A REPORT

ON
STRUCTURAL ANALYSIS AND DESIGN
OF
RESIDENTIAL BUILDING
OF

MR. BINOD CHAUDHARI


AT

KIRTIPUR-08, KATHMANDU

SUBMITTED TO:
KIRTIPUR MUNICIPALITY
PANGA, KIRTIPUR, KATHMANDU
Table of Contents
1.1 General....................................................................................................................................4

1.2 Project Location......................................................................................................................4

1.3 Access......................................................................................................................................4

1.4 Site Area..................................................................................................................................4

1.5 Anatomy of Building...............................................................................................................4

1.6 Description of the Building.....................................................................................................5

1.7 Scope and Limitation..............................................................................................................6

2 Load Cases.....................................................................................................................................6

2.1 Codes of Practices...................................................................................................................6

2.2 Load Pattern............................................................................................................................7

2.3 Loading Combinations (IS 1893: PART 1).............................................................................7

3 Design Parameters..........................................................................................................................8

3.1 Structural System....................................................................................................................8

3.2 Construction Materials:...........................................................................................................8

4 Load Calculation............................................................................................................................8

4.1 Dead Load...............................................................................................................................8

4.2 Live Load................................................................................................................................8

4.3 Floor Finish Load....................................................................................................................8

4.4 Seismic Load...........................................................................................................................9

5 3D Analysis..................................................................................................................................10

5.1 Input in ETABS.....................................................................................................................11

5.2 Output from ETABS.............................................................................................................14

5.3 Output from SAFE................................................................................................................20

6 Sample Design Calculation..........................................................................................................28

6.1 Column Design......................................................................................................................28

6.2 Beam Design.........................................................................................................................31

6.3 SLAB DESIGN.....................................................................................................................33


6.4 Structural Details...................................................................................................................34

7 Annex...........................................................................................Error! Bookmark not defined.

7.1 Acceptability Criteria............................................................Error! Bookmark not defined.

8 Structural Design Check List.......................................................................................................35


Introduction

1.1 General
The purpose of this report is to summarize design methodology, structural calculation and design
output of proposed residential building of Mr. Binod Chaudhari. The data inputs, analysis,
calculations and outputs are computer aided by the structural analysis software ETABS v18.1.1 and
SAFE v16.0.1. The seismic design of the building is done and the brief has been prepared.

1.2 Project Location


The proposed project is situated at Kirtipur, Kathmandu.

1.3 Access
The site is connected via 4.7m wide road in East direction.

1.4 Site Area


The total Land Area of the proposed project (as per field measurement) is 1333.26 sq. ft.

The proposed building is a 3.5 story residential building.

1.5 Anatomy of Building


The vertical or gravity load carrying system of the building comprises a system of vertical columns
interconnected by horizontal beams, which supports the floors and roofing. The components of a
typical RCC-framed structure are:

 Foundation
 Column
 Beam
 Slab
 Staircase
 Wall

4
1.6 Description of the Building
Building Type Residential Building
Location Kirtipur, Kathmandu, Nepal
Total Land Area 1536.783 sq. ft.
Plinth Area 533.783 sq. ft.
Structural system Special Moment Resisting Frame structure
Soil type Medium Soil
Seismic zone Zone V
Bearing Capacity 120 kN/m2 (Assumed)
Foundation Isolated
Number of storey Three and Half
Top storey height 8’4”
Floor to floor height 8’4”
Width of wall 230 mm & 115 mm
i. Dead Load
Type of loads ii. Live Load as per IS 875 part II
iii. Earthquake induced load as per IS 1893
Analysis Tools ETABS v18.1.1, SAFE v16.0.1
Size of Beam 230 mmx356 mm (9”x16”) & 9”x18”
Size of Column 350 mm x 350 mm (14”x14”)
Depth of Slab 127 mm (5”)
Type of Staircase Open well Staircase
Grade of Concrete M20
Grade of Steel Fe500

5
1.7 Scope and Limitation
The report is based in the architectural drawing provided.

