SUPPRESSION
DISCONNECT / DISABLE

FIRE COIL SUPERVISIONMODULE( 2 AMP) 2081- 9046


YEL

RELEASING
RED INSTALLATIONINSTRUCTIONS574- 437 REV
NAC+ MAINTAIN1/4 " SEPARATION
NORMAL
BETW EENPOW ERLIMITED
( RED/BLK) ANDNONPOW ER S

DEVICE LIMITED( YEL/BLK) W IRING


0

DISC./
1
DISABLE DATECODE: 519- 958
BLK
NAC-
FIRE SUPPRESSION BLK S IM P L E X T IM E R E C O R D E R C O .G A R D N E R M A .U S A

DISCONNECT / DISABLE

FIRE SUPPRESSION
SYSTEM ABORT

- IDNET IN +
+IDNET IN -

PUSH AND HOLD


MANUAL
RELEASE

Maximum Notification Appliance Circuit (NAC) Wiring Distances to a Suppression Release Peripheral
(0.5 A to 1.75 A drop is based on a total drop of 3.4V; 2 A drop is based upon a total drop of 1.2 V)
FIRE SUPPRESSION
RAC Output Current Distance SYSTEM ABORT
Total Line
(refer to solenoid
18 AWG 16 AWG 14 AWG Resistance
rating)
0.50 A 250 ft 76 m 399 ft 122 m 635 ft 194 m 3.58 
0.75 A 167 ft 51 m 266 ft 81 m 423 ft 129 m 2.39 
1.00 A 125 ft 38 m 199 ft 61 m 317 ft 97 m 1.79  PUSH AND HOLD
1.25 A 100 ft 30 m 159 ft 48 m 254 ft 77 m 1.43 
1.5 A 84 ft 26 m 133 ft 41 m 212 ft 65 m 1.19 
1.75 A 72 ft 22 m 114 ft 35 m 181 ft 55 m 1.02 
2.00 A 25 ft 7.6 m 39 ft 12 m 63 ft 19 m 0.36 
2 2 2
Metric wire equivalents: 18 AWG = 0.82 mm ; 16 AWG = 1.31 mm ; 14 AWG = 2.08 mm

5 S4010-0005-3 2/2012
Specifications

Suppression Release Peripheral 4090-9005 and 4090-9006


Communications IDNet, one address

RAC Output with 4010ES 2 A maximum At nominal 24 VDC, regulated; refer to NAC Power
Rating with 4009 IDNet NAC Extender 1 A maximum Requirements for more detail

Voltage 16 to 32 VDC (nominal 24 VDC)


NAC Power Requirements No additional current required, circuit appears as standard end-of-line (EOL)
Supervisory Current
NAC loading
NOTE: 4010ES NACs are
RAC Current NAC Current RAC Current NAC Current
rated at 3 A; 4009 IDNet Alarm Current
NAC Extender NACs are 0.5 A 0.845 A 1.25 A 2.14 A
Reference
rated at 2 A, Extender 0.75 A 1.28 A 1.5 A 2.56 A
expansion NACs are rated
1.5 A (RAC current = 0.87 A 1.5 A 1.75
actuator current) 3A
1A 1.71 A 2A
Screw terminals for input and output wiring, 18 to 12 AWG wire
Wire Connections
(0.82 mm2 to 3.31 mm2)
Up to 2500 ft (762 m) from the IDNet source module
IDNet Wiring Distance Reference Up to 10,000 ft (3048 m) total Class B wiring distance including T-Taps
Compatible with Simplex 2081-9044 Overvoltage Protectors
Dimensions See installation reference on page 8
Operating Temperature 32° to 120° F (0° to 49° C) indoor operation only
Operating Humidity Range 10 to 90% RH at 90° F (32° C)

Coil Supervision Module 2081-9046


Construction Epoxy encapsulated
Dimensions 1-3/8” W x 2-7/16” L x 1-1/16” H (34 mm x 62 mm x 27 mm)
Wiring 18 AWG (0.82 mm2) wire leads, color coded
Current Rating 2 A Maximum; internally fused at 3 A, non-replaceable

Compatible UL Listed Valves and Actuators

MFG. Model Number Coil Details MFG. Model Number


*AUTOMAN II-C Assembly; solenoid
12 VDC, 458 mA 8210A107 (097617-005D coil) 1/2” NPS, 5/8” orifice,
17728; coil 25924
24 VDC
AUTOMAN II-C Explosion-Proof
Releasing Device; solenoid 31492; coil 24 VDC, 467 mA
31438 8210G207 (238310 coil) 1/2” NPS, 1/2” orifice
*AUTOMAN II-C Assembly; solenoid
12 VDC, 458 mA ASCO 8211A107 (097617-005D coil) 24VDC
68739; coil 25924,
Solenoid Electric Actuator; solenoid
24 VDC, 1 A HV2628571 (23810 coil) N.C. 1/2” NPS, 1/2” orifice
73111; coil 73097
ANSUL
*CV90 HF Electric Actuator 73327; may 9 VDC max, HV2648581 (23810 coil) N.O. 1/2” NPS, 1/2” orifice
use 73606 in-line resistor for 12 VDC 450 mA R8210A107 (097617-005D coil) 1/2” NPS, 5/8” orifice
LP CO2 w/ASCO solenoid 422934, 24 VDC, 442 mA T8210A107 (097617-005D coil) 1/2” NPS, 5/8” orifice
LP CO2 double action solenoid 430948 24 VDC, 438 mA ECH Electrical Control Head (551201)
LP CO2 3-way selector valve solenoid
24 VDC, 438 mA Pyro- Explosion-Proof Electric Actuator (570147)
433419
Chem
Electric Actuator 24 VDC solenoid
24 VDC, 250 mA Removable Electric Actuator (570209) 0.2 A
570537
71395SN2ENJ1NOH111C2 (Skinner coil H111C2) 1/4”, NPS, 1/16”
73212BN4TN00NOC111C2 (Skinner coil C111C2) 1/2”, 5-300 psi
Skinner 73212BN4TNLVNOC322C2 (Skinner coil C322C2) 1/2”, NPS, 0.92 A, 250 psi
73218BN4UNLVNOH111C2 (Skinner coil H111C2)
73218BN4UNLVNOC111C2 (Skinner coil C111C2) 1/2”, NPS, 5/8 in. orifice
* 12 VDC coils, either wire two in series for 24 VDC activation, or, if available from manufacturer, use series resistor

6 S4010-0005-3 2/2012
FM Approved Water Control Valves

FM
Manufacturer Model Number Details
Group
A Skinner LV2LBX25* 24 VDC, 11 W, 458 mA, 1/2 inch NPS, 1/2 inch orifice

T8210A107

B ASCO R8210A107 24 VDC, 16.8 W, 700 mA, 1/2 inch NPS, 5/8 inch orifice

8210A107

D ASCO 8210G207 24 VDC, 10.6 W, 440 mA, 1/2 inch NPS, 1/2 inch orifice

73218BN4UNLVNOC111C2* 24 VDC, 10 W, 420 mA, 1/2 inch NPS, 5/8 inch orifice
E Skinner 24 VDC, 10 W, 420 mA, 1/2 inch NPS, 5/8 inch orifice; 5-300 psi rated
73212BN4TN00N0C111C2
working pressure

F Skinner 73212BN4TNLVNOC322C2 24 VDC, 22 W, 1/2 inch NPS, 920 mA, 250 psi (1725 kPa), 1/2 inch orifice

24 VDC, 10 W, 420 mA, 1/4 inch NPS, 1/16 inch orifice, 250 psi
G Skinner 71395SN2ENJ1NOH111C2
(1725 kPa) rated working pressure

I Vitaulic Series 753-E solenoid valve 24 VDC, 8.7 W, 1⁄2 inch NPS, 364 mA, 300 psi (2069 kPa), 1⁄2 inch orifice

11591 and 11592 Normally closed (NC) Explosion proof solenoid valves, 24 VDC, 10 W,
J Viking
1⁄2 inch NPS, 300 psi (2069 kPa), 4.1 Cv
11595 and 11596 Normally open (NO)

K Viking 11601 and 11602 NC solenoid valve, 24 VDC, 9 W, 1⁄2 inch NPS, 250 psi (1725 kPa), 6.2 Cv

* For new applications, LV2LBX25 has been replaced by model number 73218BN4UNLVNOC111C2.

7 S4010-0005-3 2/2012
Suppression Release Peripheral Installation Reference Diagram

2975-9227 Box, red with white


lettering (supplied with 4090-9006)

Door hinges on left and


lifts off for access

4 Knockouts,
one each side

Door height Door screw


8-1/8" fastener
(206 mm)

4090-9812 LED indicator


option (supplied with
4090-9006)
Door depth
1/2" (13 mm)

Door width Box depth


6-1/8" (156 mm) 4" (102 mm)
Box depth with door
4-1/16" (103 mm)

4090-9005 Suppression
Release Peripheral assembly
(supplied with 4090-9006)
NAC +
NAC -

Box height
8" (203 mm)
IDNet+

RAC -
RAC +
IDNet-

ON

1 2 3 4 5 6 7 8

IDNET SUPPRESSION RELEASE PERIPHERAL ASSY 566-104

Box width
6" (152 mm)

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4010-0005-3 2/2012


www.simplexgrinnell.com
© 2012 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
SMOKE PHOTOELECTRIC
DETECTOR
TrueAlarm Analog Sensing
UL, ULC, CSFM Listed; FM Approved; TrueAlarm Analog Sensors – Photoelectric,
MEA (NYC) Acceptance* Ionization, and Heat; Standard Bases and Accessories

Features
TrueAlarm analog sensing provides:
! Digital transmission of analog sensor values via IDNet
or MAPNET II two-wire communications
For use with the following Simplex® products:
! 4100ES, 4100U, 4010ES, and 4010 Series control
panels; and 4008 Series control panels with reduced
feature set (refer to data sheet S4008-0001 for details)
! 4020, 4100, and 4120 Series control panels, Universal
Transponders, and 2120 TrueAlarm CDTs equipped for
MAPNET II operation 4098-9714 TrueAlarm Photoelectric
Fire alarm control panel provides: Sensor Mounted in Base
! Peak value logging allowing accurate analysis of each
sensor for individual sensitivity selection Description
! Sensitivity monitoring satisfying NFPA 72 sensitivity
Digital Communication of Analog Sensing.
testing requirements; automatic individual sensor
calibration check verifies sensor integrity TrueAlarm analog sensors provide an analog
measurement digitally communicated to the host control
! Automatic environmental compensation, multi-stage
panel using Simplex addressable communications. At the
alarm operation, and display of sensitivity directly in
control panel, the data is analyzed and an average value is
percent per foot
determined and stored. An alarm or other abnormal
! Ability to display and print detailed sensor information condition is determined by comparing the sensor’s present
in plain English language value against its average value and time.
Photoelectric smoke sensors provide:
! Seven levels of sensitivity from 0.2% to 3.7% Intelligent Data Evaluation. Monitoring each sensor’s
(refer to additional information on page 3) average value provides a continuously shifting reference
point. This software filtering process compensates for
Heat sensors provide:
environmental factors (dust, dirt, etc.) and component
! Fixed temperature sensing
aging, providing an accurate reference for evaluating new
! Rate-of-rise temperature sensing activity. With this filtering, there is a significant reduction
! Utility temperature sensing in the probability of false or nuisance alarms caused by
! Listed to UL 521 and ULC-S530 shifts in sensitivity, either up or down.
Ionization smoke sensors provide: Control Panel Selection. Peak activity per sensor is
! Three levels of sensitivity; 0.5%, 0.9%, and 1.3% stored to assist in evaluating specific locations. The alarm
(refer to additional information on page 3) set point for each TrueAlarm sensor is determined at the
General features: host control panel, selectable as more or less sensitive as
! Listed to UL 268 and ULC-S529 the individual application requires.
! Louvered smoke sensor design enhances smoke
capture by directing flow to chamber; entrance areas Timed/Multi-Stage Selection. Sensor alarm set points
are minimally visible when ceiling mounted can be programmed for timed automatic sensitivity
selection (such as more sensitive at night, less sensitive
! Designed for EMI compatibility
during day). Control panel programming can also provide
! Magnetic test feature is provided multi-stage operation per sensor. For example, a 0.2%
! Optional accessories include remote LED alarm level may cause a warning to prompt investigation while a
indicator and output relays 2.5% level may initiate an alarm.
Additional base reference:
Sensor Alarm and Trouble LED Indication. Each
! For isolator bases, refer to data sheet S4098-0025
sensor base’s LED pulses to indicate communications
! For sounder bases, refer to data sheet S4098-0028 with the panel. If the control panel determines a sensor is
! For photo/heat sensors, refer to data sheet S4098-0024 in alarm, or is dirty or has some other type of trouble, the
(single address) and S4098-0033 (dual address) details are annunciated at the control panel and that sensor
* These products have been approved by the California State Fire Marshal (CSFM) pursuant to base’s LED will be turned on steadily. During a system
Section 13144.1 of the California Health and Safety Code. See CSFM Listings
7272-0026:218, 7271-0026:231, 7270-0026:216, and 7300-0026:217 for allowable values
alarm, the control panel will control the LEDs such that
and/or conditions concerning material presented in this document. It is subject to an LED indicating a trouble will return to pulsing to help
re-examination, revision, and possible cancellation. Accepted for use – City of New York identify the alarmed sensors.
Department of Buildings – MEA35-93E. Additional listings may be applicable, contact your
local Simplex product supplier for the latest status. Listings and approvals under Simplex
Time Recorder Co. are the property of Tyco Fire Protection Products.
S4098-0019-14 11/2012
TrueAlarm Sensor Bases and Accessories Description
Sensor Base Features TrueAlarm sensor bases contain integral addressable
electronics that constantly monitor the status of the
Base mounted address selection: detachable photoelectric, ionization, or heat sensors. Each
! Address remains with its programmed location sensor’s output is digitized and transmitted to the system
! Accessible from front (DIP switch under sensor) fire alarm control panel every four seconds.
General features: Since TrueAlarm sensors use the same base, different
! Automatic identification provides default sensitivity sensor types can be easily interchanged to meet specific
when substituting sensor types location requirements. This feature also allows intentional
! Integral red LED for power-on (pulsing), or alarm or sensor substitution during building construction. When
trouble (steady on) conditions are temporarily dusty, instead of covering the
smoke sensors (causing them to be disabled), heat sensors
! Locking anti-tamper design mounts on standard outlet
may be installed without reprogramming the control
box
panel. Although the control panel will indicate an
! Magnetically operated functional test incorrect sensor type, the heat sensor will operate at a
Sensor Bases default sensitivity providing heat detection for building
protection at that location.
4098-9792, Standard sensor base
4098-9789, Sensor base with wired connections for: Mounting Reference
! 2098-9808 Remote LED alarm indicator or 4098-9822 Electrical Box Requirements: (boxes are by others)
relay (unsupervised) Without relay: 4" octagonal or 4" square, 1-1/2" deep;
4098-9791, Sensor base with supervised relay driver single gang, 2" deep
output (not compatible with 2120 CDT): With relay : 4" octagonal or 4" square, 1-1/2" deep,
with 1-1/2" extension ring
! Relay operation is programmable and can be manually
operated from control panel 4" (102 mm) Square Box 4" (102 mm) Octagonal Box

