Datasheet Fire System
Datasheet Fire System
Features
Actuator
Releasing control using the Simplex® 4010ES Agent Agent
Fire Alarm Control Panel to provide: source discharge
Coverage for multiple areas of Automatic Extinguishing Actuator path
Control
Release and/or Deluge and Preaction Sprinkler System Circuit
Release including audible escalation of events Coil supervisory
module
Control of compatible Listed/Approved 24 VDC automatic
control actuators, one per circuit; or two 12 VDC actuators in
COILSUPERVISIONMODULE( 2AMP) 2081 - 9046
RED INST ALLATION INSTRUCT IONS574- 437 REV YEL
NAC+ MAINTAIN1/4 " SEPARATION
BETW EENPOW ERLIMIT ED
( RED/BLK) ANDNONPOW ER S
LIMIT ED( YEL/BLK) W IRING
DATECODE: 519- 9 58
BLK
NAC-
BLK S IMP L E X T IM E R E C O RD E R CO .G A R D N E R MA .U S A
Disconnect Switch
0
DISC./
1
DISABLE
Power for
Additional actuator circuit control and additional NACs are indicator lamp
available using 4009 IDNet Addressable NAC Extenders (if required)
FIRE
and Suppression Release Peripherals RELEASING
Suppression
Audible Escalation of Events: Release Peripheral
DEVICE
Temporal or 20 bpm March Time pattern for first
cross-zone alarm
120 bpm March Time pattern indicates releasing timer active Typical addressable
initiating devices
On steady indicates releasing timer expired and actuator is IDNet
activated communications
FIRE SUPPRESSION
SYSTEM ABORT
Dedicated
PUSH AND HOLD
NAC circuit
on separate NACs
4009 IDNet NAC Extenders provide:
Up to eight NACs for notification requirements and for
NAC input to Suppression Release Peripherals
Control is via IDNet addressable communications SUPPRESSION RELEASE PANEL
2 S4010-0005-3 2/2012
Product Selection
2080-9056* Flush mount As required, connects via an IDNet addressable interface module;
Abort Switch mounted on a single gang stainless steel plate; installation
2080-9057* Surface mount requires a single gang box, 2-1/2” (64 mm) minimum depth
* Refer to data sheet S2080-0010 for Abort and Maintenance switch details.
Contact your local Simplex product supplier for additional information on compatible IDNet addressable devices and TrueAlert
notification appliances.
3 S4010-0005-3 2/2012
4010ES Releasing System One-Line Connection Reference with 4009 IDNet NAC Extenders
0
(FM Approved
DEVICE
1
DISC./ RED
NAC+
COIL SUPERVISIONMODULE( 2AMP) 2081- 9 046
INSTAL LATIONINSTRUCTIONS574- 437 REV
MAINTAIN1/4" SEPARATION
YEL
DISABLE
water valves
BETW EENPOW ERLIMITED
( RED/BLK) ANDNONPOW ER S
LIMITED( YEL/BLK) W IRING
DATECODE: 519- 958 BLK
NAC-
BLK S IMP L E X T IME R E CO R D E R CO .G A R D NE R M A .U S A
FIRE SUPPRESSION
DISCONNECT / DISABLE
Group A, B, D,
E, F, G, or H)
Agent discharge path
IDNet communications
to up to 10 total 4009 Dedicated
IDNet NAC Extenders NAC
FIRE SUPPRESSION
SYSTEM ABORT
- I DNET IN +
+IDNET IN -
CAUTI ON
DI SCO NNECT
4009 IDNet
PO W ER
BEFO RE
SERVI CI NG
IDNet communications
IDNet communications
Dedicated NAC wiring To SRP, either from 4010ES
(dashed line) or from 4009 IDNet NAC Extender
FIRE SUPPRESSION
SYSTEM ABORT
- IDNET IN +
audible escalation of
events
NAC for strobe control
4 S4010-0005-3 2/2012
Suppression Release Peripheral Wiring Reference
Maximum Release Appliance Circuit (RAC) Wiring Distances from Suppression Release Peripheral to
the Valve Solenoid (based on a total drop of 0.6 V)
RAC Output Current Distance Total Line
(refer to solenoid
18 AWG 16 AWG 14 AWG Resistance
rating)
0.50 A 74 ft 23 m 118 ft 36 m 188 ft 57 m 1.06
0.75 A 50 ft 15 m 79 ft 24 m 126 ft 38 m 0.71
1.00 A 37 ft 11 m 59 ft 18 m 94 ft 29 m 0.53
1.25 A 30 ft 9m 47 ft 14 m 75 ft 23 m 1.06
1.5 A 25 ft 7.6 m 39 ft 12 m 63 ft 19 m 0.71
1.75 A 21 ft 6.4 m 34 ft 10 m 54 ft 16 m 0.53
2.00 A 19 ft 5.8 m 30 ft 9m 47 ft 14 m 0.53
2 2 2
Metric wire equivalents: 18 AWG = 0.82 mm ; 16 AWG = 1.31 mm ; 14 AWG = 2.08 mm
NORMAL
DISC./
1
DISABLE
FIRE SUPPRESSION
DISCONNECT / DISABLE
RELEASING
RED INSTALLATIONINSTRUCTIONS574- 437 REV
NAC+ MAINTAIN1/4 " SEPARATION
NORMAL
BETW EENPOW ERLIMITED
( RED/BLK) ANDNONPOW ER S
DISC./
1
DISABLE DATECODE: 519- 958
BLK
NAC-
FIRE SUPPRESSION BLK S IM P L E X T IM E R E C O R D E R C O .G A R D N E R M A .U S A
DISCONNECT / DISABLE
FIRE SUPPRESSION
SYSTEM ABORT
- IDNET IN +
+IDNET IN -
Maximum Notification Appliance Circuit (NAC) Wiring Distances to a Suppression Release Peripheral
(0.5 A to 1.75 A drop is based on a total drop of 3.4V; 2 A drop is based upon a total drop of 1.2 V)
FIRE SUPPRESSION
RAC Output Current Distance SYSTEM ABORT
Total Line
(refer to solenoid
18 AWG 16 AWG 14 AWG Resistance
rating)
0.50 A 250 ft 76 m 399 ft 122 m 635 ft 194 m 3.58
0.75 A 167 ft 51 m 266 ft 81 m 423 ft 129 m 2.39
1.00 A 125 ft 38 m 199 ft 61 m 317 ft 97 m 1.79 PUSH AND HOLD
1.25 A 100 ft 30 m 159 ft 48 m 254 ft 77 m 1.43
1.5 A 84 ft 26 m 133 ft 41 m 212 ft 65 m 1.19
1.75 A 72 ft 22 m 114 ft 35 m 181 ft 55 m 1.02
2.00 A 25 ft 7.6 m 39 ft 12 m 63 ft 19 m 0.36
2 2 2
Metric wire equivalents: 18 AWG = 0.82 mm ; 16 AWG = 1.31 mm ; 14 AWG = 2.08 mm
5 S4010-0005-3 2/2012
Specifications
RAC Output with 4010ES 2 A maximum At nominal 24 VDC, regulated; refer to NAC Power
Rating with 4009 IDNet NAC Extender 1 A maximum Requirements for more detail
6 S4010-0005-3 2/2012
FM Approved Water Control Valves
FM
Manufacturer Model Number Details
Group
A Skinner LV2LBX25* 24 VDC, 11 W, 458 mA, 1/2 inch NPS, 1/2 inch orifice
T8210A107
B ASCO R8210A107 24 VDC, 16.8 W, 700 mA, 1/2 inch NPS, 5/8 inch orifice
8210A107
D ASCO 8210G207 24 VDC, 10.6 W, 440 mA, 1/2 inch NPS, 1/2 inch orifice
73218BN4UNLVNOC111C2* 24 VDC, 10 W, 420 mA, 1/2 inch NPS, 5/8 inch orifice
E Skinner 24 VDC, 10 W, 420 mA, 1/2 inch NPS, 5/8 inch orifice; 5-300 psi rated
73212BN4TN00N0C111C2
working pressure
F Skinner 73212BN4TNLVNOC322C2 24 VDC, 22 W, 1/2 inch NPS, 920 mA, 250 psi (1725 kPa), 1/2 inch orifice
24 VDC, 10 W, 420 mA, 1/4 inch NPS, 1/16 inch orifice, 250 psi
G Skinner 71395SN2ENJ1NOH111C2
(1725 kPa) rated working pressure
I Vitaulic Series 753-E solenoid valve 24 VDC, 8.7 W, 1⁄2 inch NPS, 364 mA, 300 psi (2069 kPa), 1⁄2 inch orifice
11591 and 11592 Normally closed (NC) Explosion proof solenoid valves, 24 VDC, 10 W,
J Viking
1⁄2 inch NPS, 300 psi (2069 kPa), 4.1 Cv
11595 and 11596 Normally open (NO)
K Viking 11601 and 11602 NC solenoid valve, 24 VDC, 9 W, 1⁄2 inch NPS, 250 psi (1725 kPa), 6.2 Cv
* For new applications, LV2LBX25 has been replaced by model number 73218BN4UNLVNOC111C2.