2 Load Cases
2.1 Codes of Practices

Following codes of practices developed by Bureau of Indian Standards and Nepal National Building
Codes were followed in the analysis and design of building:

1. Nepal National Building Codes

a. NBC 101 (Material Specifications)

b. NBC 102 (Unit Weight of Materials)

c. NBC 103 (Occupancy Loads)

d. NBC 105 (Seismic Design of Buildings)

e. NBC 110 (Plain and Reinforced Concrete)

2. Indian Standard

a. IS 456:2000 (Code of practice for plain and reinforced concrete)

b. IS 1893 (part 1):2016 (Criteria for earthquake resistant design of structures)

c. IS 13920: 1993 (Code of practice for ductile detailing of reinforced concrete


structures subjected to seismic forces)

d. IS 875 (part 1):1987 (to assess dead loads)

e. IS 875 (part 2):1987 (to assess live loads)

f. SP 16, SP 24 and SP 34 (design aids and hands book)

6
2.2 Load Pattern
TABLE: Load Patterns
Name Type Self Weight Multiplier Auto Load
       
Dead Dead 1  
Live Load Live 0  
Floor Finish Dead 0  
9inch wall load Dead 0  
5inchwall load Dead 0
Parapet Load Dead 0  
Stair live live 0
Stair load Dead 0
EQx Seismic 0 IS1893 2016
EQy Seismic 0 IS1893 2016
`

2.3 Loading Combinations (IS 1893: PART 1)


LOAD COMBINATIONS
i. 1.5 (DL)
ii. 1.5 (DL + LL)
iii. 1.2 (DL + LL + EQx)
iv. 1.2 (DL + LL - EQx)
v. 1.2 (DL + LL + EQy)
vi. 1.2 (DL + LL – EQy)
vii. 1.5 (DL + EQx)
viii. 1.5 (DL - EQx)
ix. 1.5 (DL + EQy)
x. 1.5 (DL - EQy)
xi. 0.9DL + 1.5EQx
xii. 0.9DL - 1.5EQx
xiii. 0.9DL + 1.5EQy
xiv. 0.9DL - 1.5EQy

7
3 Design Parameters
3.1 Structural System
Since, the building has number of plane frames along both directions, 3D frame analysis has been
done. The frames are analyzed as Special Moment Resisting Frame (SMRF)

3.2 Construction Materials:

Brick: 1st class Local bricks of compressive strength of 100


2
kg/cm
Sand: Specification as per IS Code
Aggregate: Specification as per IS Code
Grade of Concrete: M20
Grade of Steel: Fe500 TMT Steel

4 Load Calculation
4.1 Dead Load
Calculation of wall load
Brick Masonry density = 19.2 kN/m3, IS : 875 (Part 1) - 1987
Floor height = 2.9718m
Floor height deducting beam depth = 2.9718-0.3556m=2.6162m
load intensities are;
Solid 9” thick wall (0% void) = 11.57 kN/m
Solid 9” thick wall (10% void) = 10.42 kN/m
Solid 9” thick wall (35% void) = 7.51 kN/m
Solid 5” thick wall below slab (0% void)= 6.95 kN/m
Solid 5” thick wall below beam (0% void)= 6.39kN/m
And respective wall loads according to the voids
Parapet wall = 2.92kN/m
Stair deadload = 5.52kN/m, 8.1 kN/m and 9.83KN/m
Stair live = 2.61kN/m, 3.83kN/m and 4.94KN/m

4.2 Live Load

All rooms and kitchens = 2.0 kN/m2 {IS 875 (Part 2) 1987-Table 1}
Toilet and bath rooms = 2.0 kN/m2 {IS 875 (Part 2) 1987-Table 1}
Corridors, passages, staircases
including fire escapes and store
rooms = 3.0 kN/m2 {IS 875 (Part 2) 1987-Table 1}
Terrace with access provided = 1.5 kN/m2 {IS 875 (Part 2) 1987-Table 2}
Terrace with access not provided = 0.75 kN/m2 {IS 875 (Part 2) 1987-Table 2}
(Except for Maintenance)