! Use with remote mount 2098-9737 relay Surface mount reference

! Also includes wired connections for remote LED alarm


indicator or 4098-9822 relay
Sensor Base Options
2098-9737, Remote or local mount supervised relay: 1-1/2" (38 mm)
minimum box depth
! DPDT contacts for resistive/suppressed loads, power Flush mount reference, mount even with final
surface, or with up to 1/4" (6.4 mm) maximum recess
limited rating of 3 A @ 28 VDC; non-power limited
rating of 3 A @ 120 VAC (requires external 24 VDC 2098-9737 Relay (mounts in 4098-9822 Relay (mounts
coil power) base electrical box or remotely) in base electrical box)
4098-9822, LED Annunciation Relay:
! Activates when base LED is on steady, indicating local
alarm or trouble
! DPDT contacts for resistive/suppressed loads, power
limited rating of 2 A @ 28 VDC; non-power limited
rating of 1/2 A @ 120 VAC, (requires external 24 VDC
Relay Size: 2-1/2" X 1-1/2" X 1" (3.75 cubic inches)
coil power) (64 mm X 38 mm X 25.4 mm)
4098-9832, Adapter plate:
NOTE: Review total wire count, wire size, and accessories
! Required for surface or semi-flush mounting to being wired to determine required box volume.
4” square electrical box and for surface mounting to
4” octagonal box 6-3/8" (162 mm)
! Can be used for cosmetic retrofitting to existing 6-3/8”
diameter base product 4098-9832 Adapter Plate, required for
1/4" mounting to surface mounted boxes
2098-9808, Remote red LED Alarm (6.4 mm) and 4" square flush box
Indicator:
4-7/8" (124 mm)
! Mounts on single gang box ALARM
(shown in illustration to right) 15/16"
(24 mm)

TrueAlarm Bases
4098-9789, -9791, & -9792

2 S4098-0019-14 11/2012
TrueAlarm Sensors 4098-9714 Photoelectric Sensor
Features TrueAlarm photoelectric sensors use a stable, pulsed
Sealed against rear air flow entry infrared LED light source and a silicon photodiode receiver
to provide consistent and accurate low power smoke
Interchangeable mounting
sensing. Seven levels of sensitivity are available for each
EMI/RFI shielded electronics individual sensor, ranging from 0.2% to 3.7% per foot of
Heat sensors: smoke obscuration. Sensitivities of 0.2%, 0.5%, and 1% are
! Selectable rate compensated, fixed temperature for special applications in clean areas. Standard sensitivities
sensing with or without rate-of-rise operation are 1.5%, 2.0%, 2.5%, and 3.7%. Sensitivity is selected and
! Rated spacing distance between sensors: monitored at the fire alarm control panel.*
Fixed Temp. UL & ULC FM Spacing, Either Fixed The sensor head design provides 360° smoke entry for
Setting Spacing Temperature Setting optimum response to smoke from any direction. Due to its
135° F 60 ft x 60 ft 20 ft x 20 ft (6.1 m) for fixed photoelectric operation, air velocity is not normally a factor,
(57.2° C) (18.3 m) temperature only; RTI = Quick except for impact on area smoke flow.
50 ft x 50 ft (15.2 m) for fixed
155° F 40 ft x 40 ft temperature with either rate-of-rise 4-7/8" (124 mm)
(68° C) (12.2 m) selection; RTI = Ultra Fast
LED status indicator
Smoke Sensors: 2-1/8"
! Photoelectric or ionization technology sensing (54 mm)
! 360° smoke entry for optimum response
! Built-in insect screens
4098-9733 Heat Sensor 4098-9714 Photoelectric Sensor with Base
TrueAlarm heat sensors are self-restoring and provide rate 4098-9717 Ionization Sensor
compensated, fixed temperature sensing, selectable with
or without rate-of-rise temperature sensing. Due to its TrueAlarm Ionization sensors use a single radioactive source
small thermal mass, the sensor accurately and quickly with an outer sampling ionization chamber and an inner
measures the local temperature for analysis at the fire reference ionization chamber to provide stable operation
alarm control panel. under fluctuations in environmental conditions such as
Rate-of-rise temperature detection is selectable at the temperature and humidity. Smoke and invisible combustion
control panel for either 15° F (8.3° C) or 20° F (11.1° C) gases can freely penetrate the outer chamber. With both
per minute. Fixed temperature sensing is independent of chambers ionized by a small radioactive source [Am 241
rate-of-rise sensing and programmable to operate at (Americium)], a very small current flows in the circuit. The
135° F (57.2° C) or 155° F (68° C). In a slow developing presence of particles of combustion will cause a change in
fire, the temperature may not increase rapidly enough to the voltage ratio between chambers. This difference is
operate the rate-of-rise feature. However, an alarm will be measured by the electronics in the sensor base and digitally
initiated when the temperature reaches its rated fixed transmitted back to the control panel for processing.
temperature setting. Three levels of sensitivity are available for each ionization
sensor: 0.5, 0.9, and 1.3% per foot of smoke obscuration.
TrueAlarm heat sensors can be programmed as a utility
Sensitivities of 0.5% and 0.9% are for special applications in
device to monitor for temperature extremes in the range
clean areas. Standard sensitivity is 1.3%. Sensitivity is
from 32° F to 155° F (0° C to 68° C). This feature can
selected and monitored at the fire alarm control panel.*
provide freeze warnings or alert to HVAC system
problems. Refer to specific panels for availability.
4-7/8" (124 mm)
4-7/8" (124 mm)
LED status indicator
LED status indicator 2-1/8"
(54 mm)
2-3/8"
(60 mm)

4098-9717 Ionization Sensor with Base

4098-9733 Heat Sensor with Base Application Reference


Sensor locations should be determined only after careful
WARNING: In most fires, hazardous levels of smoke
consideration of the physical layout and contents of the area
and toxic gas can build up before a heat detection to be protected. Refer to NFPA 72, the National Fire Alarm
device would initiate an alarm. In cases where Life and Signaling Code. On smooth ceilings, smoke sensor
Safety is a factor, the use of smoke detection is highly spacing of 30 ft (9.1 m) may be used as a guide.*
recommended. * For detailed application information including sensitivity
selection, refer to Installation Instructions 574-709.
3 S4098-0019-14 11/2012
TrueAlarm Analog Sensing Product Selection Chart
TrueAlarm Sensor Bases
(Refer to Application Manual 574-709 and Installation Instructions 574-707 for additional information)
Model Description Compatibility Mounting Requirements
4” octagonal or 4” square box, 1-1/2” min.
4098-9792 Standard Sensor Base, no options Sensors 4098-9714, -9733, & -9717
depth; or single gang box, 2” min. depth
Sensor Base with connections for Sensors 4098-9714, -9733, & -9717
4” octagonal or 4” square box
4098-9789 Remote LED Alarm Indicator or 2098-9808 remote LED alarm
Unsupervised Relay indicator or 4098-9822 relay Note: Box depth requirements depend on
total wire count and wire size, refer to
Sensor Base with connections for Sensors 4098-9714, -9733, & -9717
accessories list below for reference.
Supervised Remote Relay and 2098-9737 remote relay (supervised)
4098-9791** ** NOTE: 4098-9791 is NOT compatible
connections for Remote Alarm 2098-9808 remote alarm indicator or
Indicator or Unsupervised Relay with the 2120 CDT
4098-9822 relay (unsupervised)
TrueAlarm Sensors
Model Description Compatibility Mounting Requirements
4098-9714 Photoelectric Smoke Sensor
Bases 4098-9792, 4098-9789,
4098-9717 Ionization Smoke Sensor Refer to base requirements
and 4098-9791
4098-9733 Heat Sensor
TrueAlarm Sensor/Base Accessories
Model Description Compatibility Mounting Requirements
Remote Mounting requires 4” octagonal or
Supervised Relay, mounts remote 4” square box, 1-1/2” minimum depth
2098-9737 For use with 4098-9791 base
or in base electrical box Base Mounting requires 4” octagonal box,
2-1/8” deep with 1-1/2” extension ring
Remote Red LED Alarm Indicator
2098-9808 Single gang box, 1-1/2” minimum depth
on single gang stainless steel plate
Relay, tracks base LED status Bases 4098-9789 and 4098-9791
4” octagonal box, 2-1/8” deep with 1-1/2”
4098-9822 (unsupervised, mounts only in base
extension ring
electrical box)
Required for surface or semi-flush
4098-9832 Adapter Plate Bases 4098-9792, -9789, & -9791 mounted 4” square box and for surface
mounted 4” octagonal box

Specifications
General Operating Specifications
MAPNET II or IDNet, auto-select, 24-40 VDC w/data, 400 "A typical,
Communications and Sensor Supervisory Power
1 address per base
2 2
Communications Connections Screw terminals for in/out wiring, 18 to 14 AWG (0.82 mm to 2.08 mm )
Remote LED Alarm Indicator Current 1 mA typical, no impact to alarm current
2
Remote LED Alarm Indicator and Relay Connections Color coded wire leads, 18 AWG (0.82 mm )
UL Listed Temperature Range 32° to 100° F (0° to 38° C)
Operating with 4098-9717 or 4098 -9733 32° to 122° F (0° to 50° C)
Temperature Range with 4098-9714 15° to 122° F (-9° to 50° C)
Humidity Range 10 to 95% RH
Smoke Sensor 4098-9714, Photoelectric Sensor Air velocity = 0-4000 ft/min (0-1220 m/min)
Ambient Ratings 4098-9717, Ionization Sensor Air velocity = 0-200 ft/min (0-61 m/min); Altitude is up to 8000 ft (2.4 km)
Housing Color Frost White
4098-9791 Base With Supervised Remote Relay 2098-9737 (see page 2 for contact ratings)
Externally Supplied Relay Coil Voltage 18-32 VDC (nominal 24 VDC)
Supervisory Current 270 "A, from 24 VDC supply
Alarm Current with 2098-9737 Relay 28 mA, from 24 VDC supply
4098-9822 Unsupervised Relay, Requirements for Bases 4098-9789 and 4098-9791 (see page 2 for contact ratings)
Externally Supplied Relay Coil Voltage 18-32 VDC (nominal 24 VDC)
Supervisory Current Supplied from communications
Alarm Current 13 mA from separate 24 VDC supply

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and
Signaling Code are trademarks of the National Fire Protection Association (NFPA).