7 S4010-0005-3 2/2012
Suppression Release Peripheral Installation Reference Diagram
4 Knockouts,
one each side
4090-9005 Suppression
Release Peripheral assembly
(supplied with 4090-9006)
NAC +
NAC -
Box height
8" (203 mm)
IDNet+
RAC -
RAC +
IDNet-
ON
1 2 3 4 5 6 7 8
Box width
6" (152 mm)
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.
Features
TrueAlarm analog sensing provides:
! Digital transmission of analog sensor values via IDNet
or MAPNET II two-wire communications
For use with the following Simplex® products:
! 4100ES, 4100U, 4010ES, and 4010 Series control
panels; and 4008 Series control panels with reduced
feature set (refer to data sheet S4008-0001 for details)
! 4020, 4100, and 4120 Series control panels, Universal
Transponders, and 2120 TrueAlarm CDTs equipped for
MAPNET II operation 4098-9714 TrueAlarm Photoelectric
Fire alarm control panel provides: Sensor Mounted in Base
! Peak value logging allowing accurate analysis of each
sensor for individual sensitivity selection Description
! Sensitivity monitoring satisfying NFPA 72 sensitivity
Digital Communication of Analog Sensing.
testing requirements; automatic individual sensor
calibration check verifies sensor integrity TrueAlarm analog sensors provide an analog
measurement digitally communicated to the host control
! Automatic environmental compensation, multi-stage
panel using Simplex addressable communications. At the
alarm operation, and display of sensitivity directly in
control panel, the data is analyzed and an average value is
percent per foot
determined and stored. An alarm or other abnormal
! Ability to display and print detailed sensor information condition is determined by comparing the sensor’s present
in plain English language value against its average value and time.
Photoelectric smoke sensors provide:
! Seven levels of sensitivity from 0.2% to 3.7% Intelligent Data Evaluation. Monitoring each sensor’s
(refer to additional information on page 3) average value provides a continuously shifting reference
point. This software filtering process compensates for
Heat sensors provide:
environmental factors (dust, dirt, etc.) and component
! Fixed temperature sensing
aging, providing an accurate reference for evaluating new
! Rate-of-rise temperature sensing activity. With this filtering, there is a significant reduction
! Utility temperature sensing in the probability of false or nuisance alarms caused by
! Listed to UL 521 and ULC-S530 shifts in sensitivity, either up or down.
Ionization smoke sensors provide: Control Panel Selection. Peak activity per sensor is
! Three levels of sensitivity; 0.5%, 0.9%, and 1.3% stored to assist in evaluating specific locations. The alarm
(refer to additional information on page 3) set point for each TrueAlarm sensor is determined at the
General features: host control panel, selectable as more or less sensitive as
! Listed to UL 268 and ULC-S529 the individual application requires.
! Louvered smoke sensor design enhances smoke
capture by directing flow to chamber; entrance areas Timed/Multi-Stage Selection. Sensor alarm set points
are minimally visible when ceiling mounted can be programmed for timed automatic sensitivity
selection (such as more sensitive at night, less sensitive
! Designed for EMI compatibility
during day). Control panel programming can also provide
! Magnetic test feature is provided multi-stage operation per sensor. For example, a 0.2%
! Optional accessories include remote LED alarm level may cause a warning to prompt investigation while a
indicator and output relays 2.5% level may initiate an alarm.
Additional base reference:
Sensor Alarm and Trouble LED Indication. Each
! For isolator bases, refer to data sheet S4098-0025
sensor base’s LED pulses to indicate communications
! For sounder bases, refer to data sheet S4098-0028 with the panel. If the control panel determines a sensor is
! For photo/heat sensors, refer to data sheet S4098-0024 in alarm, or is dirty or has some other type of trouble, the
(single address) and S4098-0033 (dual address) details are annunciated at the control panel and that sensor
* These products have been approved by the California State Fire Marshal (CSFM) pursuant to base’s LED will be turned on steadily. During a system
Section 13144.1 of the California Health and Safety Code. See CSFM Listings
7272-0026:218, 7271-0026:231, 7270-0026:216, and 7300-0026:217 for allowable values
alarm, the control panel will control the LEDs such that
and/or conditions concerning material presented in this document. It is subject to an LED indicating a trouble will return to pulsing to help
re-examination, revision, and possible cancellation. Accepted for use – City of New York identify the alarmed sensors.
Department of Buildings – MEA35-93E. Additional listings may be applicable, contact your
local Simplex product supplier for the latest status. Listings and approvals under Simplex
Time Recorder Co. are the property of Tyco Fire Protection Products.
S4098-0019-14 11/2012
TrueAlarm Sensor Bases and Accessories Description
Sensor Base Features TrueAlarm sensor bases contain integral addressable
electronics that constantly monitor the status of the
Base mounted address selection: detachable photoelectric, ionization, or heat sensors. Each
! Address remains with its programmed location sensor’s output is digitized and transmitted to the system
! Accessible from front (DIP switch under sensor) fire alarm control panel every four seconds.
General features: Since TrueAlarm sensors use the same base, different
! Automatic identification provides default sensitivity sensor types can be easily interchanged to meet specific
when substituting sensor types location requirements. This feature also allows intentional
! Integral red LED for power-on (pulsing), or alarm or sensor substitution during building construction. When
trouble (steady on) conditions are temporarily dusty, instead of covering the
smoke sensors (causing them to be disabled), heat sensors
! Locking anti-tamper design mounts on standard outlet
may be installed without reprogramming the control
box
panel. Although the control panel will indicate an
! Magnetically operated functional test incorrect sensor type, the heat sensor will operate at a
Sensor Bases default sensitivity providing heat detection for building
protection at that location.