8
4.3 Floor Finish Load
Floor Finish Load = 1.0 kN/m2 (screed)

4.4 Seismic Load


Lateral load acting on the buildings are seismic load and wind load. But seismic load is predominant
in case of RCC building situated on Kathmandu valley.
So, the seismic load is calculated by seismic coefficient method as per NBC 105 2077
Seismic Load = As per NBC 105:2077
Seismic coefficient method considers the calculation of base shear of the building considering
different factors. It also realizes each storey as a lumped mass system and distributes the base shear
to all lump mass systems.

Seismic coefficient is calculated as per NBC 105:2077

9
5 3D Analysis
The space frame is modeled using Integrated Building Design Software ETABS v18.1.1 and the
foundation system is modeled using SAFE v16.0.1. The loads are taken as per above
calculations and design data considered.

Figure 5-4.4-i: 3D model of building

10
5.1 Input in ETABS

Figure 5.1-: Typical floor Live Load

Figure 5.1-ii: Floor Finish Load

11
Figure 5.1-iiiii: Stair dead Load

Figure 5.1-iviii: Stair live Load

12
5.2 Output from ETABS

Figure 5.2-v: Joint Reaction for 1.5(LL+DL)

Figure 5.2- vi: AFD for 1.5(DL+LL) at GRID 1

13
Figure 5.2-vii: AFD for 1.5(DL+LL) at GRID 2

Figure 5.2- viii: AFD for 1.5(DL+LL) at GRID 3

14
Figure 5.2- ix: AFD for 1.5(DL+LL) at GRID 4

Figure 5.2- x: In plane Shear for 1.5(DL+LL) at GRID 1

15
Figure 5.2-xi: In plane Shear for 1.5(DL+LL) at GRID 2

Figure 5.2- xii: Inplane shear diagram for 1.5(DL+LL) at GRID 3

16
Figure 5.2-xiii: In plane Shear for 1.5(DL+LL) at GRID 4

Figure 5.2-xiv: In plane Bending for 1.5(DL+LL) at GRID 1

17
Figure 5.2- xv: In plane Bending for 1.5(DL+LL) at GRID 2

Figure 5.2- xvi: In plane Bending for 1.5(DL+LL) at Grid 3

18
Figure 5.2-xviix: In plane Bending for 1.5(DL+LL) at Grid 4

Figure 5.2xviii: Longitudinal Reinforcement Demand at Grid 1

19
Figure 5.2xix: Longitudinal Reinforcement Demand at Grid 2

Figure 5.2xx: Longitudinal Reinforcement Demand at Grid 3

20
Figure 0xxi: Longitudinal Reinforcement Demand at Grid 4

Figure 0xxii: Longitudinal Reinforcement Demand at Grid A

21
Figure 0xxiii: Longitudinal Reinforcement Demand at Grid C

Figure 0xxiv: Longitudinal Reinforcement Demand at Grid D

22
5.3 Output from SAFE

Figure 5.3-xxv: Footing Plan with beam size and footing thickness
note: number denotes thickness