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4098-0019-14 11/2012


www.simplexgrinnell.com
© 2012 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
MANUAL PULL STATION
Releasing System Peripherals
UL, ULC Listed; FM MAPNET II® or IDNet™ Communicating Devices;
and CSFM Approved* Addressable Manual Stations for Releasing Applications

Features
Individually addressable manual fire alarm
stations for releasing applications with:
• Power and data supplied via MAPNET II or IDNet
addressable communications using a single wire pair**
• Operation that complies with ADA requirements
PUSH
• Pull lever that protrudes when alarmed
• Break-rod supplied (use is optional)
• Dual action push and pull operation
• Label kit provides for six varieties of releasing
applications (ordered separately)
Compatible with: MANUAL
RELEASE
• Simplex® 4010/4100/4120/4020 fire alarm control
panels equipped with either IDNet or MAPNET II 4099-9012 Addressable Manual Station for Releasing
communications Applications (front and side view)
Compact construction:
• Electronics module enclosure minimizes dust infiltration CLEAN AGENT
RELEASE
• Allows mounting in standard electrical boxes EXTINGUISHING
RELEASE
• Screw terminals for wiring connections
CARBON DIOXIDE
Tamper resistant reset key lock RELEASE

FOAM SYSTEM
• Locks are keyed the same as Simplex fire alarm cabinets RELEASE
Multiple mounting options: SPRINKLER
RELEASE
• Surface or semi-flush with standard boxes or matching
MANUAL
Simplex boxes RELEASE

• Flush mount adapter kit


Label Kit
• Adapters are available for retrofitting to commonly 4099-9802
available existing boxes
UL listed to Standard 38 Operation
Description Activation requires that a spring loaded interference
plate (marked PUSH) be pushed back to access the station
These 4099 series addressable manual stations combine pull lever with a firm downward pull that activates the
the familiar Simplex housing with a compact alarm switch. Completing the action breaks an internal
communication module providing easy installation for plastic break-rod (visible below the pull lever, use is
releasing applications. The integral individual addressable optional). The use of a break-rod can be a deterrent to
module (IAM) monitors status and communicates changes vandalism without interfering with the minimum pull
to the connected control panel via MAPNET II or IDNet requirements needed for easy activation. The pull lever
communications wiring. latches into the alarm position and remains extended out
A blank area on the front of the station allows the of the housing to provide a visible indication.
selection of a label to match the specific releasing Station reset requires the use of a key to reset the
application (label kit is ordered separately). (Refer to data manual station lever and deactivate the alarm switch. (If
sheet S4099-0001 for standard Simplex addressable the break-rod is used, it must be replaced.)
manual stations.) Station testing is performed by physical activation of
the pull lever. Electrical testing can be also performed by
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7150-0026:224 unlocking the station housing to activate the alarm switch.
for allowable values and/or conditions concerning material presented in this document. It is
subject to re-examination, revision, and possible cancellation. This product was not approved ** MAPNET II and IDNet addressable communications designs are protected by U.S. Patent
by MEA (NYC) as of document revision date. Additional listings may be applicable; contact No. 4,796,025.
your local Simplex product supplier for the latest status. Listings and approvals under
Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster.

S4099-0002-1 6/2003
Addressable Manual Station Product Selection
Addressable Manual Stations
Model Description
Double action, Push operation, Addressable manual station; red housing with white letters and white pull
4099-9012
lever; requires label kit 4099-9802
Label kit, white lettering on red background; select the label required for the specific releasing application;
4099-9802
types include: Clean Agent, Extinguishing, Carbon Dioxide, Foam System, Sprinkler, and Manual
Accessories
Model Description Reference
2975-9178 Surface mount steel box, red
Refer to page 3 for dimensions
2975-9022 Cast aluminum surface mount box, red
2099-9813 Semi-flush trim plate for double gang switch box, red
Typically for retrofit, refer to page 4
2099-9814 Surface trim plate for Wiremold box V5744-2, red
2099-9819 Flush mount adapter kit, black
Refer to page 4 for details
2099-9820 Flush mount adapter kit, beige
2099-9804 Replacement break-rod

Specifications

MAPNET II or IDNet, 1 address per station, up to 2500 ft (762 m) from fire alarm control
Power and Communications
panel, up to 10,000 ft (3048 m) total wiring distance (including T-Taps)
Address Means Dipswitch, 8 position
Screw terminal for in/out wiring, for 18 to 14 AWG wire
Wire Connections
Metric wire equivalents: 18 AWG = 0.82 mm2; 14 AWG = 2.08 mm2
UL Listed Temperature Range 32° to 120° F (0° to 49° C) intended for indoor operation
Humidity Range Up to 93% RH at 100° F (38° F)
Housing Color Red with white raised lettering
Material Housing and pull lever are Lexan® polycarbonate or equal
Pull Lever Color White with red raised lettering
Housing Dimensions 5” H x 3-3/4” W x 1” D (127 mm x 95 mm x 25 mm)

Addressable Manual Station Semi-Flush Mounting


Single Gang Box Mount 4" Square Box Mount
Single gang box, 2-1/2" deep 4" (102 mm) square box, 2-1/8" (54 mm) minimum
(64 mm), RACO #500 or equal depth, RACO #231 or equal (supplied by others)
(supplied by others)

Mount flush or with


1/16" (2 mm)
maximum extension
4" Square box
DO NOT RECESS
with cover plate

Station
FIRE ALARM side view

Single gang cover plate, 3/4"


PUSH (19 mm) extension, RACO #773
or equal (supplied by others)
PULL DOWN
Single gang
box outline
Wall surface

Semi-Flush Mount Side View


MANUAL
RELEASE

2 S4099-0002-1 6/2003
Addressable Manual Stations Surface Mounting

2975-9178 Box 2975-9022 Cast Box


Preferred Mounting. For 5-3/16" H x 4" W x 2-3/16" D 5" H x 3-7/8" W x 2-3/16" D
(132 mm x 102 mm x 56 mm) (127 mm x 98 mm x 56 mm)
surface mounting of these (ordered separately) (ordered separately)
addressable manual stations, the
preferred electrical boxes are
shown in the illustration to the
right.
Additional Mounting Knockouts located
Reference. Refer to page 4 for top and bottom
Wiremold box mounting
compatibility.
FIR
FIRE ALARM
E
PUSH
PULL DOWN
Access for 3/4" threaded
5" conduit located top and bottom
(127 mm)

MANUAL
RELEASE
1" (25.4 mm)

3-3/4" (95 mm)

4099 Series Addressable Manual Station

Surface Mount Side View with Internal Detail

1-1/4"
(32 mm) Simplex 2975-9178 box
Field wiring (shown for reference)
(shown for reference)

Address setting under


resealable label (accessible
with cover open)
2-5/8"
(67 mm)

Station cover
hinges open for
installation access

Switch wiring
(prewired)

3 S4099-0002-1 6/2003
Addressable Manual Station, Additional Mounting Information
For retrofit and new
installations, additional
compatible mounting boxes
and the required adapter plates Wiremold
receptacle box
are shown in the illustration to 2099-9814 Surface trim model V5744-2
the right. for Wiremold box (supplied by
5-1/8" H x 5" W others)
(130 mm x 127 mm)

Two gang switch box, each


3" H x 2" W x 2-3/4" D
(76 mm x 51 mm x 70 mm)
(supplied by others)
PUSH

MANUAL
RELEASE

2099-9813 Semi-flush trim for


2-gang switch box, 6" H x 4-1/2" W
(152 mm x 114 mm)

Addressable Manual Station, Flush Mounting Information


Flush mount adapter kit
2099-9819, Black
2099-9820, Beige

Box must be recessed into wall


1" to 1-1/8" (25.4 mm to 29 mm)

8"
(203 mm) PUSH
Hole cutout must be a
minimum of 6" H by 5" W
6" (152 mm by 127 mm)
(152
mm)

MANUAL
RELEASE

4-11/16" (119 mm)


square box, 2-1/8"
(54 mm) minimum
Wall depth (by others)
4-3/4" (121 mm) surface

6-3/4" (171 mm)

Front View Side View

Tyco, Simplex, the Simplex logo, MAPNET II, and IDNet are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries. Lexan is a trademark
of the General Electric Co. Wiremold is a trademark of the Wiremold Company.

Tyco Safety Products Westminster • Westminster, MA • 01441-0001 • USA S4099-0002-1 6/2003


www.tycosafetyproducts-usa-wm.com
© 2003 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
MAINTENANCE SWITCH
+
ABORT SWITCH
Releasing System Peripherals
UL, ULC, CSFM Listed; Fire Suppression System Abort Switches and Releasing
MEA (NYC) Acceptance* Appliance Circuit (RAC) Maintenance Switches

Features
Abort switches provide a manual Fire Suppression
System release abort request:
!" Pushbutton momentary switch is mounted on a
stainless steel single-gang plate FIRE SUPPRESSION
SYSTEM ABORT
!" A protruding collar protects the switch from
accidental contact (collar is removable if required)
!" Available flush or surface mount
!" Flush mounting requires standard single-gang box
!" Surface mounting includes a red mounting box
!" Models are available with internal 1.2 k# resistor for PUSH AND HOLD
current limited operation
Maintenance switches provide a secure and visible
disconnect means for servicing Fire Suppression
System Releasing Appliance Circuits (RACs): Abort Switch
(shown 1/2 size)
!" Maintained position keyswitch is mounted on a
stainless steel double-gang plate
!" Key is removable in either normal or disabled
position
!" Disabled position opens connection to output circuit
and places a 16.2 k# resistor across the input circuit
to initiate a supervisory condition at the host panel
!" Disconnect indicator lamp is a bright incandescent NORMAL
bulb with red lens, powered from separate 24 VDC
0
!" Available for flush or surface mount DISC./
1
!" Flush mounting requires a standard double-gang box DISABLE

!" Surface mount models includes a red mounting box


FIRE SUPPRESSION
UL listed to Standard 864
DISCONNECT / DISABLE
Description
Releasing systems typically require maintenance disconnect
switches and often require abort switches. These abort and Maintenance Switch with Disconnect Indicator Lamp
maintenance switches are clearly labeled and combine easy (shown 1/2 size)
operation with rugged construction for high integrity
operation.

* Refer to page 2 for specific product listings. NOTE: MEA is not applicable to
Maintenance Switches. FM is not applicable to Abort Switches.
As indicated on page 2, these products have been approved by the California State Fire
Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See
CSFM Listing 7300-0026:313 for allowable values and/or conditions concerning material
presented in this document. Abort switches are accepted for use – City of New York
Department of Buildings – MEA35-93E. Maintenance switches were not approved by FM as
of document revision date. Additional listings may be applicable, contact your local Simplex®
product supplier for the latest status. Listings and approvals under Simplex Time Recorder
Co. are the property of Tyco Safety Products Westminster.

S2080-0010-2 11/2006
Product Selection (see page 3 for specifications)

Abort Switches
Model Description Listing Status Details
2080-9056 Flush mount UL, ULC, & CSFM
Single-gang size; includes 3 position contact block housing
Surface mount; includes listed; MEA (NYC)
2080-9057 with one contact block installed
red mounting box Acceptance

Abort Switches for 4004R Series Suppression Release Panel Current Limited Operation
Model Description Listing Status Details
2080-9067 Flush mount UL, ULC, & CSFM Single-gang size; includes 1.2 k#, 1W resistor for current
Surface mount; includes listed; MEA (NYC) limited operation and 3 position contact block housing with
2080-9068 Acceptance one contact block installed
red mounting box
Maintenance Switches with Disconnect Indicator Lamp
Model Description Listing Status Details
2080-9059 Flush mount Double-gang size; includes 3 position contact block housing
UL, ULC, & CSFM with 2 contact blocks installed; disabled position opens
Surface mount; includes listed connection to output and places a 16.2 k# resistor across the
2080-9060
red mounting box input circuit; resistor is removable if required for retrofit
Accessories for Field Installation
Model Description
Additional Contact Block for Abort or Maintenance Switch; 1 Form C contact; UL recognized component for use
2080-9061
with these switches; listings and approvals are not applicable

Abort Switch Installation Reference

Red box is supplied with surface mount


Abort Switch 2080-9057 or 2080-9068
Box width
3" (76 mm) 2-1/4" (56 mm) into box

1/2"
FIRE SUPPRESSION (13 mm)
SYSTEM ABORT Abort Switch
height 4-1/2"
(114 mm)
Box height
4-13/16"
(122 mm)
Switch recess
depth 5/32"
(4 mm)
PUSH AND HOLD

Removable
collar

Abort Switch 2-3/4"


width, 2-3/4" (70 mm) (70 mm)

Supplied gasket attaches to box; NOTE: For flush mounting, use


field installed for flush mount; a 2-3/4" deep (70 mm)
pre-attached for surface mount single-gang box

2 S2080-0010-2 11/2006
Maintenance Switch Installation Reference

Red box is supplied with surface mount


Maintenance Switch 2080-9060
Box dimensions
4-13/16" (122 mm) square 2-1/4" (56 mm) into box

4-1/2"
NORMAL (114 mm)

DISC./
1
DISABLE

FIRE SUPPRESSION
DISCONNECT / DISABLE

Maintenance Switch 2-3/4"


width 4-9/16" (116 mm) (70 mm)

Supplied gasket attaches to box; NOTE: For flush mounting, use


field installed for flush mount; a 2-3/4" deep (70 mm)
pre-attached for surface mount double-gang box

Specifications

Electrical Ratings
Abort Switch; One Contact block Silver contacts; 1 N.O. & 1 N.C.; rated 2 A resistive @ 30 VDC

Maintenance Switch with Lamp; Circuit control: Silver contacts; 1 N.O. & 1 N.C.; rated 2 A resistive @ 30 VDC
Two Contact blocks Lamp control: Silver contacts; 1 Form C; rated 2 A resistive @ 30 VDC
Maintenance Switch Indicator
Replaceable 2 W incandescent bulb; 24 to 30 VDC typical; 83 mA @ 24 VDC; requires
Light (models 2080-9059 and
separate 24 VDC
2080-9060)

Wiring Connections
Abort Switch Terminal blocks for in/out wiring; 18 to 14 AWG wire (0.82 mm2 to 2.08 mm2 )
Abort Switch with Current Limited Terminal blocks for first wire connection; 18 to 14 AWG wire (0.82 mm2 to 2.08 mm2 );
Resistor 18 AWG wire lead for second wire connection
18 AWG (0.82 mm2 ) color coded wire leads for suppression circuit; terminal blocks for
Maintenance Switch 2 2
lamp wiring; 18 to 14 AWG wire (0.82 mm to 2.08 mm )

Environmental Ratings
Temperature Range 32° F to 120° F (0° C to 49° C)
Humidity Range Up to 93% at 90°F (32° C)

3 S2080-0010-2 11/2006
ALARM BELL
Fire Alarm Bell GB
Applications
The GB Series provide durable and dependable operation S E R I E S
required for life safety alarm systems.
Alarm bells are low current, high decibel notification
appliances for use in fire and burglary systems or other
signaling applications. The GB Series is available in
24VDC or 120VAC.
The GB Series is available in 6" or 10" housing and listed
for indoor and outdoor applications. Bells must be used
with the GBBB box for outdoor use.
The GB Series is UL 464 listed and the units are
warrented for 3 years from the date of purchase.