4098-9792, Standard sensor base
4098-9789, Sensor base with wired connections for: Mounting Reference
! 2098-9808 Remote LED alarm indicator or 4098-9822 Electrical Box Requirements: (boxes are by others)
relay (unsupervised) Without relay: 4" octagonal or 4" square, 1-1/2" deep;
4098-9791, Sensor base with supervised relay driver single gang, 2" deep
output (not compatible with 2120 CDT): With relay : 4" octagonal or 4" square, 1-1/2" deep,
with 1-1/2" extension ring
! Relay operation is programmable and can be manually
operated from control panel 4" (102 mm) Square Box 4" (102 mm) Octagonal Box
TrueAlarm Bases
4098-9789, -9791, & -9792
2 S4098-0019-14 11/2012
TrueAlarm Sensors 4098-9714 Photoelectric Sensor
Features TrueAlarm photoelectric sensors use a stable, pulsed
Sealed against rear air flow entry infrared LED light source and a silicon photodiode receiver
to provide consistent and accurate low power smoke
Interchangeable mounting
sensing. Seven levels of sensitivity are available for each
EMI/RFI shielded electronics individual sensor, ranging from 0.2% to 3.7% per foot of
Heat sensors: smoke obscuration. Sensitivities of 0.2%, 0.5%, and 1% are
! Selectable rate compensated, fixed temperature for special applications in clean areas. Standard sensitivities
sensing with or without rate-of-rise operation are 1.5%, 2.0%, 2.5%, and 3.7%. Sensitivity is selected and
! Rated spacing distance between sensors: monitored at the fire alarm control panel.*
Fixed Temp. UL & ULC FM Spacing, Either Fixed The sensor head design provides 360° smoke entry for
Setting Spacing Temperature Setting optimum response to smoke from any direction. Due to its
135° F 60 ft x 60 ft 20 ft x 20 ft (6.1 m) for fixed photoelectric operation, air velocity is not normally a factor,
(57.2° C) (18.3 m) temperature only; RTI = Quick except for impact on area smoke flow.
50 ft x 50 ft (15.2 m) for fixed
155° F 40 ft x 40 ft temperature with either rate-of-rise 4-7/8" (124 mm)
(68° C) (12.2 m) selection; RTI = Ultra Fast
LED status indicator
Smoke Sensors: 2-1/8"
! Photoelectric or ionization technology sensing (54 mm)
! 360° smoke entry for optimum response
! Built-in insect screens
4098-9733 Heat Sensor 4098-9714 Photoelectric Sensor with Base
TrueAlarm heat sensors are self-restoring and provide rate 4098-9717 Ionization Sensor
compensated, fixed temperature sensing, selectable with
or without rate-of-rise temperature sensing. Due to its TrueAlarm Ionization sensors use a single radioactive source
small thermal mass, the sensor accurately and quickly with an outer sampling ionization chamber and an inner
measures the local temperature for analysis at the fire reference ionization chamber to provide stable operation
alarm control panel. under fluctuations in environmental conditions such as
Rate-of-rise temperature detection is selectable at the temperature and humidity. Smoke and invisible combustion
control panel for either 15° F (8.3° C) or 20° F (11.1° C) gases can freely penetrate the outer chamber. With both
per minute. Fixed temperature sensing is independent of chambers ionized by a small radioactive source [Am 241
rate-of-rise sensing and programmable to operate at (Americium)], a very small current flows in the circuit. The
135° F (57.2° C) or 155° F (68° C). In a slow developing presence of particles of combustion will cause a change in
fire, the temperature may not increase rapidly enough to the voltage ratio between chambers. This difference is
operate the rate-of-rise feature. However, an alarm will be measured by the electronics in the sensor base and digitally
initiated when the temperature reaches its rated fixed transmitted back to the control panel for processing.
temperature setting. Three levels of sensitivity are available for each ionization
sensor: 0.5, 0.9, and 1.3% per foot of smoke obscuration.
TrueAlarm heat sensors can be programmed as a utility
Sensitivities of 0.5% and 0.9% are for special applications in
device to monitor for temperature extremes in the range
clean areas. Standard sensitivity is 1.3%. Sensitivity is
from 32° F to 155° F (0° C to 68° C). This feature can
selected and monitored at the fire alarm control panel.*
provide freeze warnings or alert to HVAC system
problems. Refer to specific panels for availability.
4-7/8" (124 mm)
4-7/8" (124 mm)
LED status indicator
LED status indicator 2-1/8"
(54 mm)
2-3/8"
(60 mm)
Specifications
General Operating Specifications
MAPNET II or IDNet, auto-select, 24-40 VDC w/data, 400 "A typical,
Communications and Sensor Supervisory Power
1 address per base
2 2
Communications Connections Screw terminals for in/out wiring, 18 to 14 AWG (0.82 mm to 2.08 mm )
Remote LED Alarm Indicator Current 1 mA typical, no impact to alarm current
2
Remote LED Alarm Indicator and Relay Connections Color coded wire leads, 18 AWG (0.82 mm )
UL Listed Temperature Range 32° to 100° F (0° to 38° C)
Operating with 4098-9717 or 4098 -9733 32° to 122° F (0° to 50° C)
Temperature Range with 4098-9714 15° to 122° F (-9° to 50° C)
Humidity Range 10 to 95% RH
Smoke Sensor 4098-9714, Photoelectric Sensor Air velocity = 0-4000 ft/min (0-1220 m/min)
Ambient Ratings 4098-9717, Ionization Sensor Air velocity = 0-200 ft/min (0-61 m/min); Altitude is up to 8000 ft (2.4 km)
Housing Color Frost White
4098-9791 Base With Supervised Remote Relay 2098-9737 (see page 2 for contact ratings)
Externally Supplied Relay Coil Voltage 18-32 VDC (nominal 24 VDC)
Supervisory Current 270 "A, from 24 VDC supply
Alarm Current with 2098-9737 Relay 28 mA, from 24 VDC supply
4098-9822 Unsupervised Relay, Requirements for Bases 4098-9789 and 4098-9791 (see page 2 for contact ratings)
Externally Supplied Relay Coil Voltage 18-32 VDC (nominal 24 VDC)
Supervisory Current Supplied from communications
Alarm Current 13 mA from separate 24 VDC supply
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and
Signaling Code are trademarks of the National Fire Protection Association (NFPA).
Features
Individually addressable manual fire alarm
stations for releasing applications with:
• Power and data supplied via MAPNET II or IDNet
addressable communications using a single wire pair**
• Operation that complies with ADA requirements
PUSH
• Pull lever that protrudes when alarmed
• Break-rod supplied (use is optional)
• Dual action push and pull operation
• Label kit provides for six varieties of releasing
applications (ordered separately)
Compatible with: MANUAL
RELEASE
• Simplex® 4010/4100/4120/4020 fire alarm control
panels equipped with either IDNet or MAPNET II 4099-9012 Addressable Manual Station for Releasing
communications Applications (front and side view)
Compact construction:
• Electronics module enclosure minimizes dust infiltration CLEAN AGENT
RELEASE
• Allows mounting in standard electrical boxes EXTINGUISHING
RELEASE
• Screw terminals for wiring connections
CARBON DIOXIDE
Tamper resistant reset key lock RELEASE
FOAM SYSTEM
• Locks are keyed the same as Simplex fire alarm cabinets RELEASE
Multiple mounting options: SPRINKLER
RELEASE
• Surface or semi-flush with standard boxes or matching
MANUAL
Simplex boxes RELEASE
S4099-0002-1 6/2003
Addressable Manual Station Product Selection
Addressable Manual Stations
Model Description
Double action, Push operation, Addressable manual station; red housing with white letters and white pull
4099-9012
lever; requires label kit 4099-9802
Label kit, white lettering on red background; select the label required for the specific releasing application;
4099-9802
types include: Clean Agent, Extinguishing, Carbon Dioxide, Foam System, Sprinkler, and Manual
Accessories
Model Description Reference
2975-9178 Surface mount steel box, red
Refer to page 3 for dimensions
2975-9022 Cast aluminum surface mount box, red
2099-9813 Semi-flush trim plate for double gang switch box, red
Typically for retrofit, refer to page 4
2099-9814 Surface trim plate for Wiremold box V5744-2, red
2099-9819 Flush mount adapter kit, black
Refer to page 4 for details
2099-9820 Flush mount adapter kit, beige
2099-9804 Replacement break-rod
Specifications
MAPNET II or IDNet, 1 address per station, up to 2500 ft (762 m) from fire alarm control
Power and Communications
panel, up to 10,000 ft (3048 m) total wiring distance (including T-Taps)
Address Means Dipswitch, 8 position
Screw terminal for in/out wiring, for 18 to 14 AWG wire
Wire Connections
Metric wire equivalents: 18 AWG = 0.82 mm2; 14 AWG = 2.08 mm2
UL Listed Temperature Range 32° to 120° F (0° to 49° C) intended for indoor operation
Humidity Range Up to 93% RH at 100° F (38° F)
Housing Color Red with white raised lettering
Material Housing and pull lever are Lexan® polycarbonate or equal
Pull Lever Color White with red raised lettering
Housing Dimensions 5” H x 3-3/4” W x 1” D (127 mm x 95 mm x 25 mm)
Station
FIRE ALARM side view
2 S4099-0002-1 6/2003
Addressable Manual Stations Surface Mounting
MANUAL
RELEASE
1" (25.4 mm)
1-1/4"
(32 mm) Simplex 2975-9178 box
Field wiring (shown for reference)
(shown for reference)
Station cover
hinges open for
installation access
Switch wiring
(prewired)
3 S4099-0002-1 6/2003
Addressable Manual Station, Additional Mounting Information
For retrofit and new
installations, additional
compatible mounting boxes
and the required adapter plates Wiremold
receptacle box
are shown in the illustration to 2099-9814 Surface trim model V5744-2
the right. for Wiremold box (supplied by
5-1/8" H x 5" W others)
(130 mm x 127 mm)
MANUAL
RELEASE
8"
(203 mm) PUSH
Hole cutout must be a
minimum of 6" H by 5" W
6" (152 mm by 127 mm)
(152
mm)
MANUAL
RELEASE
Tyco, Simplex, the Simplex logo, MAPNET II, and IDNet are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries. Lexan is a trademark
of the General Electric Co. Wiremold is a trademark of the Wiremold Company.