23
Figure 5.3- xxvi: Soil Pressure Diagram under Service Load

Figure 5.3- xxvii: Displacement/Settlement under Service Load

24
Figure 5.3- xxviii: Punching Shear Ratio

COMMENT: Strap Beams are provided so punching is safe

Figure 5.3- xxix: Reinforcement Demand (mm2/m) along Strap Beam

25
5.3- xxx: Reinforcement Demand (mm2/m) along Strap Beam

5.4 Analysis Results

TABLE 1: Modal Participating Mass Ratios        


Case Mode Period SumUX SumUY SumUZ SumRX SumRY SumRZ
    sec            
Modal 1 0.445 0.0141 0.6625 0 0.1722 0.0026 0.2021
Modal 2 0.42 0.8673 0.6825 0 0.1757 0.1611 0.2023
Modal 3 0.349 0.8735 0.8743 0 0.1793 0.1623 0.8782
Modal 4 0.152 0.9551 0.8773 0 0.1998 0.798 0.8859
Modal 5 0.151 0.9571 0.9697 0 0.9017 0.8142 0.8905
Modal 6 0.144 0.9694 0.97 0 0.9028 0.91 0.9599
Modal 7 0.1 0.9895 0.9753 0 0.927 0.9693 0.9721
Modal 8 0.098 0.9969 0.9973 0 0.9984 0.991 0.9779
Modal 9 0.095 1 1 0 1 1 1

TABLE 2: Diaphragm Center Of Mass Displacements            


Story Output Case Step Number UX UY RZ Point X Y
      mm mm rad   m m
Story3 EQx 1 7.097 -0.047 -0.000065 1 6.1184 2.68
Story3 EQx 2 7.112 -0.196 -0.00019 1 6.1184 2.68

26
Story3 EQx 3 7.083 0.102 0.00006 1 6.1184 2.68
Story3 EQy 1 -0.012 7.749 0.000375 1 6.1184 2.68
Story3 EQy 2 -0.038 8.014 0.000589 1 6.1184 2.68
Story3 EQy 3 0.013 7.485 0.000161 1 6.1184 2.68
Story2 EQx 1 5.11 0.005 -0.000043 70 4.8523 2.7218
Story2 EQx 2 5.123 -0.023 -0.000124 70 4.8523 2.7218
Story2 EQx 3 5.097 0.034 0.000038 70 4.8523 2.7218
Story2 EQy 1 -0.031 5.223 0.000327 70 4.8523 2.7218
Story2 EQy 2 -0.054 5.274 0.000472 70 4.8523 2.7218
Story2 EQy 3 -0.008 5.172 0.000182 70 4.8523 2.7218
Story1 EQx 1 2.315 0.003 -0.00002 71 4.6833 2.6729
Story1 EQx 2 2.319 -0.004 -0.000057 71 4.6833 2.6729
Story1 EQx 3 2.311 0.01 0.000018 71 4.6833 2.6729
Story1 EQy 1 -0.008 2.331 0.000141 71 4.6833 2.6729
Story1 EQy 2 -0.016 2.344 0.000209 71 4.6833 2.6729
Story1 EQy 3 -0.001 2.318 0.000074 71 4.6833 2.6729

TABLE: Story Drifts            


Directio
Story Output Case n Drift Label X Y Z
          m m m
Story 0.00071
3 EQx X 9 16 10.04 5.065 8.52
Story 0.00075
3 EQx X 8 16 10.04 5.065 8.52
Story 0.00071
3 EQx X 9 19 9.405 0 8.52
Story 0.00080
3 EQy Y 9 16 10.04 5.065 8.52
Story 0.00091
3 EQy Y 5 16 10.04 5.065 8.52
Story 0.00075
3 EQy Y 4 11 3.35 0.1394 8.52
Story 0.00100
2 EQx X 3 14 -0.45 5.065 5.68
Story 0.00104
2 EQx X 2 14 -0.45 5.065 5.68
Story 0.00100
2 EQx X 1 19 9.405 0 5.68
Story 0.00134
2 EQy Y 9 16 10.04 5.065 5.68
Story 0.00150
2 EQy Y 1 16 10.04 5.065 5.68
Story 0.00119
2 EQy Y 8 16 10.04 5.065 5.68
Story 0.00083
1 EQx X 2 8 8.805 5.065 2.84
Story EQx X 0.00086 8 8.805 5.065 2.84
27
1 4
Story
1 EQx X 0.00083 10 8.805 0 2.84
Story 0.00102
1 EQy Y 6 10 8.805 0 2.84
Story 0.00112
1 EQy Y 8 10 8.805 0 2.84
Story 0.00092
1 EQy Y 4 10 8.805 0 2.84