Standard Features GB10 GB6 GBBB

• Available in 24VDC or 120VAC


• Available in 6” or 10” housing Product Listings
• Four wire 24VDC or 120VAC operation
• High dbA output
• Mounts to a standard 4" square electrical box
• UL listed for outdoor use when used with the GBBB
back box • UL 464
• 18 AWG wire leads • CSFM: 7135-0569:139
• BS+A/MEA #285-91-E
• Available in red metal finish • BFP (City of Chicago)
• Meets UL464 requirements
Product Compliance
• NFPA 72

GB Series Alarm Bells 24VDC or 120VAC


Model Number Part Number Voltage Current Draw dBA @ 10ft.
GB6-24 904-1278-002 24VDC 100mA 95
GB10-24 904-1279-002 24VDC 100mA 96
GB6-120 904-1280-002 120VAC 25mA 95
GB10-120 904-1281-002 120VAC 25mA 98
GB
S E R I E S
Dimensions Mounting

GBBB Box

Wiring Diagrams

24 units per carton


44 pounds per carton GB6
50 pounds per carton GB10

Architect & Engineering Specifications


The audible signal shall be Gentex GB Series or approved equal and shall be listed by Underwriters Laboratories, Inc. per
UL 464. The notification appliance shall also be listed with the California State Fire Marshal (CSFM) and the Bureau of
Standards and Appeals (NYC).
The notification appliance shall produce a peak sound output of 95dBA or greater as measured in an anechoic chamber. The
appliance shall be polarized to allow for electrical supervision of the system wiring. The unit will mount to a double gang box or
double workbox without the use of an adapter plate. The GB unit must be used with the GBBB outdoor box for outdoor
applications to meet UL listing requirements.

Important Notice:
These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes
only, are necessarily summary, and are not purported to serve as legal advice and should not be used
551-0042-02
as such. Gentex makes no representations and warranties, express or implied, that these materials
are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws,
regulations and rules. The materials do not address all legal considerations as there is inevitable
uncertainty regarding interpretation of laws, regulations and rules and the application of such laws,
regulations and rules to particular fact patterns. Each person's activities can differently affect the
obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be
used only for informational purposes and should not be used as a substitute for seeking professional
legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the
information contained in this material.
MODULES
Addressable Peripherals
UL, ULC, CSFM Listed; FM Approved; IDNet Addressable Devices, Model 4090-9007
MEA (NYC) Acceptance* Signal IAM (Individual Addressable Module)

Features
Signal IAMs provide additional selective signaling
for Simplex® 4100ES, 4010ES, 4100U, and 4008

8
Series fire alarm control panels:

7
6
+

ADDRESSABLE

5
4
! Signal output notification appliance circuit (NAC)

3
LOOP

2
- SHLD

ON

1
wiring is supervised and connected to the signal input

(STYLE Z)
RETURN
SIGNAL

-
under IDNet communications control

+
-
! NAC output is rated 0.5 A for Special Application or

-
SIGNAL

(STYLE Y)
+ SHLD
Regulated 24 VDC Appliances, or for audio operation

SIGNAL

SHLD +
IN

OUT
(12.5 W @ 25 VRMS, 35 W @ 70.7 VRMS); and can
be wired Class B or Class A; see additional information
on page 2, specifications section
! Signal coding of horn/strobe control, strobe
synchronization, or other coding is provided by the 4090-9007 Signal IAM
signal input; coding at the Signal IAM via IDNet (shown approximately 1/2 size)
addressable communications is not supported
! 4100U compatibility requires Software Revision Description
11.11.01 or higher; also compatible with 4100ES, Additional NAC Operation. For applications requiring
4100U and 4010ES IDNet+ additional individual NAC supervision and control, the
! Signal IAMs are not compatible with 4010 fire alarm 4090-9007 Signal IAM provides a 0.5 A remote NAC
control panels IDNet communications under host panel addressable point control. IDNet
Supervision features: communications monitor the Signal IAM status and then
connects the output NAC to the separate signal input for
! Relay contacts isolate signal inputs from outputs during local alarm notification.
supervision and do not monitor signal presence; signal
NOTE: The Signal IAM provides additional NACs to the
inputs sources will need to be monitored separately
host control panel, it does not provide additional power.
! During supervision, signal outputs are isolated from Refer to the diagram on page 3 for additional system
signal inputs by open contacts allowing consideration for requirements.
use with SCIF applications (Sensitive Compartmented
Audio Control. The Signal IAM also allows the control
Information Facilities)
panel to use IDNet communications to control audio
Operation details: circuits from a compatible Simplex audio control panel.
! Signal IAM operation is powered and supervised by the Only one signal source is used per Signal IAM, separate
IDNet addressable communications loop – separate Signal IAMs would be required for control of DC
24 VDC is not required for the IAM – separate signal powered appliances such as strobes.
power is required for the on-board NAC NOTE: Firefighter phone circuits are not supported.
! Signal IAM communications use a single physical
address; however, each Signal IAM reduces the IDNet Application Reference
loop capacity by two addresses to accommodate the Selective Signaling. Use Signal IAMs to provide
extra power required for output NAC supervision additional local area notification zones per applicable
Compact construction: version of NFPA 72 (the National Fire Alarm and
! Mounts in standard 4” square electrical box Signaling Code), local codes and system requirements.
! Visible LED flashes to indicate communications General Signaling. Use Signal IAMs to connect to
higher current appliances (rated output is 0.5 A).
! Optional covers are available to allow LED to be
viewed after installation For retrofit of Class B NAC wiring, where only two wires
are available, in/out connections can be made at the
! Screw terminals for wiring connections
Signal IAM maintaining appliance wiring supervision per
UL Listed to Standard 864 applicable version of NFPA 72 and local codes .
NOTE: Signal IAM operation is programmed at the fire
* This product has been approved by the California State Fire Marshal (CSFM) pursuant
to Section 13144.1 of the California Health and Safety Code. See CSFM Listings alarm control panel per system requirements.
7300-0026:319, 7165-0026:251, 7165-0026:318, and 7170-0026:250 for allowable
values and/or conditions concerning material presented in this document. It is subject to Wiring Requirements
re-examination, revision, and possible cancellation. Additional listings may be
applicable, contact your local Simplex product supplier for the latest status. Listings and Wire Signal IAMS with both IDNet communications and
approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection signal/NAC input to the latest requirements of UL 864,
Products.
and to NFPA 72 per local code. Please refer to the
diagram on page 3 for additional information.
S4090-0010-6 4/2012
Product Selection

Model Description
Signal IAM; programming types are hardware type SIGNAL for 4008; device type SIGIAM for
4090-9007
4100ES/4100U/4010ES

4090-9801 For semi-flush mounted box Optional trim plate with LED viewing window, includes mounting screws;
4090-9802 For surface mounted box galvanized steel

IDNet Communications Isolator; may be required for loop connections to Signal IAM (see diagram on page 3);
4090-9116
refer to data sheet S4090-0005 for details

4081-9008 End-of-line resistor for Signal IAM NAC output when wired Class B; 10 k", 1/2 W; (ref. 733-894)

Overvoltage Protector; for up to 200 mA DC or IDNet communications; required where wiring exits and enters
2081-9044
a building; refer to data sheet S2081-0016 for details

Specifications
Electrical
Communications 4100ES/4100U/4010ES or 4008 IDNet, one address
Consumes two unit loads (each Signal IAM reduces the IDNet loop capacity by two addresses);
Channel Loading
refer to the IDNet source for the total available address capacity
Nominal 24 VDC from control panel NAC or NAC extender
NAC Input Choices
25 VRMS or 70.7 VRMS from compatible listed audio source
Special Application or Regulated 24 VDC Appliances = 0.5 A
NAC Output Ratings
Audio rating for speakers = 0.5 A @ 25 VRMS (12.5 W) or 70.7 VRMS (35 W)
Compatible with Simplex strobe synchronization; not compatible with SmartSync 2-wire
Appliance Compatibility horn/strobe control or with TrueAlert addressable control; for horn/strobe appliance applications,
Details use 4-wire appliances (see data sheet S4903-0011), for horn control, select horn operation as
free-run
Wire Connections Screw terminals for in/out wiring, 18 to 12 AWG wire (0.82 mm2 to 3.31 mm2 )
End-of-Line Resistor For Class B NAC; 10 k", 1/2 W; 4081-9008
Wiring Distance Information Reference
2500 ft (762 m) maximum distance from panel
Communications
NOTE: Refer to data sheet
(4100ES/4100U/4010E 10,000 ft (3048 m) maximum total wiring distance
S4100-0046 for IDNet+ wiring
S or 4008, IDNet (including T-Taps on Class B wiring)
distances
Channel)
Refer to control panel documentation for additional information
1. Wiring connections from the NAC Riser, through the Signal IAMs, and to the notification
NAC Wiring Distance appliances are branch circuits on the NAC Riser and must be calculated accordingly.
Considerations 2. Wiring distances are limited by wire size and the allowable voltage drop from the fire alarm
(refer to diagram on control panel to the Signal IAM, and then to the farthest notification appliance per branch
page 3) connection. (The Signal IAM voltage drop is considered negligible for wiring distance
calculations.)
Mechanical
Dimensions 4” x 4-1/8” x 1-1/4” D (102 mm x 105 mm x 32 mm)
Temperature Range 32° to 120° F (0° to 49° C) indoor operation only
Humidity Range Up to 93% RH at 100° F (38° C)
Additional Information
Product Document Product Document Product Document
Installation Instructions 579-670 4003EC Voice/Audio Panel S4003-0002 4008 Control Panel S4008-0001
4100ES Basic S4100-0031 4090-9116 IDNet Isolator S4090-0005 4010ES Control Panel S4010-0004
4010ES Control Panel
4100ES Audio S4100-0034 4098-9793 Isolator Base S4098-0025 S4010-0006
(International)

2 S4090-0010-6 4/2012
One-Line Wiring Reference

A/V Note: Use 4-Wire A/Vs Wiring Reference Notes:


(not SmartSync control) with 1. To determine the required NAC and IDNet wiring
the 4090-9007: performance and survivability requirements, circuit
Area 2 4903-9425, 4903-9426, classes, and placement and quantity of isolators, refer
4903-9427, 4903-9431, to the applicable system specifications and/or adopted
4903-9732, 4903-9433 fire code.

Horn/Strobe 2. This reference wiring diagram shows a Class A signal


(A/V) riser providing input to each Signal IAM, and a Class A
IDNet signaling line circuit (SLC) for control of the
Signal IAMs. The IDNet SLC also is shown with short
circuit isolation devices.
Horn
3. Note: Signal Riser wiring is in/out, no "T-tapping" is
allowed.
I
SHLD +
(STYLE Y)

+ SHLD
SIGNAL
OUT

SIGNAL
IN

Strobe
-

-
(STYLE Z)
RETURN
SIGNAL
+

- SHLD
ADDRESSABLE
-

LOOP
ON
1

(V/O)
2
3

Area 1
4
5

+
6
7
8

Typical audible and visible


notification appliances, see A/V note

I
8
7
6
+

ADDRESSABLE

5
4
3
LOOP

2
- SHLD

ON

(STYLE Z)
RETURN
SIGNAL

+ -
-

-
SIGNAL

(STYLE Y)
+ SHLD

SIGNAL

SHLD +
IN

OUT
SHLD +
(STYLE Y)

+ SHLD
SIGNAL
OUT

SIGNAL
IN
-

Signal
(STYLE Z)
RETURN
SIGNAL
+

Return wiring for


- SHLD
ADDRESSABLE
-

LOOP
ON
1
2
3
4
5

IAM
6
7

Class A operation
8

End of line resistor


for Class B operation

Area 3 I
When IDNet SLC isolation is required, use 4090-9116
IDNet addressable isolators or 4098-9793 IDNet
Isolator sensor bases

I Class A IDNet Riser with "T-tapped" branch


connections shown; can be wired in/out at Signal IAM
if desired NOTE: If isolators are used, the first and
last isolators are recommended to be close nippled (in
conduit and within 20 ft (6 m) of the panel); not
necessary when using the 4100-3107 IDNet+ module).