Features
Abort switches provide a manual Fire Suppression
System release abort request:
!" Pushbutton momentary switch is mounted on a
stainless steel single-gang plate FIRE SUPPRESSION
SYSTEM ABORT
!" A protruding collar protects the switch from
accidental contact (collar is removable if required)
!" Available flush or surface mount
!" Flush mounting requires standard single-gang box
!" Surface mounting includes a red mounting box
!" Models are available with internal 1.2 k# resistor for PUSH AND HOLD
current limited operation
Maintenance switches provide a secure and visible
disconnect means for servicing Fire Suppression
System Releasing Appliance Circuits (RACs): Abort Switch
(shown 1/2 size)
!" Maintained position keyswitch is mounted on a
stainless steel double-gang plate
!" Key is removable in either normal or disabled
position
!" Disabled position opens connection to output circuit
and places a 16.2 k# resistor across the input circuit
to initiate a supervisory condition at the host panel
!" Disconnect indicator lamp is a bright incandescent NORMAL
bulb with red lens, powered from separate 24 VDC
0
!" Available for flush or surface mount DISC./
1
!" Flush mounting requires a standard double-gang box DISABLE
* Refer to page 2 for specific product listings. NOTE: MEA is not applicable to
Maintenance Switches. FM is not applicable to Abort Switches.
As indicated on page 2, these products have been approved by the California State Fire
Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See
CSFM Listing 7300-0026:313 for allowable values and/or conditions concerning material
presented in this document. Abort switches are accepted for use – City of New York
Department of Buildings – MEA35-93E. Maintenance switches were not approved by FM as
of document revision date. Additional listings may be applicable, contact your local Simplex®
product supplier for the latest status. Listings and approvals under Simplex Time Recorder
Co. are the property of Tyco Safety Products Westminster.
S2080-0010-2 11/2006
Product Selection (see page 3 for specifications)
Abort Switches
Model Description Listing Status Details
2080-9056 Flush mount UL, ULC, & CSFM
Single-gang size; includes 3 position contact block housing
Surface mount; includes listed; MEA (NYC)
2080-9057 with one contact block installed
red mounting box Acceptance
Abort Switches for 4004R Series Suppression Release Panel Current Limited Operation
Model Description Listing Status Details
2080-9067 Flush mount UL, ULC, & CSFM Single-gang size; includes 1.2 k#, 1W resistor for current
Surface mount; includes listed; MEA (NYC) limited operation and 3 position contact block housing with
2080-9068 Acceptance one contact block installed
red mounting box
Maintenance Switches with Disconnect Indicator Lamp
Model Description Listing Status Details
2080-9059 Flush mount Double-gang size; includes 3 position contact block housing
UL, ULC, & CSFM with 2 contact blocks installed; disabled position opens
Surface mount; includes listed connection to output and places a 16.2 k# resistor across the
2080-9060
red mounting box input circuit; resistor is removable if required for retrofit
Accessories for Field Installation
Model Description
Additional Contact Block for Abort or Maintenance Switch; 1 Form C contact; UL recognized component for use
2080-9061
with these switches; listings and approvals are not applicable
1/2"
FIRE SUPPRESSION (13 mm)
SYSTEM ABORT Abort Switch
height 4-1/2"
(114 mm)
Box height
4-13/16"
(122 mm)
Switch recess
depth 5/32"
(4 mm)
PUSH AND HOLD
Removable
collar
2 S2080-0010-2 11/2006
Maintenance Switch Installation Reference
4-1/2"
NORMAL (114 mm)
DISC./
1
DISABLE
FIRE SUPPRESSION
DISCONNECT / DISABLE
Specifications
Electrical Ratings
Abort Switch; One Contact block Silver contacts; 1 N.O. & 1 N.C.; rated 2 A resistive @ 30 VDC
Maintenance Switch with Lamp; Circuit control: Silver contacts; 1 N.O. & 1 N.C.; rated 2 A resistive @ 30 VDC
Two Contact blocks Lamp control: Silver contacts; 1 Form C; rated 2 A resistive @ 30 VDC
Maintenance Switch Indicator
Replaceable 2 W incandescent bulb; 24 to 30 VDC typical; 83 mA @ 24 VDC; requires
Light (models 2080-9059 and
separate 24 VDC
2080-9060)
Wiring Connections
Abort Switch Terminal blocks for in/out wiring; 18 to 14 AWG wire (0.82 mm2 to 2.08 mm2 )
Abort Switch with Current Limited Terminal blocks for first wire connection; 18 to 14 AWG wire (0.82 mm2 to 2.08 mm2 );
Resistor 18 AWG wire lead for second wire connection
18 AWG (0.82 mm2 ) color coded wire leads for suppression circuit; terminal blocks for
Maintenance Switch 2 2
lamp wiring; 18 to 14 AWG wire (0.82 mm to 2.08 mm )
Environmental Ratings
Temperature Range 32° F to 120° F (0° C to 49° C)
Humidity Range Up to 93% at 90°F (32° C)
3 S2080-0010-2 11/2006
ALARM BELL
Fire Alarm Bell GB
Applications
The GB Series provide durable and dependable operation S E R I E S
required for life safety alarm systems.
Alarm bells are low current, high decibel notification
appliances for use in fire and burglary systems or other
signaling applications. The GB Series is available in
24VDC or 120VAC.
The GB Series is available in 6" or 10" housing and listed
for indoor and outdoor applications. Bells must be used
with the GBBB box for outdoor use.
The GB Series is UL 464 listed and the units are
warrented for 3 years from the date of purchase.
GBBB Box
Wiring Diagrams
Important Notice:
These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes
only, are necessarily summary, and are not purported to serve as legal advice and should not be used
551-0042-02
as such. Gentex makes no representations and warranties, express or implied, that these materials
are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws,
regulations and rules. The materials do not address all legal considerations as there is inevitable
uncertainty regarding interpretation of laws, regulations and rules and the application of such laws,
regulations and rules to particular fact patterns. Each person's activities can differently affect the
obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be
used only for informational purposes and should not be used as a substitute for seeking professional
legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the
information contained in this material.