6 Sample Design Calculation


6.1 Design

Column ETABS Concrete Frame Design


IS 456:2000 + IS 13920:2016 Column Section Design

Column Element Details Type: Ductile Frame (Summary)


Level Element Unique Name Section ID Combo ID Station Loc Length (mm) LLRF
Story2 C9 35 COL 14"x14" UDCon14 0 2840 0.957

Section Properties
b (mm) h (mm) dc (mm) Cover (Torsion) (mm)
304.8 304.8 60 30

Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
22360.68 20 1 500 500

Design Code Parameters


ɣC ɣS
1.5 1.15

Axial Force and Biaxial Moment Design For Pu , Mu2 , Mu3


Design Pu Design Mu2 Design Mu3 Minimum M2 Minimum M3 Rebar Area Rebar %
kN kN-m kN-m kN-m kN-m mm² %
97.0372 -56.0845 -3.5984 1.9407 1.9407 1306 1.41

28
Axial Force and Biaxial Moment Factors
K Factor Length Initial Moment Additional Moment Minimum Moment
Unitless mm kN-m kN-m kN-m
Major Bend(M3) 0.764859 2484.4 -1.7255 0 1.9407
Minor Bend(M2) 0.660209 2484.4 -17.8578 0 1.9407

Shear Design for Vu2 , Vu3


Shear Vu Shear Vc Shear Vs Shear Vp Rebar Asv /s
kN kN kN kN mm²/m
Major, Vu2 28.5507 50.936 29.8462 28.5507 337.85
Minor, Vu3 33.3034 50.936 29.8462 33.3034 337.85

Joint Shear Check/Design


Joint Shear Shear Shear Shear Joint Shear
Force VTop Vu,Tot Vc Area Ratio
kN kN kN kN cm² Unitless
Major Shear, Vu2 N/A N/A N/A N/A N/A N/A
Minor Shear, Vu3 N/A N/A N/A N/A N/A N/A

(1.4) Beam/Column Capacity Ratio


Major Ratio Minor Ratio
N/A N/A

Additional Moment Reduction Factor k (IS 39.7.1.1)


Ag Asc Puz Pb Pu k
cm² cm² kN kN kN Unitless
929 13.1 1325.7729 290.692 97.0372 1

Additional Moment (IS 39.7.1)


Consider Length Section KL/Depth KL/Depth KL/Depth Ma
Ma Factor Depth (mm) Ratio Limit Exceeded Moment (kN-m)
Major Bending (M3 ) Yes 0.875 304.8 6.234 12 No 0
Minor Bending (M2 ) Yes 0.875 304.8 5.381 12 No 0

Notes:
N/A: Not Applicable
N/C: Not Calculated
N/N: Not Needed

29
30
6.2 Beam Design

ETABS Concrete Frame Design


IS 456:2000 + IS 13920:2016 Beam Section Design

Beam Element Details Type: Ductile Frame (Summary)


Level Element Unique Name Section ID Combo ID Station Loc Length (mm) LLRF
Story1 B10 80 BEMA 9"x16" UDCon7 2397.6 2550 1

Section Properties
b (mm) h (mm) bf (mm) ds (mm) dct (mm) dcb (mm)
228.6 355.6 228.6 0 30 30

Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
22360.68 20 1 500 500

Design Code Parameters


ɣC ɣS
1.5 1.15

Factored Forces and Moments


Factored Factored Factored Factored
Mu3 Tu Vu2 Pu
kN-m kN-m kN kN
-30.3818 0.1517 40.6704 0

Design Moments, Mu3 & Mt


Factored Factored Positive Negative
Moment Mt Moment Moment
kN-m kN-m kN-m kN-m
-30.3818 0.228 0 -30.6098