IDNet communications Alternate NAC sources


and NAC source (drawings are not to scale)

4100ES, 4100U, 4010ES or 4008

SYSTEM
POWER ON AC ALARM
TROUBLE STROBE
TROUBLE ACTIVE
ACTIVE

MESSAGES
1 Bell - Fire Alarm

2 Bell - Armed Intruder


CAUTI ON
DI SCO NNECT

3 Bomb Threat

4 Severe Weather

PO W ER
TROU BL E BEFO RE
SILENCE 5 Tone - Severe Weather SERVI CI NG

FIRE SYSTEM SYSTEM ALARM AC


Tone - Attention
ALARM SUPER VISORY TROUBLE SILENCED POWER 6 Emergency
RECORD

7 Chime - Drill

ALARM S UPV TROUBLE ALARM SYSTEM


ACK ACK ACK S ILE NCE RE SET 8 Chime - All Clear
CAUTION
DISCONNECT

4009 IDNet NAC EXTENDER


TM

BATTERY AND
A. C. POWER
BEFORE
SERVICING

Remote
4003EC Voice Control Panel NAC Extender
4100ES, 4100U, or 4010ES Fire 4008 Fire Alarm
Alarm Control Panel Control Panel

4008 NOTE: The 4008 controls the output NACs of these external panels by wired (not IDNet) connections to its NAC outputs;
refer to individual panel installation instructions for details
4100ES/4100U/4010ES NOTES: For use with 4100ES, 4100U, or 4010ES fire alarm control panels, 4009 IDNet NAC Extenders
are controlled by IDNet communications and audio signals are typically provided by the 4100ES or 4100U system audio NACs

3 S4090-0010-6 4/2012
Mounting Information

Signal IAM

Mounting Box (by others): Square box, 4" (102 mm),


4" square cover plate, required depth depends on total conductor requirements
RACO 752 or equal
(by others) Minimum depth = 2-1/8" (54 mm), RACO 232 or equal

Extended depth (for maximum conductors), add 1-1/2"


(38 mm) extension ring, RACO 201 or equal

Mounting Reference with 4" Square Blank Cover Plate

Light pipe for LED viewing

4-9/16" 4-5/16"
(116 mm) (109 mm)

4-9/16" (116 mm) 4-5/16" (109 mm)

4090-9801, Trim plate for 4090-9802, Trim plate for


semi-flush mounted box surface mounted box
Optional Trim Plates for Visible LED

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and
Signaling Code are registered trademarks of the National Fire Protection Association (NFPA).

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4090-0010-6 4/2012


www.simplexgrinnell.com
© 2012 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Multi-Application Peripherals
UL, ULC, CSFM Listed; FM Approved; IDNet™ and MAPNET II® Communicating Devices,
MEA (NYC) Acceptance* Individual Addressable Modules (IAMs)

Features
IDNet or MAPNET II addressable communications
supply both data and power over a single wire pair
to provide**:
Supervised Class B monitoring of normally open, dry
contacts - IDNET IN +
+IDNET IN -

Total wiring distance from IAM to supervision


resistor(s) of up to 500 ft (152 m)
Monitored connection is compatible with Simplex®
2081-9044 Overvoltage Protectors for outdoor wiring or
electrically noisy applications 4090-9001 Supervised IAM
For use in indoor locations up to 158° F (70° C) such as (shown approximately 3/4 size)
attic spaces or similar applications
For use with following Simplex control panels:
Model Series 4008, 4010, 4010ES, 4100U and 4100ES
fire alarm control panels for IDNet communications
Model Series 4100/4100U/4100ES, 4120, 4020, and
2120 Communicating Device Transponders (CDTs)
equipped with MAPNET II communications
Model 4090-9001:
Enclosed design minimizes dust infiltration
Mounts in standard single gang electrical box LISTED
SIGNALING
DEVIC E
ISSUE NO
.
Screw terminals for wiring connections
Visible LED flashes to indicate communications
Optional covers are available to allow LED to be 4090-9051 Supervised IAM
viewed after installation (requires mounting bracket, (shown approximately 3/4 size)
ordered separately)
Model 4090-9051:
Encapsulated design for extended exposure to high
Description
humidity (LED is not present on this model)
Color coded 18 AWG leads for wiring Individual addressable modules (IAMs) receive
IDNet communications provides current limited both power and communications from a two-wire
monitoring: MAPNET II or IDNet circuit. They provide location
specific addressability to a single initiating device (such
Provides monitoring of tamper switch (supervisory)
as single station smoke detector alarm contacts or heat
and waterflow switch (alarm) on same circuit using
detector contacts) or multiple devices at the same location
one point
by monitoring normally open dry contacts and the wiring
Available with IDNet communications only to an end-of-line resistor.
Multiple operation modes are available and are
Model 4090-9001 is packaged in a thermoplastic
selectable at the control panel:
housing and provides screw terminal connections and a
Contact closure status can be tracked status indicating LED.
Momentary contact closure conditions can be selected at
the panel to be latched or tracked (not available with the Model 4090-9051 is an encapsulated package with wire
2120 CDT) leads. It does not provide a status indicating LED.

UL listed to Standard 864


* These products have been approved by the California State Fire Marshal (CSFM) pursuant
to Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7300-0026:223 for allowable values and/or conditions concerning material presented in this
document. It is subject to re-examination, revision, and possible cancellation. Accepted for
use – City of New York Department of Buildings – MEA35-93E. Additional listings may be
applicable; contact your local Simplex product supplier for the latest status. Listings and
approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products
Westminster.

S4090-0001-10
Operation Current Limited Operation Applications
Contact Closure. Closure of the monitored contact(s) For use with IDNet communications only, these
initiates an alarm or other response as programmed at the IAMs can provide quad-state sensing of normal, open
fire alarm control panel. An open in the monitored circuit circuit, short circuit, and current limited conditions.
wiring will cause a trouble to be reported. (Program type is “T-sense.”) With the proper end-of-line
and current limiting resistors, dual functions such as
Panel Selections. Selections can be made at the control
tamper switch and waterflow switch monitoring can be
panel to maintain the alarm condition if the initiating
determined and communicated by a single addressable
device contacts are momentary, such as from a
point.
rate-of-rise heat detector, or to track the device contact
status (not available with the 2120 CDT).

IAM Product Selection


Model Description
4090-9001 Supervised IAM, mounted in thermoplastic housing with screw terminals; see applicable options below
4090-9051 Supervised IAM, encapsulated with wire leads

Optional Trim Plates and Mounting Bracket for Model 4090-9001


Model Description
4090-9806 For semi-flush mounted box Trim plate with LED viewing window, requires 4090-9810 mounting bracket,
4090-9807 For surface mounted box includes mounting screws; galvanized steel

Mounting bracket, mounts IAM to electrical box and provides screw holes for trim plate, required for optional trim
4090-9810
plates

End-of-Line Resistor Harnesses (ordered separately as required)


Model Reference No. Description
4081-9004 733-886 6.8 k , 1/2 W; Standard end-of-line resistor harness for N.O. contact supervision
4081-9003 733-896 4.7 k , 1/2 W
Use for current limited monitoring applications
4081-9005 733-984 1.8 k , 1/2 W

Specifications
Electrical
Power and Communications MAPNET II or IDNet, auto selected, 1 address per IAM
Input Requirements Normally open, dry contacts
Screw terminals for in/out wiring, 18 to 14 AWG wire
4090-9001
Wire Connections (0.82 mm2 to 2.08 mm2)
4090-9051 Color coded wire leads, 18 AWG (0.82 mm2), 8” long (203 mm)
Installation Instructions 574-331 for 4090-9001; 579-572 for 4090-9151
Reference Documents
Field Wiring Diagrams 842-073 for IDNet operation; 841-804 for MAPNET II operation
Wiring Distances
500 ft (152 m) maximum without protectors
Distance from IAM to Contacts
400 ft (122 m) maximum with 2081-9044 Overvoltage Protectors

Wiring Distance Reference per channel, MAPNET II or 2500 ft (762 m) maximum from fire alarm control panel
IDNet Communications 10,000 ft (3048 m) maximum total wiring distance (including T-Taps)
Mechanical
4090-9001 1-9/16” W x 1-3/4” H x 1-1/4” D (40 mm x 44 mm x 32 mm)
Dimensions
4090-9051 1-9/16” W x 1-9/16” H x 9/16” D (40 mm x 40 mm x 14 mm)
Housing Material, 4090-9001 Black thermoplastic
Encapsulation Material, 4090-9051 Epoxy, beige
Temperature Range 32° to 158° F (0° to 70° C); intended for indoor operation
Humidity Range Up to 93% RH at 100° F (38° C)

2 S4090-0001-10
Mounting Information

4090-9001 IDNet Field wiring shown


supervised IAM for reference

- IDNET
LED viewing port
IN +
+IDNET IN -

Single gang electrical


box 2-1/2" (64mm)
minimum depth
(supplied by others)

Address setting under resealable label

Single gang blank cover plate and mounting screws, for use when
LED is not required to be externally viewed (supplied by others)

Mounting Reference, Single Gang Blank Cover Plate

Light pipe for


LED viewing

4-1/4" 4-1/2"
(108 mm) (114 mm)

2-1/2" 2-13/16"
(64 mm) (72 mm)
4090-9810 Mounting
4090-9806, Trim plate for 4090-9807, Trim plate for
bracket, ordered
semi-flush mounted box surface mounted box
separately

NOTE: These mounting plates require mounting bracket 4090-9810.

Optional Trim Plates and Mounting Bracket for Visible LED

3 S4090-0001-10
4090-9051 Mounting Information

Address setting is
at rear of housing

4090-9051
Encapsulated
Supervised IAM

LISTED
SIGNALING
DEVICE
ISSUE NO.

Single gang electrical


box 2-1/2" (64mm)
minimum depth
(supplied by others)

Single gang blank cover plate and


mounting screws (supplied by others)

Tyco is a registered trademark of Tyco International Services GmbH and is used under license. Simplex, the Simplex logo, IDNet, and MAPNET II are trademarks of Tyco
International Ltd. and its affiliates and are used under license.

SimplexGrinnell LP Westminster • Westminster, MA • 01441-0001 • USA S4090-0001-10


www.simplexgrinnell.com
© 2011 Tyco. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
SUPPRESSION RELEASE PERIPHERAL
Releasing Control Fire Alarm Systems
UL, ULC, CSFM Listed; FM Approved; Releasing Control Systems Reference for the
MEA (NYC) Acceptance* 4010 Fire Alarm Control Panel

Features Actuator Control Circuit

Releasing control using the Simplex® 4010 Fire Actuator


Agent
Alarm Control Panel to provide**: Agent
discharge
source
!" Coverage for up to 10 hazard areas of Automatic path

Extinguishing Release and/or Deluge and Preaction


Coil supervisory
Sprinkler System Release module
!" Releasing Appliance Circuit (RAC) control of RED
NAC+

NAC-
BLK
COIL SUPERVISION MODULE (2 AMP) 2081-9046
INSTALLATION INSTRUCTIONS 574-437 REV

DATE CODE:
MAINTAIN 1/4" SEPARATION
BETWEEN POWER LIMITED
(RED/BLK) AND NONPOWER
LIM ITED (YEL/BLK) WIRING
519-958
YEL

BLK
S IM PLE X TIM E RE CORDE R CO. GARDNER M A. US A

compatible Listed/Approved 24 VDC automatic control


actuators, one per circuit; or two 12 VDC actuators in
Release
series per circuit appliance circuit
!" RAC provides short circuit supervision to coil
supervision module Maintenance NORMAL

Disconnect Switch
0

DISC./
1
DISABLE

!" Four, 2 A Notification Appliance Circuits (NACs) in the (with indicator lamp)
FIRE SUPPRESSION
DISCONNECT / DISABLE

Power for
panel for use with Suppression Release Peripherals (SRP) indicator lamp
!" Additional actuator circuit control and additional NACs (if required)
FIRE
are available using 4009 IDNet™ Addressable NAC RELEASING
Suppression
DEVICE
Extenders and Suppression Release Peripherals Release Peripheral

Audible Escalation of Events:


!" Temporal or 20 bpm March Time pattern for first Addressable devices
IDNet
cross-zone alarm communications
!" 120 bpm March Time pattern to indicate releasing timer FIRE SUPPRESSION
SYSTEM ABORT