MODULES
Addressable Peripherals
UL, ULC, CSFM Listed; FM Approved; IDNet Addressable Devices, Model 4090-9007
MEA (NYC) Acceptance* Signal IAM (Individual Addressable Module)
Features
Signal IAMs provide additional selective signaling
for Simplex® 4100ES, 4010ES, 4100U, and 4008
8
Series fire alarm control panels:
7
6
+
ADDRESSABLE
5
4
! Signal output notification appliance circuit (NAC)
3
LOOP
2
- SHLD
ON
1
wiring is supervised and connected to the signal input
(STYLE Z)
RETURN
SIGNAL
-
under IDNet communications control
+
-
! NAC output is rated 0.5 A for Special Application or
-
SIGNAL
(STYLE Y)
+ SHLD
Regulated 24 VDC Appliances, or for audio operation
SIGNAL
SHLD +
IN
OUT
(12.5 W @ 25 VRMS, 35 W @ 70.7 VRMS); and can
be wired Class B or Class A; see additional information
on page 2, specifications section
! Signal coding of horn/strobe control, strobe
synchronization, or other coding is provided by the 4090-9007 Signal IAM
signal input; coding at the Signal IAM via IDNet (shown approximately 1/2 size)
addressable communications is not supported
! 4100U compatibility requires Software Revision Description
11.11.01 or higher; also compatible with 4100ES, Additional NAC Operation. For applications requiring
4100U and 4010ES IDNet+ additional individual NAC supervision and control, the
! Signal IAMs are not compatible with 4010 fire alarm 4090-9007 Signal IAM provides a 0.5 A remote NAC
control panels IDNet communications under host panel addressable point control. IDNet
Supervision features: communications monitor the Signal IAM status and then
connects the output NAC to the separate signal input for
! Relay contacts isolate signal inputs from outputs during local alarm notification.
supervision and do not monitor signal presence; signal
NOTE: The Signal IAM provides additional NACs to the
inputs sources will need to be monitored separately
host control panel, it does not provide additional power.
! During supervision, signal outputs are isolated from Refer to the diagram on page 3 for additional system
signal inputs by open contacts allowing consideration for requirements.
use with SCIF applications (Sensitive Compartmented
Audio Control. The Signal IAM also allows the control
Information Facilities)
panel to use IDNet communications to control audio
Operation details: circuits from a compatible Simplex audio control panel.
! Signal IAM operation is powered and supervised by the Only one signal source is used per Signal IAM, separate
IDNet addressable communications loop – separate Signal IAMs would be required for control of DC
24 VDC is not required for the IAM – separate signal powered appliances such as strobes.
power is required for the on-board NAC NOTE: Firefighter phone circuits are not supported.
! Signal IAM communications use a single physical
address; however, each Signal IAM reduces the IDNet Application Reference
loop capacity by two addresses to accommodate the Selective Signaling. Use Signal IAMs to provide
extra power required for output NAC supervision additional local area notification zones per applicable
Compact construction: version of NFPA 72 (the National Fire Alarm and
! Mounts in standard 4” square electrical box Signaling Code), local codes and system requirements.
! Visible LED flashes to indicate communications General Signaling. Use Signal IAMs to connect to
higher current appliances (rated output is 0.5 A).
! Optional covers are available to allow LED to be
viewed after installation For retrofit of Class B NAC wiring, where only two wires
are available, in/out connections can be made at the
! Screw terminals for wiring connections
Signal IAM maintaining appliance wiring supervision per
UL Listed to Standard 864 applicable version of NFPA 72 and local codes .
NOTE: Signal IAM operation is programmed at the fire
* This product has been approved by the California State Fire Marshal (CSFM) pursuant
to Section 13144.1 of the California Health and Safety Code. See CSFM Listings alarm control panel per system requirements.
7300-0026:319, 7165-0026:251, 7165-0026:318, and 7170-0026:250 for allowable
values and/or conditions concerning material presented in this document. It is subject to Wiring Requirements
re-examination, revision, and possible cancellation. Additional listings may be
applicable, contact your local Simplex product supplier for the latest status. Listings and Wire Signal IAMS with both IDNet communications and
approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection signal/NAC input to the latest requirements of UL 864,
Products.
and to NFPA 72 per local code. Please refer to the
diagram on page 3 for additional information.
S4090-0010-6 4/2012
Product Selection
Model Description
Signal IAM; programming types are hardware type SIGNAL for 4008; device type SIGIAM for
4090-9007
4100ES/4100U/4010ES
4090-9801 For semi-flush mounted box Optional trim plate with LED viewing window, includes mounting screws;
4090-9802 For surface mounted box galvanized steel
IDNet Communications Isolator; may be required for loop connections to Signal IAM (see diagram on page 3);
4090-9116
refer to data sheet S4090-0005 for details
4081-9008 End-of-line resistor for Signal IAM NAC output when wired Class B; 10 k", 1/2 W; (ref. 733-894)
Overvoltage Protector; for up to 200 mA DC or IDNet communications; required where wiring exits and enters
2081-9044
a building; refer to data sheet S2081-0016 for details
Specifications
Electrical
Communications 4100ES/4100U/4010ES or 4008 IDNet, one address
Consumes two unit loads (each Signal IAM reduces the IDNet loop capacity by two addresses);
Channel Loading
refer to the IDNet source for the total available address capacity
Nominal 24 VDC from control panel NAC or NAC extender
NAC Input Choices
25 VRMS or 70.7 VRMS from compatible listed audio source
Special Application or Regulated 24 VDC Appliances = 0.5 A
NAC Output Ratings
Audio rating for speakers = 0.5 A @ 25 VRMS (12.5 W) or 70.7 VRMS (35 W)
Compatible with Simplex strobe synchronization; not compatible with SmartSync 2-wire
Appliance Compatibility horn/strobe control or with TrueAlert addressable control; for horn/strobe appliance applications,
Details use 4-wire appliances (see data sheet S4903-0011), for horn control, select horn operation as
free-run
Wire Connections Screw terminals for in/out wiring, 18 to 12 AWG wire (0.82 mm2 to 3.31 mm2 )
End-of-Line Resistor For Class B NAC; 10 k", 1/2 W; 4081-9008
Wiring Distance Information Reference
2500 ft (762 m) maximum distance from panel
Communications
NOTE: Refer to data sheet
(4100ES/4100U/4010E 10,000 ft (3048 m) maximum total wiring distance
S4100-0046 for IDNet+ wiring
S or 4008, IDNet (including T-Taps on Class B wiring)
distances
Channel)
Refer to control panel documentation for additional information
1. Wiring connections from the NAC Riser, through the Signal IAMs, and to the notification
NAC Wiring Distance appliances are branch circuits on the NAC Riser and must be calculated accordingly.
Considerations 2. Wiring distances are limited by wire size and the allowable voltage drop from the fire alarm
(refer to diagram on control panel to the Signal IAM, and then to the farthest notification appliance per branch
page 3) connection. (The Signal IAM voltage drop is considered negligible for wiring distance
calculations.)
Mechanical
Dimensions 4” x 4-1/8” x 1-1/4” D (102 mm x 105 mm x 32 mm)
Temperature Range 32° to 120° F (0° to 49° C) indoor operation only
Humidity Range Up to 93% RH at 100° F (38° C)
Additional Information
Product Document Product Document Product Document
Installation Instructions 579-670 4003EC Voice/Audio Panel S4003-0002 4008 Control Panel S4008-0001
4100ES Basic S4100-0031 4090-9116 IDNet Isolator S4090-0005 4010ES Control Panel S4010-0004
4010ES Control Panel
4100ES Audio S4100-0034 4098-9793 Isolator Base S4098-0025 S4010-0006
(International)
2 S4090-0010-6 4/2012
One-Line Wiring Reference
+ SHLD
SIGNAL
OUT
SIGNAL
IN
Strobe
-
-
(STYLE Z)
RETURN
SIGNAL
+
- SHLD
ADDRESSABLE
-
LOOP
ON
1
(V/O)
2
3
Area 1
4
5
+
6
7
8
I
8
7
6
+
ADDRESSABLE
5
4
3
LOOP
2
- SHLD
ON
(STYLE Z)
RETURN
SIGNAL
+ -
-
-
SIGNAL
(STYLE Y)
+ SHLD
SIGNAL
SHLD +
IN
OUT
SHLD +
(STYLE Y)
+ SHLD
SIGNAL
OUT
SIGNAL
IN
-
Signal
(STYLE Z)
RETURN
SIGNAL
+
LOOP
ON
1
2
3
4
5
IAM
6
7
Class A operation
8
Area 3 I
When IDNet SLC isolation is required, use 4090-9116
IDNet addressable isolators or 4098-9793 IDNet
Isolator sensor bases
SYSTEM
POWER ON AC ALARM
TROUBLE STROBE
TROUBLE ACTIVE
ACTIVE
MESSAGES
1 Bell - Fire Alarm
3 Bomb Threat
4 Severe Weather
PO W ER
TROU BL E BEFO RE
SILENCE 5 Tone - Severe Weather SERVI CI NG
7 Chime - Drill
BATTERY AND
A. C. POWER
BEFORE
SERVICING
Remote
4003EC Voice Control Panel NAC Extender
4100ES, 4100U, or 4010ES Fire 4008 Fire Alarm
Alarm Control Panel Control Panel
4008 NOTE: The 4008 controls the output NACs of these external panels by wired (not IDNet) connections to its NAC outputs;
refer to individual panel installation instructions for details
4100ES/4100U/4010ES NOTES: For use with 4100ES, 4100U, or 4010ES fire alarm control panels, 4009 IDNet NAC Extenders
are controlled by IDNet communications and audio signals are typically provided by the 4100ES or 4100U system audio NACs
3 S4090-0010-6 4/2012
Mounting Information
Signal IAM
4-9/16" 4-5/16"
(116 mm) (109 mm)
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and
Signaling Code are registered trademarks of the National Fire Protection Association (NFPA).
Features
IDNet or MAPNET II addressable communications
supply both data and power over a single wire pair
to provide**:
Supervised Class B monitoring of normally open, dry
contacts - IDNET IN +
+IDNET IN -
S4090-0001-10
Operation Current Limited Operation Applications
Contact Closure. Closure of the monitored contact(s) For use with IDNet communications only, these
initiates an alarm or other response as programmed at the IAMs can provide quad-state sensing of normal, open
fire alarm control panel. An open in the monitored circuit circuit, short circuit, and current limited conditions.
wiring will cause a trouble to be reported. (Program type is “T-sense.”) With the proper end-of-line
and current limiting resistors, dual functions such as
Panel Selections. Selections can be made at the control
tamper switch and waterflow switch monitoring can be
panel to maintain the alarm condition if the initiating
determined and communicated by a single addressable
device contacts are momentary, such as from a
point.
rate-of-rise heat detector, or to track the device contact
status (not available with the 2120 CDT).
Mounting bracket, mounts IAM to electrical box and provides screw holes for trim plate, required for optional trim
4090-9810
plates
Specifications
Electrical
Power and Communications MAPNET II or IDNet, auto selected, 1 address per IAM
Input Requirements Normally open, dry contacts
Screw terminals for in/out wiring, 18 to 14 AWG wire
4090-9001
Wire Connections (0.82 mm2 to 2.08 mm2)
4090-9051 Color coded wire leads, 18 AWG (0.82 mm2), 8” long (203 mm)
Installation Instructions 574-331 for 4090-9001; 579-572 for 4090-9151
Reference Documents
Field Wiring Diagrams 842-073 for IDNet operation; 841-804 for MAPNET II operation
Wiring Distances
500 ft (152 m) maximum without protectors
Distance from IAM to Contacts
400 ft (122 m) maximum with 2081-9044 Overvoltage Protectors
Wiring Distance Reference per channel, MAPNET II or 2500 ft (762 m) maximum from fire alarm control panel
IDNet Communications 10,000 ft (3048 m) maximum total wiring distance (including T-Taps)
Mechanical
4090-9001 1-9/16” W x 1-3/4” H x 1-1/4” D (40 mm x 44 mm x 32 mm)
Dimensions
4090-9051 1-9/16” W x 1-9/16” H x 9/16” D (40 mm x 40 mm x 14 mm)
Housing Material, 4090-9001 Black thermoplastic
Encapsulation Material, 4090-9051 Epoxy, beige
Temperature Range 32° to 158° F (0° to 70° C); intended for indoor operation
Humidity Range Up to 93% RH at 100° F (38° C)
2 S4090-0001-10
Mounting Information
- IDNET
LED viewing port
IN +
+IDNET IN -
Single gang blank cover plate and mounting screws, for use when
LED is not required to be externally viewed (supplied by others)
4-1/4" 4-1/2"
(108 mm) (114 mm)
2-1/2" 2-13/16"
(64 mm) (72 mm)
4090-9810 Mounting
4090-9806, Trim plate for 4090-9807, Trim plate for
bracket, ordered
semi-flush mounted box surface mounted box
separately
3 S4090-0001-10
4090-9051 Mounting Information
Address setting is
at rear of housing
4090-9051
Encapsulated
Supervised IAM
LISTED
SIGNALING
DEVICE
ISSUE NO.
Tyco is a registered trademark of Tyco International Services GmbH and is used under license. Simplex, the Simplex logo, IDNet, and MAPNET II are trademarks of Tyco
International Ltd. and its affiliates and are used under license.
NAC-
BLK
COIL SUPERVISION MODULE (2 AMP) 2081-9046
INSTALLATION INSTRUCTIONS 574-437 REV
DATE CODE:
MAINTAIN 1/4" SEPARATION
BETWEEN POWER LIMITED
(RED/BLK) AND NONPOWER
LIM ITED (YEL/BLK) WIRING
519-958
YEL
BLK
S IM PLE X TIM E RE CORDE R CO. GARDNER M A. US A
Disconnect Switch
0
DISC./
1
DISABLE
!" Four, 2 A Notification Appliance Circuits (NACs) in the (with indicator lamp)
FIRE SUPPRESSION
DISCONNECT / DISABLE
Power for
panel for use with Suppression Release Peripherals (SRP) indicator lamp
!" Additional actuator circuit control and additional NACs (if required)
FIRE
are available using 4009 IDNet™ Addressable NAC RELEASING
Suppression
DEVICE
Extenders and Suppression Release Peripherals Release Peripheral
- IDNET IN +
+I DNET IN -
active
PUSH AND HOLD
MANUAL
RELEASE
Dedicated
!" On steady to indicate releasing timer expired and NAC circuit
actuator is activated
!" NOTE: Requires NACs dedicated to conventional horn
control (not SmartSync™ operation) with strobes FIRE ALARM
CONTROL
ALARM
ACK
** SYSTEM IS NORMAL **
12:02:15pm
SYSTEM
SUPERVISORY
SUPV
ACK
SYSTEM
TROUBLE
TROUBLE
ACK
Mo n 8-Mar-99
ALARM
SILENCED
ALARM
SILENCE
AC
POWER
SYSTEM
RESET
CAUTION
with Dual Command Control: 4010 Series Releasing Control Typical Block Diagram
!" Dual command control requires that both IDNet
communications commands and an activated NAC are Introduction
present to initiate the desired release
!" NAC provides wiring supervision to the actuator The 4010 series fire alarm control panel is capable of
including monitoring of coil continuity controlling actuators for use in automatic extinguishing,
and deluge or preaction releasing systems. IDNet
Suppression Release Peripheral control features:
addressable communications are used to monitor initiating
!" An on-board DC-DC regulator compensates for devices, and for control of 4009 IDNet NAC extenders
voltage drops to the peripheral and ensures proper and Suppression Release Peripherals. Releasing system
control circuit voltage over a wide operating range
logic is implemented within the 4010 control panel as
!" Provides a single RAC for control of actuators for up required for the local application.