- IDNET IN +
+I DNET IN -

active
PUSH AND HOLD
MANUAL
RELEASE

Dedicated
!" On steady to indicate releasing timer expired and NAC circuit
actuator is activated
!" NOTE: Requires NACs dedicated to conventional horn
control (not SmartSync™ operation) with strobes FIRE ALARM
CONTROL

controlled on separate NACs FI RE


ALARM

ALARM
ACK
** SYSTEM IS NORMAL **
12:02:15pm
SYSTEM
SUPERVISORY

SUPV
ACK
SYSTEM
TROUBLE

TROUBLE
ACK
Mo n 8-Mar-99
ALARM
SILENCED

ALARM
SILENCE
AC
POWER

SYSTEM
RESET
CAUTION

SUPPRESSION RELEASE PANEL

4009 IDNet NAC Extenders provide:


CAUTION: This Control Unit has been arranged for releasing DISCON NECT
PO WER BEFORE
service. Disable all releasing devicecircuits prior to servicing. SER VIC ING

!" Up to eight NACs for notification requirements and for


NAC input to Suppression Release Peripherals
!" Control is via IDNet addressable communications† 4010 Control Panel with
4090-9005/-9006 Suppression Release Peripheral Suppression Release Appliqué

with Dual Command Control: 4010 Series Releasing Control Typical Block Diagram
!" Dual command control requires that both IDNet
communications commands and an activated NAC are Introduction
present to initiate the desired release
!" NAC provides wiring supervision to the actuator The 4010 series fire alarm control panel is capable of
including monitoring of coil continuity controlling actuators for use in automatic extinguishing,
and deluge or preaction releasing systems. IDNet
Suppression Release Peripheral control features:
addressable communications are used to monitor initiating
!" An on-board DC-DC regulator compensates for devices, and for control of 4009 IDNet NAC extenders
voltage drops to the peripheral and ensures proper and Suppression Release Peripherals. Releasing system
control circuit voltage over a wide operating range
logic is implemented within the 4010 control panel as
!" Provides a single RAC for control of actuators for up required for the local application.
to 1 A using a 2 A NAC input
* 4010 Releasing Control has been approved by the California State Fire Marshal (CSFM)
Related system components: pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM
!" 4010 Series control panel with Releasing Appliqué Listings 7170-0026:226 and 7300-0026:313 for allowable values and/or conditions
concerning material presented in this document. It is subject to re-examination, revision,
!" Dedicated NAC output from 4010 or NAC Extender and possible cancellation. Accepted for use – City of New York Department of Buildings
– MEA35-93E. Additional listings may be applicable; contact your local Simplex product
!" Coil supervision module, one per RAC supplier for the latest status. Listings and approvals under Simplex Time Recorder Co.
!" Maintenance Switch, one per RAC are the property of Tyco Safety Products Westminster.
!" Abort Switch connected via an addressable interface ** This document describes features available with 4010 software revision 3.01 or higher.
Refer to data sheet S4010-0001 for model 4010 control panel details including IDNet
module communications information.
UL listed to Standard 864 † IDNet addressable communications are protected by U.S. Patent 4,796,025.

S4010-0003-4 3/2007
Automatic Extinguishing Release Systems Releasing System Requirements (Continued)
These systems automatically activate electrically 5. FM Approved Automatic Extinguishing Release
controlled actuators for the release of a fire extinguishing requires secondary standby to be a minimum of
agent (such as dry chemical, water spray, foam, CO2, or 24 hours with 5 minutes of alarm. Actuators must be
clean agent) in response to fire detection device inputs as electrically compatible.
determined by programming of the host fire alarm control 6. FM Approved Deluge and Preaction Sprinkler
panel. operation requires that: initiating device circuits be
Automatic Extinguishing Release System Panels Class A and wired to Listed/Approved devices;
are required to have a minimum of 24 hours of standby standby power capacity must be a minimum of 90
power. Initiating devices must be Listed/Approved for the hours with 10 minutes of alarm; and that approved
application, and may be wired either Class A or B. Automatic Water Control Valves must be used. (Refer
Control actuators must be electrically compatible with the to actuator list on page 7.)
control panel circuits and power supplies, and are wired 7. Maintenance Switches, one per RAC, are required
Class B to provide coil supervision. per NFPA 72®, the National Fire Alarm Code® (2002
Edition, Chapter 6) to allow the system to be tested or
Deluge or Preaction Sprinkler Systems serviced without actuating the fire suppression
These systems automatically activate water control systems. Their use may not be allowed in some
actuators in response to fire detection device inputs. jurisdictions, always confirm local requirements.
When used, Simplex Maintenance Switches are
Deluge Sprinkler Systems employ open sprinkler required to ensure that operation initiates a
heads and provide water flow when the fire detection supervisory condition.
system activates a common automatic water control
8. Abort Switches are available when abort operation is
actuator. They are used to deliver water simultaneously
required. When used, connect to an addressable
through all of the system sprinkler heads. This type of
Supervised IAM model 4090-9001 or similar
system is applicable where the immediate application of
addressable adapter module. The Simplex abort switch
large quantities of water over large areas is the proper fire
and the IAM mount in a single gang box, 2-1/2”
response.
minimum depth.
Preaction Sprinkler Systems are similar to deluge 9. Addressable Manual Releasing Stations are used to
systems except that normally closed sprinkler heads are initiate activation of the releasing actuators with the
used and supervisory air pressure is maintained in the appropriate time delay implemented by the fire alarm
pipe. Operation requires both an activated sprinkler head control panel.
and an activated fire alarm initiating device with specific
10. Notification Requirements. Each hazard area
programming determined at the host fire alarm control
typically requires general audible and visible fire
panel.
alarm notification and additional dedicated NACs for
area releasing status notification. Use of the 4009
Releasing System Requirements IDNet NAC Extender will provide the required
1. Releasing actuators are controlled from a additional NACs.
Suppression Release Peripheral (4090-9005 or 11. Additional 4010 Reference. Refer to Installation and
4090-9006). Connections are 2-wire, Class B releasing Operating Instructions 574-052 and Field Wiring
circuits with only one 24 VDC actuator per circuit. Diagram 842-058 for additional 4010 releasing and
Where applicable, two, 12 VDC actuators in series, or general panel information.
one 12 VDC actuator with manufacturer supplied 12. Additional Suppression Release Peripheral
resistor may be used. Reference. Refer to Installation Instructions 579-385.
2. Coil Supervision Module 2081-9046 must be wired
electrically before the actuator and located in the Additional Releasing Systems Reference
actuator wiring junction box. (Refer to diagram on
page 5.) The connected RAC provides continuity For additional information, refer to Factory Mutual
supervision of the actuator coil and wiring and Research Corporation (FMRC) “FMRC Approval Guide,”
provides short circuit supervision to the coil FM Approval standard “Deluge Systems and Preaction
supervision module. Systems.”
3. Cross-zoning or other alarm initiation logic per Please note that proper operation of releasing control
system requirements, is to be implemented by systems requires that the system design, installation, and
programming at the fire alarm control panel. maintenance be performed correctly and in accordance
with all applicable local and national codes, and
4. UL Listed Automatic Extinguishing Releasing
equipment manufacturer’s instructions. No liability for
operation requires that: battery standby must be a
total system operation is assumed or implied.
minimum of 24 hours with 5 minutes of alarm and that
listed actuators are used, refer to list on page 6.

2 S4010-0003-4 3/2007
Product Selection

4010 Releasing Control System Modules


Model Description Reference
Required, one per RAC, mounts in the releasing actuator wiring
2081-9046 Coil Supervision Module
junction box; see specifications section for details
One per RAC; flush or surface mount; indicator lamps require
2080-Series* Maintenance Switches
separate 24 VDC wiring

2080-9056* Flush mount As required, connects via an IDNet addressable interface module;
Abort Switch mounted on a single gang stainless steel plate; installation
2080-9057* Surface mount requires a single gang box, 2-1/2” (64 mm) minimum depth

* Refer to data sheet S2080-0010 for Abort and Maintenance switch details.

4010 Releasing Appliqués, Required for 4010 Suppression Releasing Applications


Model Description
4010-9830 English
Suppression Releasing Appliqué; field applied
4010-9830CAF French

Suppression Release Peripheral and Accessories


Model Description Reference
Basic Suppression Release Peripheral on
4090-9005 Requires mounting box 2975-9227, ordered separately
mounting plate
Suppression Release Peripheral mounted in
4090-9006 Includes LED indicator on front of door
red box; required for ULC listing
2975-9227 Red mounting box; required for 4090-9005
Red LED IDNet communications indicator These items are included with model 4090-9006
4090-9812
option kit; mounts on door of 2975-9227 box

Additional Product Data Sheet Reference

Subject Data Sheet Subject Data Sheet


Releasing System Abort and Maintenance
S2080-0010 4605 Series, 24 Point I/O Annunciator Modules S4010-0002
Switches
Addressable Manual Stations for Releasing
S4099-0002 TrueAlarm® Sensors and Bases S4098-0019
Applications
Addressable Manual Stations for Standard
S4099-0001 TrueAlert® Electronic Horns S4090-0010
Applications
4010 Control Panels S4010-0001 TrueAlert Non-Addressable Strobes (V/O) S4906-0001
Supervised IAM S4090-0001 TrueAlert Non-Addressable 4-Wire Horn/Strobes (A/V) S4903-0011
4010 Compatible Remote Battery Cabinet with
Addressable Zone Adapter Modules S4090-0003 S4081-0001
Charger
4009 IDNet NAC Extender S4009-0002

Contact your local Simplex product supplier for additional information on compatible IDNet addressable devices and TrueAlert
notification appliances.

3 S4010-0003-4 3/2007
4010 System Reference with 4009 IDNet NAC Extenders

4090-9005/-9006 Suppression Actuator Control Circuit


Release Peripheral (SRP)
Agent source

Horn and strobe NACs; FIRE Coil supervisory


4 NACs standard, up to module
RELEASING NORMAL

8 NACs available DISC./

Actuator
COIL SUPERVISION MODULE (2 AMP) 2081-9046
RED INSTALLATION INSTRUCTIONS 574-437 REV YEL

DEVICE
1 NAC+ MAINTAIN 1/4" SEPARATION
DISABLE BETWEEN POWER LIMITED
(RED/BLK) AND NONPOWER S
LIMITED (YEL/BLK) WIRING
DATE CODE: 519-958
BLK
NAC-
BLK SI MPLEX TI ME RECORDER CO. GARDNER MA. USA

FIRE SUPPRESSION
DISCONNECT / DISABLE

Agent discharge path


IDNet communications Dedicated
to up to 5 total 4009 NAC
IDNet NAC Extenders

FIRE SUPPRESSION
SYSTEM ABORT

- IDNET IN +
+IDNET IN -

PUSH AND HOLD


MANUAL
RELEASE

CAUTION
DISCONNECT

POW ER

4009 IDNet
BEFORE
SERVICING

NAC Extender 4009 IDNet NAC EXTENDER


TM 24 VDC for Maintenance Disconnect
(if required) status indicator (if required)

IDNet communications
IDNet communications

Dedicated NAC wiring To SRP, either from 4010


(dashed line) or from 4009 IDNet NAC Extender
FIRE SUPPRESSION
SYSTEM ABORT

- IDNET IN +

Suppression Release Appliqué wording:


+IDNET IN -

PUSH AND HOLD


MANUAL
RELEASE

Supervised IAM with SUPPRESSION RELEASE PANEL


optional Abort Switch CAUTION: This Control Unit has been arranged for releasing
service. Disable all releasing device circuits prior to servicing.
IDNet Addressable devices

FIRE ALARM
CONTROL

** SYSTEM IS NORMAL **
12:02:15pm Mon 8-Mar-99
FIRE SYSTEM SYSTEM ALARM AC

NAC for horn control


ALARM SUPERVISORY TROUBLE SILENCED POWER

ALARM SUPV TROUBLE ALARM SYS TEM


ACK ACK ACK SILENCE RESE T
CAUTION

SUPPRESSION RELEASE PANEL


CAUTION: This Control Unit has been arranged for releasing D ISC ON NECT
POW ER BEFOR E
Use separate NACs
service. Disable all releasing device circuits prior to servicing.

for horn and strobe


SER VIC IN G

control to implement
audible escalation of
events
NAC for strobe control

4010 Control Panel with


Suppression Release Appliqué

4 S4010-0003-4 3/2007
Suppression Release Peripheral Wiring Reference

Maximum Release Appliance Circuit (RAC) Wiring Distances from Suppression Release Peripheral to
the Valve Solenoid (based on a total drop of 0.6 V)
RAC Output Current Distance Total Line
(refer to solenoid
18 AWG 16 AWG 14 AWG Resistance
rating)
0.50 A 74 ft 23 m 118 ft 36 m 188 ft 57 m 1.06 #
0.75 A 50 ft 15 m 79 ft 24 m 126 ft 38 m 0.71 #
1.00 A 37 ft 11 m 59 ft 18 m 94 ft 29 m 0.53 #
2 2 2
Metric wire equivalents: 18 AWG = 0.82 mm ; 16 AWG = 1.31 mm ; 14 AWG = 2.08 mm

Listed/approved actuator or
A Deluge and Preaction
NORMAL Automatic Water Control
0
Valve; one if 24 VDC (or 2 in
1
DISC./ series if 12 VDC) per RAC
DISABLE