to 1 A using a 2 A NAC input
* 4010 Releasing Control has been approved by the California State Fire Marshal (CSFM)
Related system components: pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM
!" 4010 Series control panel with Releasing Appliqué Listings 7170-0026:226 and 7300-0026:313 for allowable values and/or conditions
concerning material presented in this document. It is subject to re-examination, revision,
!" Dedicated NAC output from 4010 or NAC Extender and possible cancellation. Accepted for use – City of New York Department of Buildings
– MEA35-93E. Additional listings may be applicable; contact your local Simplex product
!" Coil supervision module, one per RAC supplier for the latest status. Listings and approvals under Simplex Time Recorder Co.
!" Maintenance Switch, one per RAC are the property of Tyco Safety Products Westminster.
!" Abort Switch connected via an addressable interface ** This document describes features available with 4010 software revision 3.01 or higher.
Refer to data sheet S4010-0001 for model 4010 control panel details including IDNet
module communications information.
UL listed to Standard 864 † IDNet addressable communications are protected by U.S. Patent 4,796,025.
S4010-0003-4 3/2007
Automatic Extinguishing Release Systems Releasing System Requirements (Continued)
These systems automatically activate electrically 5. FM Approved Automatic Extinguishing Release
controlled actuators for the release of a fire extinguishing requires secondary standby to be a minimum of
agent (such as dry chemical, water spray, foam, CO2, or 24 hours with 5 minutes of alarm. Actuators must be
clean agent) in response to fire detection device inputs as electrically compatible.
determined by programming of the host fire alarm control 6. FM Approved Deluge and Preaction Sprinkler
panel. operation requires that: initiating device circuits be
Automatic Extinguishing Release System Panels Class A and wired to Listed/Approved devices;
are required to have a minimum of 24 hours of standby standby power capacity must be a minimum of 90
power. Initiating devices must be Listed/Approved for the hours with 10 minutes of alarm; and that approved
application, and may be wired either Class A or B. Automatic Water Control Valves must be used. (Refer
Control actuators must be electrically compatible with the to actuator list on page 7.)
control panel circuits and power supplies, and are wired 7. Maintenance Switches, one per RAC, are required
Class B to provide coil supervision. per NFPA 72®, the National Fire Alarm Code® (2002
Edition, Chapter 6) to allow the system to be tested or
Deluge or Preaction Sprinkler Systems serviced without actuating the fire suppression
These systems automatically activate water control systems. Their use may not be allowed in some
actuators in response to fire detection device inputs. jurisdictions, always confirm local requirements.
When used, Simplex Maintenance Switches are
Deluge Sprinkler Systems employ open sprinkler required to ensure that operation initiates a
heads and provide water flow when the fire detection supervisory condition.
system activates a common automatic water control
8. Abort Switches are available when abort operation is
actuator. They are used to deliver water simultaneously
required. When used, connect to an addressable
through all of the system sprinkler heads. This type of
Supervised IAM model 4090-9001 or similar
system is applicable where the immediate application of
addressable adapter module. The Simplex abort switch
large quantities of water over large areas is the proper fire
and the IAM mount in a single gang box, 2-1/2”
response.
minimum depth.
Preaction Sprinkler Systems are similar to deluge 9. Addressable Manual Releasing Stations are used to
systems except that normally closed sprinkler heads are initiate activation of the releasing actuators with the
used and supervisory air pressure is maintained in the appropriate time delay implemented by the fire alarm
pipe. Operation requires both an activated sprinkler head control panel.
and an activated fire alarm initiating device with specific
10. Notification Requirements. Each hazard area
programming determined at the host fire alarm control
typically requires general audible and visible fire
panel.
alarm notification and additional dedicated NACs for
area releasing status notification. Use of the 4009
Releasing System Requirements IDNet NAC Extender will provide the required
1. Releasing actuators are controlled from a additional NACs.
Suppression Release Peripheral (4090-9005 or 11. Additional 4010 Reference. Refer to Installation and
4090-9006). Connections are 2-wire, Class B releasing Operating Instructions 574-052 and Field Wiring
circuits with only one 24 VDC actuator per circuit. Diagram 842-058 for additional 4010 releasing and
Where applicable, two, 12 VDC actuators in series, or general panel information.
one 12 VDC actuator with manufacturer supplied 12. Additional Suppression Release Peripheral
resistor may be used. Reference. Refer to Installation Instructions 579-385.
2. Coil Supervision Module 2081-9046 must be wired
electrically before the actuator and located in the Additional Releasing Systems Reference
actuator wiring junction box. (Refer to diagram on
page 5.) The connected RAC provides continuity For additional information, refer to Factory Mutual
supervision of the actuator coil and wiring and Research Corporation (FMRC) “FMRC Approval Guide,”
provides short circuit supervision to the coil FM Approval standard “Deluge Systems and Preaction
supervision module. Systems.”
3. Cross-zoning or other alarm initiation logic per Please note that proper operation of releasing control
system requirements, is to be implemented by systems requires that the system design, installation, and
programming at the fire alarm control panel. maintenance be performed correctly and in accordance
with all applicable local and national codes, and
4. UL Listed Automatic Extinguishing Releasing
equipment manufacturer’s instructions. No liability for
operation requires that: battery standby must be a
total system operation is assumed or implied.
minimum of 24 hours with 5 minutes of alarm and that
listed actuators are used, refer to list on page 6.
2 S4010-0003-4 3/2007
Product Selection
2080-9056* Flush mount As required, connects via an IDNet addressable interface module;
Abort Switch mounted on a single gang stainless steel plate; installation
2080-9057* Surface mount requires a single gang box, 2-1/2” (64 mm) minimum depth
* Refer to data sheet S2080-0010 for Abort and Maintenance switch details.
Contact your local Simplex product supplier for additional information on compatible IDNet addressable devices and TrueAlert
notification appliances.