FIRE SUPPRESSION Yel Blk


DISCONNECT / DISABLE + Out - Valve wiring
+ In - junction box
Red Blk
Maintenance Disconnect Switch

4090-9005/-9006 Suppression
Release Peripheral Coil Supervision
Module 2081-9046

FIRE NORMAL
COIL SUPERVISION MODULE (2 AMP) 2081-9046
RED INSTALLATION INSTRUCTIONS 574-437 REV YEL

RELEASING
0

1
DISC./ NAC+ MAINTAIN 1/4" SEPARATION
DISABLE
BETWEEN POWER LIMITED
(RED/BLK) AND NONPOWER S

DEVICE FIRE SUPPRESSION LIMITED (YEL/BLK) WIRING


DISCONNECT / DISABLE DATE CODE: 519-958
BLK
NAC-
BLK SIM PLEX TIM E RECORDER CO. GARDNER M A. USA

24 VDC power
for indicator Releasing
lamp (if used) Appliance Circuit

Addressable devices
Class B NAC wiring
dedicated to Suppression
FIRE SUPPRESSION
SYSTEM ABORT
Supervised IAM with
Release Peripheral
- IDNET IN +
+IDNET IN -

PUSH AND HOLD


optional Abort Switch
MANUAL
RELEASE

IDNet communications,
Class A or Class B
To 4009 IDNet NAC Extender or
4010 Fire Alarm Control Panel
FIRE SUPPRESSION
Maximum Notification Appliance Circuit (NAC) Wiring Distances to a Suppression Release Peripheral SYSTEM ABORT
(based on a total drop of 3.4V)
RAC Output Current Distance Total Line
(refer to solenoid
18 AWG 16 AWG 14 AWG Resistance
rating)
0.50 A 250 ft 76 m 399 ft 122 m 635 ft 194 m 3.58 #
PUSH AND HOLD
0.75 A 167 ft 51 m 266 ft 81 m 423 ft 129 m 2.39 #
1.00 A 125 ft 38 m 199 ft 61 m 317 ft 97 m 1.79 #
2 2 2
Metric wire equivalents: 18 AWG = 0.82 mm ; 16 AWG = 1.31 mm ; 14 AWG = 2.08 mm
2080-9056/-9057 Abort
Switch (as required)

5 S4010-0003-4 3/2007
Specifications

Suppression Release Peripheral 4090-9005 and 4090-9006


Communications IDNet, one address
RAC Output Rating, with 4010 control panel* 1 A maximum @ nominal 24 VDC, regulated
Voltage 16 to 32 VDC (nominal 24 VDC)
NAC Power No additional current required, circuit appears as standard end-of-line
Requirements Supervisory Current
(EOL) NAC loading
NOTE: 4010 NACs are RAC Current NAC Current
rated 2 A; 4009 IDNet NAC Alarm Current
0.5 A 0.845 A
Extender standard NACs Reference
are rated at 2 A, Extender 0.75 A 1.28 A
expansion NACs are rated (RAC current =
1.5 A 0.87 A 1.5 A
actuator current)
1A 1.71 A
Screw terminals for input and output wiring, 18 to 12 AWG wire
Wire Connections 2 2
(0.82 mm to 3.31 mm )
Up to 2500 ft (762 m) from the IDNet communications source module
IDNet Wiring Distance Reference Up to 10,000 ft (3048 m) total Class B wiring distance including T-Taps
Compatible with Simplex 2081-9044 Overvoltage Protectors
Dimensions See installation reference on page 8
Operating Temperature 32° to 120° F (0° to 49° C) indoor operation only
Operating Humidity Range 10 to 90% RH at 90° F (32° C)
Coil Supervision Module 2081-9046
Construction Epoxy encapsulated
Dimensions 1-3/8” W x 2-7/16” L x 1-1/16” H (34 mm x 62 mm x 27 mm)
Wiring 18 AWG (0.82 mm2) wire leads, color coded
Current Rating 2 A maximum; internally fused at 3 A, non-replaceable
* Refer to data sheet S4100-0040 for application information when using the Suppression Release Peripheral with the 4100U Series Fire
Alarm Control Panels.

Compatible UL Listed Valves and Actuators

MFG. Model Number MFG. Model Number


*AUTOMAN II-C Assembly (solenoid 17728; coil 25924) 8210A107 (097617-005D coil) 1/2” NPS, 5/8” orifice,
24 VDC
AUTOMAN II-C Explosion-Proof Releasing Device
(solenoid 31492; coil 31438) 8210G207 (238310 coil) 1/2” NPS, 1/2” orifice
*AUTOMAN II-C Assembly (solenoid 68739; coil 25924) 8211A107 (097617-005D coil) 24VDC
ASCO
Solenoid Electric Actuator (solenoid 73111; coil 73097) HV2628571 (23810 coil) N.C. 1/2” NPS, 1/2” orifice
ANSUL *CV90 HF Electric Actuator 73327 (may use 73606 in-line HV2648581 (23810 coil) N.O. 1/2” NPS, 1/2” orifice
resistor) R8210A107 (097617-005D coil) 1/2” NPS, 5/8” orifice
LP CO2 w/ASCO solenoid 422934 T8210A107 (097617-005D coil) 1/2” NPS, 5/8” orifice
LP CO2 double action 24 VDC solenoid 430948 ECH Electrical Control Head (551201)
Pyro-
LP CO2 3-way selector valve solenoid 433419 Chem Explosion-Proof Electric Actuator (570147)
Electric Actuator 24 VDC solenoid 570537 Removable Electric Actuator (570209) 0.2 A
71395SN2ENJ1NOH111C2 (Skinner coil H111C2) 1/4”, NPS, 1/16”
73212BN4TN00NOC111C2 (Skinner coil C111C2) 1/2”, 5-300 psi
Skinner 73212BN4TNLVNOC322C2 (Skinner coil C322C2) 1/2”, NPS, 0.92 A, 250 psi
73218BN4UNLVNOH111C2 (Skinner coil H111C2)
73218BN4UNLVNOC111C2 (Skinner coil C111C2) 1/2”, NPS, 5/8 in. orifice
* 12 VDC coils, either wire two in series for 24 VDC activation, or, if available from manufacturer, use series resistor

6 S4010-0003-4 3/2007
FM Approved Water Control Valves

FM
Manufacturer Model Number Details
Group
A Skinner LV2LBX25* 24 VDC, 11 W, 458 mA, 1/2 inch NPS, 1/2 inch orifice

T8210A107

B ASCO R8210A107 24 VDC, 16.8 W, 700 mA, 1/2 inch NPS, 5/8 inch orifice

8210A107

D ASCO 8210G207 24 VDC, 10.6 W, 440 mA, 1/2 inch NPS, 1/2 inch orifice

73218BN4UNLVNOC111C2* 24 VDC, 10 W, 420 mA, 1/2 inch NPS, 5/8 inch orifice
E Skinner
24 VDC, 10 W, 420 mA, 1/2 inch NPS, 5/8 inch orifice; 5-300 psi rated
73212BN4TN00N0C111C2
working pressure

F Skinner 73212BN4TNLVNOC322C2 24 VDC, 22 W, 1/2 inch NPS, 920 mA, 250 psi (1725 kPa), 1/2 inch orifice

24 VDC, 10 W, 420 mA, 1/4 inch NPS, 1/16 inch orifice, 250 psi
G Skinner 71395SN2ENJ1NOH111C2
(1725 kPa) rated working pressure

I Vitaulic Series 753-E solenoid valve 24 VDC, 8.7 W, 1⁄2 inch NPS, 364 mA, 300 psi (2069 kPa), 1⁄2 inch orifice

11591 and 11592 Normally closed (NC) Explosion proof solenoid valves, 24 VDC, 10 W,
J Viking
1⁄2 inch NPS, 300 psi (2069 kPa), 4.1 Cv
11595 and 11596 Normally open (NO)

K Viking 11601 and 11602 NC solenoid valve, 24 VDC, 9 W, 1⁄2 inch NPS, 250 psi (1725 kPa), 6.2 Cv

* For new applications, LV2LBX25 has been replaced by model number 73218BN4UNLVNOC111C2.

7 S4010-0003-4 3/2007
Suppression Release Peripheral Installation Reference Diagram

2975-9227 Box, red with white


lettering (supplied with 4090-9006)

Door hinges on left and


lifts off for access

4 Knockouts,
one each side

Door height Door screw


8-1/8" fastener
(206 mm)

4090-9812 LED indicator


option (supplied with
4090-9006)
Door depth
1/2" (13 mm)

Door width Box depth


6-1/8" (156 mm) 4" (102 mm)
Box depth with door
4-1/16" (103 mm)

4090-9005 Suppression
Release Peripheral assembly
(supplied with 4090-9006)
NAC +
NAC -

Box height
8" (203 mm)
IDNet+

RAC -
RAC +
IDNet-

ON

1 2 3 4 5 6 7 8

IDNET SUPPRESSION RELEASE PERIPHERAL ASSY 566-104

Box width
6" (152 mm)

Tyco, Simplex, the Simplex logo, TrueAlarm, TrueAlert, and IDNet are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries. NFPA 72
and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).

Tyco Safety Products Westminster • Westminster, MA • 01441-0001 • USA S4010-0003-4 3/2007


www.tycosafetyproducts-usa-wm.com
© 2007 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
HORN & STROBE
DN-7087:C1

SpectrAlert® Advance
Selectable Output
Notification Appliances
Audio/Visual Devices

General
System Sensor® SpectrAlert® Advance selectable-output
horns, strobes and horn/strobes are rich with features guaran-

7087pho1.jpg

7087pho4.jpg
teed to cut installation times and maximize profits. The Spec-
trAlert Advance series of notification appliances is designed to
simplify your installations, with features such as: plug-in
designs, instant feedback messages to ensure correct installa- Indoor Ceiling Outdoor Ceiling
tion of individual devices, and eleven field-selectable candela Horn/Strobe Strobe
settings for wall and ceiling strobes and horn/strobes.
More specifically, when installing Advance products, first
attach a universal mounting plate to a four-inch square, four-

7087pho2.jpg
inch octagon, or double-gang junction box. The two-wire

7087pho3.jpg
mounting plate attaches to a single-gang junction box.
Then, connect the notification appliance circuit wiring to the
SEMS terminals on the mounting plate. Indoor Wall Indoor Ceiling
Horn/Strobe Strobe
Finally, attach the horn, strobe, or horn/strobe to the mounting
plate by inserting the product’s tabs in the mounting plate’s
grooves. The device will rotate into position, locking the prod-
uct’s pins into the mounting plate’s terminals. The device will
temporarily hold in place with a catch until it is secured with a

7087pho5.jpg

7087pho6.jpg
captured mounting screw.
SpectrAlert Advance products allow you to choose:
• 12 or 24 volts. Indoor Wall Outdoor Wall
Horn Strobe
• 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, or 185 can-
dela by way of a rear-mounted slide switch and front view- • Outdoor products rated from –40°F and 151°F (–40°C and
ing window. 66°C).
• Horn tones and volume by way of a rotary switch. • Outdoor products rainproof per UL50 (NEMA 3R) and
weatherproof per NEMA 4X, IP56
• The SpectrAlert Advance series includes outdoor notifica-
tion appliances. Outdoor strobes and horn/strobes (two- • Minimal intrusion into the backbox.
wire and four-wire) are available for wall or ceiling. Outdoor • Horn rated at 88+ dbA at 16 volts.
horns are available for wall only. All System Sensor outdoor • Rotary switch for tone selection.
products are rated between –40°F and 151°F (–40°C and
66°C) in wet or dry applications. • Three horn volume settings.
Models available: • Electrically compatible with existing SpectrAlert products.

• Indoor wall-mount: horn, strobe, 2-wire horn/strobe, 4-wire


horn/strobe.
Engineering Specifications
• Indoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire SpectrAlert Advance horns, strobes, and horn/strobes shall
horn/strobe. mount to a standard 4.0" x 4.0" x 1.5" (10.16 x 10.16 x 3.81
cm) backbox, 4.0" (10.16 cm) octagonal backbox, or a double-
• Outdoor wall-mount: horn, strobe, 2-wire horn/strobe, 4- gang backbox. Two-wire products shall also mount to a single-
wire horn/strobe. gang 2.0" x 4.0" x 1.875" (5.08 x 10.16 x 4.763 cm) backbox. A
• Outdoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire universal mounting plate shall be used for mounting ceiling
horn/strobe. and wall products. The notification appliance circuit wiring
shall terminate at the universal mounting plate. Also, Spec-
Features trAlert Advance products, when used with the Sync•Circuit™
Module accessory, shall be powered from a non-coded notifi-
• Plug-in design. cation appliance circuit output and shall operate on a nominal
• Same mounting plate for wall- and ceiling-mount units. 12 or 24 volts. When used with the Sync•Circuit Module, 12-
• Shorting spring on mounting plate for continuity check volt rated notification appliance circuit outputs shall operate
before installation. between 9 and 17.5 volts; 24-volt rated notification appliance
• Captive mounting screw. circuit outputs shall operate between 17 and 33 volts. Indoor
SpectrAlert Advance products shall operate between 32°F and
• Tamper-resistance capability. 120°F (0°C and 49°C) from a regulated DC, or full-wave-recti-
• Field-selectable candela settings on wall and ceiling units: fied, unfiltered power supply. Strobes and horn/strobes shall
15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, 185. have field-selectable candela settings including 15, 15/75, 30,
• Automatic selection of 12 or 24 volt operation at 15 and 15/ 75, 95, 110, 115, 135, 150, 177, 185.
75 candela.
• Outdoor wall and ceiling products.

DN-7087:C1 • 11/9/11 — Page 1 of 4


STROBE Operating Specifications
The strobe shall be a System Sensor SpectrAlert Advance • Standard operating temperature: 32°F to 120°F (0°C to
Model _______ listed to UL 1971 and shall be approved for fire 49°C).
protective service. The strobe shall be wired as a primary-sig-
naling notification appliance and comply with the Americans • K Series operating temperature: –40°F to 151°F (–40°C
with Disabilities Act requirements for visible signaling appli- to 66°C).
ances, flashing at 1 Hz over the strobe’s entire operating volt- • Humidity range: 10% to 93% non-condensing (indoor
age range. The strobe light shall consist of a xenon flash tube products).
and associated lens/reflector system. • Strobe flash rate: 1 flash per second.
HORN/STROBE COMBINATION • Nominal voltage: regulated 12 VDC/FWR or regulated 24
VDC/FWR. NOTE: Full Wave Rectified (FWR) voltage is a
The horn/strobe shall be a System Sensor SpectrAlert non-regulated, time-varying power source that is used on
Advance Model _______ listed to UL 1971 and UL 464 and some power supply and panel outputs.
shall be approved for fire protective service. The horn/strobe
shall be wired as a primary-signaling notification appliance • Operating voltage range: 8 V to 17.5 V (12 V nominal); or
16 V to 33 V (24 V nominal). NOTE: P, S, PC, and SC prod-
and comply with the Americans with Disabilities Act require-
ucts will operate at 12 V nominal only for 15 cd and 15/75
ments for visible signaling appliances, flashing at 1 Hz over the
strobe’s entire operating voltage range. The strobe light shall cd.
consist of a xenon flash tube and associated lens/reflector sys- • Input terminal wire gauge: 12 to 18 AWG (3.31 to 0.821
tem. The horn shall have three audibility options and an option mm²).
to switch between a Temporal 3 pattern and a Non-Temporal • Ceiling-mount dimensions (including lens): 6.8" diame-
(continuous) pattern. These options are set by a multiple posi- ter x 2.5" deep (17.3 cm diameter x 6.4 cm deep).
tion switch. On four-wire products, the strobe shall be powered • Wall-mount dimensions (including lens): 5.6" H x 4.7" W
independently of the sounder. The horn on horn/strobe models x 2.5" D (14.2 cm H x 11.9 cm W x 6.4 cm D).
shall operate on a coded or non-coded power supply.
• Horn dimensions: 5.6" H x 4.7" W x 1.3" D (14.2 cm H x
OUTDOOR PRODUCTS 11.9 cm W x 3.3 cm D).
SpectrAlert Advance outdoor horns, strobes and horn/strobes
shall be listed for outdoor use by UL and shall operate Agency Listings and Approvals
between –40°F and 151°F (–40°C and 66°C). The products The listings and approvals below apply to SpectrAlert Advance
shall be listed for use with a System Sensor outdoor/weather- Selectable Output Notification Devices. In some cases, certain
proof backbox with half-inch and three-fourths-inch conduit modules may not be listed by certain approval agencies, or
entries. listing may be in process. Consult factory for latest listing sta-
SYNCHRONIZATION MODULE tus.
The module shall be a System Sensor Sync•Circuit MDL3R or • UL Listed: S4011 (HR__, HW__, P2__, P4__, PC2__,
MDL3W listed to UL 464 and shall be approved for fire protec- PC4__ models); S5512 (models SCR, SCRH, SCW,
tive service. The module shall synchronize SpectrAlert strobes SCWH, SR, SRH, SW, SWH); S3593 (SCRHK, SCRK,
at 1 Hz and horns at Temporal 3. Also, while operating the SRHK, SRK).
strobes, the module shall silence the horns on horn/strobe • ULC Listed: S4011 (HRA, HRKA); S5512 (typically “A”
models over a single pair of wires. The module shall mount to models, with exception of outdoor strobes). See Canadian
a 4.688" x 4.688" x 2.125" (11.906 x 11.906 x 5.398 cm) back- data sheet for listings and specifications.
box. The module shall also control two Style Y (class B) cir- • FM approved
cuits or one Style Z (Class A) circuit. The module shall
• MEA: 452-05-E
synchronize multiple zones. Daisy-chaining two or more syn-
chronization modules together will synchronize all the zones • CSFM: 7125-1653:0186 (SCR, SCRH, SCW, SCWH, SR,
they control. The module shall not operate on a coded power SRH, SW, SWH); 7300-1653:0188 (P2_, P4_, PC2_, PC4_
supply. modules); 7135-1653:0189 (HR, HRK, HW); 7300-
1653:0187 (SCRHK, SCRK, SRHK, SRK).

Strobe Current Draw, Horn Current Draw,


UL Maximum (mA RMS) UL Maximum (mA RMS)
8 – 17.5 V 16 – 33 V Sound 8 – 17.5 V 16 – 33 V
Candela dB
DC FWR DC FWR Pattern DC FWR DC FWR
15 123 128 66 71 Temporal High 57 55 69 75
15/75 142 148 77 81 Temporal Medium 44 49 58 69
Standard 30 NA N/A 94 96 Temporal Low 38 44 44 48
Candela 75 NA NA 158 153 Non-temporal High 57 56 69 75
Range 95 NA NA 181 176 Non-temporal Medium 42 50 60 69
110 NA NA 202 195 Non-temporal Low 41 44 50 50
115 NA NA 210 205 Coded High 57 55 69 75
135 NA NA 228 207 Coded Medium 44 51 56 69
High 150 NA NA 246 220 Coded Low 40 46 52 50
Candela
Range 177 NA NA 281 251
185 NA NA 286 258

Page 2 of 4 — DN-7087:C1 • 11/9/11


Horn and Horn/Strobe Horn and Horn/Strobe Output (dBA)
Rotary Switch Setting 8 – 17.5 V 16 – 33 V
Switch Sound
Setting Repetition Rate dB Level dB FW FW
Position Pattern DC DC
1 Temporal horn High R R
2 Temporal horn Medium 1 Temporal High 78 78 84 84
3 Temporal horn Low 2 Temporal Medium 74 74 80 80
4 Normal horn High 3 Temporal Low 71 73 76 76
5 Normal horn Medium 4 Non-temporal High 82 82 88 88
6 Normal horn Low 5 Non-temporal Medium 78 78 85 85
7* Externally coded High 6 Non-temporal Low 75 75 81 81
8* Externally coded Medium 7* Coded High 82 82 88 88
9* Externally coded Low 8* Coded Medium 78 78 85 85
*NOTE: Settings 7, 8, and 9 are not available 9* Coded Low 75 75 81 81
on 2-wire horn/strobe. *NOTE: Settings 7, 8, and 9 are not available on 2-wire horn/strobe.

Two-Wire Horn/Strobe, STANDARD Candela Range (15 – 115 cd),


UL Maximum Current Draw (mA RMS)
Input, Sound Pattern, dB 8 – 17.5 V 16 – 33 V
Level 15 15/75 15 15/75 30 75 95 110 115
DC Input, Temporal, High 137 147 79 90 107 176 194 212 218
DC Input, Temporal, Medium 132 144 69 80 97 157 182 201 210
DC Input, Temporal, Low 132 143 66 77 93 154 179 198 207
DC Input, Non-temporal, High 141 152 91 100 116 176 201 221 229
DC Input, Non-temporal, Medium 133 145 75 85 102 163 187 207 216
DC Input, Non-temporal, Low 131 144 68 79 96 156 182 201 210
FWR Input, Temporal, High 136 155 88 97 112 168 190 210 218
FWR Input, Temporal, Medium 129 152 78 88 103 160 184 202 206
FWR Input, Temporal, Low 129 151 76 86 101 160 184 194 201
FWR Input, Non-temporal, High 142 161 103 112 126 181 203 221 229
FWR Input, Non-temporal, Medium 134 155 85 95 110 166 189 208 216
FWR Input, Non-temporal, Low 132 154 80 90 105 161 184 202 211

Two-Wire Horn/Strobe, HIGH Candela Range (135 – 185 cd),


UL Maximum Current Draw (mA RMS)
16 – 33 V 16 – 33 V
DC Input FWR Input
135 150 177 185 135 150 177 185
DC, Temporal, High 245 259 290 297 FWR, Temporal, High 215 231 258 265
DC, Temporal, Medium 235 253 288 297 FWR, Temporal, Medium 209 224 250 258
DC, Temporal, Low 232 251 282 292 FWR, Temporal, Low 207 221 248 256
DC, Non-temporal, High 255 270 303 309 FWR, Non-temporal, High 233 248 275 281
DC, Non-temporal, Medium 242 259 293 299 FWR, Non-temporal, Medium 219 232 262 267
DC, Non-temporal, Low 238 254 291 295 FWR, Non-temporal, Low 214 229 256 262

7087dim12009.tif

4.7” 6.8”

2.5
5.6”

2.5”

DN-7087:C1 • 11/9/11 — Page 3 of 4


Ordering Information
Model Description Model Description
WALL HORN/STROBES CEILING HORN/STROBES
P2R 2-wire horn/strobe, standard cd, red. PC2R 2-wire horn/strobe, standard cd, red.
P2RH 2-wire horn/strobe, high cd, red. PC2RH 2-wire horn/strobe, high cd, red.
P2RK 2-wire horn/strobe, standard cd, red, outdoor. PC2RK 2-wire horn/strobe, standard cd, red, outdoor.
P2RHK 2-wire horn/strobe, high cd, red, outdoor. PC2RHK 2-wire horn/strobe, high cd, red, outdoor.
P2W 2-wire horn/strobe, standard cd, white. PC2W 2-wire horn/strobe, standard cd, white.
P2WH 2-wire horn/strobe, high cd, white. PC2WH 2-wire horn/strobe, high cd, white.
P4R 4-wire horn/strobe, standard cd, red. PC4R 4-wire horn/strobe, standard cd, red.
P4RH 4-wire horn/strobe, high cd, red. PC4RH 4-wire horn/strobe, high cd, red.
P4RK 4-wire horn/strobe, standard cd, red, outdoor. PC4RK 4-wire horn/strobe, standard cd, red, outdoor.
P4RHK 4-wire horn/strobe, high cd, red, outdoor. PC4RHK 4-wire horn/strobe, high cd, red, outdoor.
P4W 4-wire horn/strobe, standard cd, white. PC4W 4-wire horn/strobe, standard cd, white.
P4WH 4-wire horn/strobe, high cd, white. PC4WH 4-wire horn/strobe, high cd, white.
WALL STROBES CEILING STROBES
SR Strobe, standard cd, red. SCR Strobe, standard cd, red.
SRH Strobe, high cd, red. SCRH Strobe, high cd, red.
SRK Strobe, standard cd, red, outdoor. SCRK Strobe, standard cd, red, outdoor.
SRHK Strobe, high cd, red, outdoor. SCRHK Strobe, high cd, red, outdoor.
SW Strobe, standard cd, white. SCW Strobe, standard cd, white.
SWH Strobe, high cd, white. SCWH Strobe, high cd, white.
ACCESSORIES HORNS
BBS-2A Backbox skirt, wall, red. HR Horn, red.
BBSW-2A Backbox skirt, wall, white. HRK Horn, red, outdoor.
BBSC-2A Backbox skirt, ceiling, red. HW Horn, white.
BBSCW-2A Backbox skirt, ceiling, white. ACCESSORIES, continued
SA-WBB Weatherproof backbox, wall. TR-HS Trim Ring, wall, red, package of 5
SA-WBBC Weatherproof backbox, ceiling. TRW-HS Trim Ring, wall, white, package of 5
WTP Weatherproof, flush mount plate, red TRC-HS Trim Ring, ceiling, red, package of 5
WTPW Weatherproof, flush mount plate, white TRCW-HS Trim Ring, ceiling, white, package of 5
NOTE: “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. “Standard cd” refers to strobes that
include 15, 15/75, 30, 75, 95, 110, and 115 candela settings.
NOTE: For strobes and horn/strobes, add suffix “F” for French or “B” for Bilingual.
NOTE: All outdoor models (“K(A)” suffix) include a plastic weatherproof backbox.
NOTE: Add “-R” to models for weatherproof replacement device (no back box included). Only for use with weatherproof outdoor
flush mounting plate, WTP and WTPW.
NOTE: Add “P” to model for plain housing. (No “FIRE” marking on cover.)

Sync•Circuit™ is a trademark and NOTIFIER® and SpectrAlert® are


registered trademarks of Honeywell International Inc.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com

Page 4 of 4 — DN-7087:C1 • 11/9/11