3 S4010-0003-4 3/2007
4010 System Reference with 4009 IDNet NAC Extenders
Actuator
COIL SUPERVISION MODULE (2 AMP) 2081-9046
RED INSTALLATION INSTRUCTIONS 574-437 REV YEL
DEVICE
1 NAC+ MAINTAIN 1/4" SEPARATION
DISABLE BETWEEN POWER LIMITED
(RED/BLK) AND NONPOWER S
LIMITED (YEL/BLK) WIRING
DATE CODE: 519-958
BLK
NAC-
BLK SI MPLEX TI ME RECORDER CO. GARDNER MA. USA
FIRE SUPPRESSION
DISCONNECT / DISABLE
FIRE SUPPRESSION
SYSTEM ABORT
- IDNET IN +
+IDNET IN -
CAUTION
DISCONNECT
POW ER
4009 IDNet
BEFORE
SERVICING
IDNet communications
IDNet communications
- IDNET IN +
FIRE ALARM
CONTROL
** SYSTEM IS NORMAL **
12:02:15pm Mon 8-Mar-99
FIRE SYSTEM SYSTEM ALARM AC
control to implement
audible escalation of
events
NAC for strobe control
4 S4010-0003-4 3/2007
Suppression Release Peripheral Wiring Reference
Maximum Release Appliance Circuit (RAC) Wiring Distances from Suppression Release Peripheral to
the Valve Solenoid (based on a total drop of 0.6 V)
RAC Output Current Distance Total Line
(refer to solenoid
18 AWG 16 AWG 14 AWG Resistance
rating)
0.50 A 74 ft 23 m 118 ft 36 m 188 ft 57 m 1.06 #
0.75 A 50 ft 15 m 79 ft 24 m 126 ft 38 m 0.71 #
1.00 A 37 ft 11 m 59 ft 18 m 94 ft 29 m 0.53 #
2 2 2
Metric wire equivalents: 18 AWG = 0.82 mm ; 16 AWG = 1.31 mm ; 14 AWG = 2.08 mm
Listed/approved actuator or
A Deluge and Preaction
NORMAL Automatic Water Control
0
Valve; one if 24 VDC (or 2 in
1
DISC./ series if 12 VDC) per RAC
DISABLE
4090-9005/-9006 Suppression
Release Peripheral Coil Supervision
Module 2081-9046
FIRE NORMAL
COIL SUPERVISION MODULE (2 AMP) 2081-9046
RED INSTALLATION INSTRUCTIONS 574-437 REV YEL
RELEASING
0
1
DISC./ NAC+ MAINTAIN 1/4" SEPARATION
DISABLE
BETWEEN POWER LIMITED
(RED/BLK) AND NONPOWER S
24 VDC power
for indicator Releasing
lamp (if used) Appliance Circuit
Addressable devices
Class B NAC wiring
dedicated to Suppression
FIRE SUPPRESSION
SYSTEM ABORT
Supervised IAM with
Release Peripheral
- IDNET IN +
+IDNET IN -
IDNet communications,
Class A or Class B
To 4009 IDNet NAC Extender or
4010 Fire Alarm Control Panel
FIRE SUPPRESSION
Maximum Notification Appliance Circuit (NAC) Wiring Distances to a Suppression Release Peripheral SYSTEM ABORT
(based on a total drop of 3.4V)
RAC Output Current Distance Total Line
(refer to solenoid
18 AWG 16 AWG 14 AWG Resistance
rating)
0.50 A 250 ft 76 m 399 ft 122 m 635 ft 194 m 3.58 #
PUSH AND HOLD
0.75 A 167 ft 51 m 266 ft 81 m 423 ft 129 m 2.39 #
1.00 A 125 ft 38 m 199 ft 61 m 317 ft 97 m 1.79 #
2 2 2
Metric wire equivalents: 18 AWG = 0.82 mm ; 16 AWG = 1.31 mm ; 14 AWG = 2.08 mm
2080-9056/-9057 Abort
Switch (as required)
5 S4010-0003-4 3/2007
Specifications
6 S4010-0003-4 3/2007
FM Approved Water Control Valves
FM
Manufacturer Model Number Details
Group
A Skinner LV2LBX25* 24 VDC, 11 W, 458 mA, 1/2 inch NPS, 1/2 inch orifice
T8210A107
B ASCO R8210A107 24 VDC, 16.8 W, 700 mA, 1/2 inch NPS, 5/8 inch orifice
8210A107
D ASCO 8210G207 24 VDC, 10.6 W, 440 mA, 1/2 inch NPS, 1/2 inch orifice
73218BN4UNLVNOC111C2* 24 VDC, 10 W, 420 mA, 1/2 inch NPS, 5/8 inch orifice
E Skinner
24 VDC, 10 W, 420 mA, 1/2 inch NPS, 5/8 inch orifice; 5-300 psi rated
73212BN4TN00N0C111C2
working pressure
F Skinner 73212BN4TNLVNOC322C2 24 VDC, 22 W, 1/2 inch NPS, 920 mA, 250 psi (1725 kPa), 1/2 inch orifice
24 VDC, 10 W, 420 mA, 1/4 inch NPS, 1/16 inch orifice, 250 psi
G Skinner 71395SN2ENJ1NOH111C2
(1725 kPa) rated working pressure
I Vitaulic Series 753-E solenoid valve 24 VDC, 8.7 W, 1⁄2 inch NPS, 364 mA, 300 psi (2069 kPa), 1⁄2 inch orifice
11591 and 11592 Normally closed (NC) Explosion proof solenoid valves, 24 VDC, 10 W,
J Viking
1⁄2 inch NPS, 300 psi (2069 kPa), 4.1 Cv
11595 and 11596 Normally open (NO)
K Viking 11601 and 11602 NC solenoid valve, 24 VDC, 9 W, 1⁄2 inch NPS, 250 psi (1725 kPa), 6.2 Cv
* For new applications, LV2LBX25 has been replaced by model number 73218BN4UNLVNOC111C2.
7 S4010-0003-4 3/2007
Suppression Release Peripheral Installation Reference Diagram
4 Knockouts,
one each side
4090-9005 Suppression
Release Peripheral assembly
(supplied with 4090-9006)
NAC +
NAC -
Box height
8" (203 mm)
IDNet+
RAC -
RAC +
IDNet-
ON
1 2 3 4 5 6 7 8
Box width
6" (152 mm)
Tyco, Simplex, the Simplex logo, TrueAlarm, TrueAlert, and IDNet are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries. NFPA 72
and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).
SpectrAlert® Advance
Selectable Output
Notification Appliances
Audio/Visual Devices
General
System Sensor® SpectrAlert® Advance selectable-output
horns, strobes and horn/strobes are rich with features guaran-
7087pho1.jpg
7087pho4.jpg
teed to cut installation times and maximize profits. The Spec-
trAlert Advance series of notification appliances is designed to
simplify your installations, with features such as: plug-in
designs, instant feedback messages to ensure correct installa- Indoor Ceiling Outdoor Ceiling
tion of individual devices, and eleven field-selectable candela Horn/Strobe Strobe
settings for wall and ceiling strobes and horn/strobes.
More specifically, when installing Advance products, first
attach a universal mounting plate to a four-inch square, four-
7087pho2.jpg
inch octagon, or double-gang junction box. The two-wire
7087pho3.jpg
mounting plate attaches to a single-gang junction box.
Then, connect the notification appliance circuit wiring to the
SEMS terminals on the mounting plate. Indoor Wall Indoor Ceiling
Horn/Strobe Strobe
Finally, attach the horn, strobe, or horn/strobe to the mounting
plate by inserting the product’s tabs in the mounting plate’s
grooves. The device will rotate into position, locking the prod-
uct’s pins into the mounting plate’s terminals. The device will
temporarily hold in place with a catch until it is secured with a
7087pho5.jpg
7087pho6.jpg
captured mounting screw.
SpectrAlert Advance products allow you to choose:
• 12 or 24 volts. Indoor Wall Outdoor Wall
Horn Strobe
• 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, or 185 can-
dela by way of a rear-mounted slide switch and front view- • Outdoor products rated from –40°F and 151°F (–40°C and
ing window. 66°C).
• Horn tones and volume by way of a rotary switch. • Outdoor products rainproof per UL50 (NEMA 3R) and
weatherproof per NEMA 4X, IP56
• The SpectrAlert Advance series includes outdoor notifica-
tion appliances. Outdoor strobes and horn/strobes (two- • Minimal intrusion into the backbox.
wire and four-wire) are available for wall or ceiling. Outdoor • Horn rated at 88+ dbA at 16 volts.
horns are available for wall only. All System Sensor outdoor • Rotary switch for tone selection.
products are rated between –40°F and 151°F (–40°C and
66°C) in wet or dry applications. • Three horn volume settings.
Models available: • Electrically compatible with existing SpectrAlert products.
7087dim12009.tif
4.7” 6.8”
2.5
5.6”
2.5”
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.