Design Moment and Flexural Reinforcement for Moment, Mu3 & Tu


Design Design -Moment +Moment Minimum Required
-Moment +Moment Rebar Rebar Rebar Rebar
kN-m kN-m mm² mm² mm² mm²
Top (+2 Axis) -30.6098 235 0 235 160
Bottom (-2 Axis) 0 118 0 0 118

Shear Force and Reinforcement for Shear, Vu2 & Tu

31
Shear Ve Shear Vc Shear Vs Shear Vp Rebar Asv /s
kN kN kN kN mm²/m
52.9269 0 53.9885 33.233 459.48

Torsion Force and Torsion Reinforcement for Torsion, Tu & VU2


Tu Vu Core b1 Core d1 Rebar Asvt /s
kN-m kN mm mm mm²/m
0.1517 40.6426 188.6 315.6 220.34

32
6.3 SLAB DESIGN

fy 500 N/mm2
fck 20 N/mm2
d' 20 mm
DESIGN OF TWO WAY SLAB

Type Self Partition Mome nt Spacing Spacing


lx Ly d D FF LL BM dreq D AstFinal Ф

Check
Slab of Weight Load Coefficie nt re quire provided
No. Pane kN/m
(m) (m) (mm) (mm) kN/m2 kN/m2 kN/m2 Value (kNM) (mm) d+d' (mm2) (mm) ( ") ( ")
l 2

Slab at ground floor level


3.30 4.88 107.00 127.00 0.0742 9.10 58 78 OK 266.44 10 11.61 6.0
F1 3.30 4.88 107.00 127.00 0.0554 6.79 51 71 OK 242.13 10 12.64 6.0
4 3.18 1.00 1.32 2.00
(3) 3.30 4.88 107.00 127.00 0.047 12.58 69 89 OK 362.92 10 8.52 6.0
3.30 4.88 107.00 127.00 0.035 9.37 59 79 OK 299.78 10 10.31 6.0

DEFLECTION CHECK (IS 456:2000, cl 23.2.1)

a b c
cl 23.2.1 cl 23.2.1
cl 23.2.1 a
b c
23 1 1.45

Ast required 362.92


Ast provided 515.35
fs 204
pt 0.48

33
6.4 Structural Details
Foundation Details
Type of foundation: Isolated & Strap footing
Concrete Grade: M20
Reinforcement Grade: Fe500
Clear Cover: 50 mm
**Refer Structural Drawing**

Column Details
Size: 14”x14”
Concrete Grade: M20
Reinforcement Grade: Fe500
Clear Cover: 40 mm
**Refer Structural Drawing**

Beam Details
Primary beam size: 9”x14”
Concrete Grade: M20
Reinforcement Grade: Fe500
Clear Cover: 25 mm
**Refer Structural Drawing**

Slab Details
Thickness: 5”
Concrete Grade: M20
Reinforcement Grade: Fe500
Clear Cover: 15 mm
**Refer Structural Drawing**

Staircase Details
Waist slab thickness: 5”
Concrete Grade: M20
Reinforcement Grade: Fe500
Clear Cover: 15 mm
**Refer Structural Drawing**

34
7 Structural Design Check List
AS PER SUBMITTED
BUILDING ELEMENTS REMARKS
DESIGN

GENERAL

Building Structure Type RCC Frame Structure

Number of storey applied for permit (in Nos.) 5

Number of storey considered in structural design (in Nos.) 5

If Computer Aided Design (CAD) is used, please state the


ETABS, SAFE
name of the software package

☐Yes
Provision for further extension
☒No

Total height (h) of structure with extension (in m) 14.224

NBC 101-1994 MATERIALS SPECIFICATIONS

☐Structural Aluminium
☐Brick Masonry
Materials to be used in structure(tick the listed materials ☐Timber
that will be used in structure element) ☐Structural Steel
☒RCC (Reinforcement Bar)
☐Stone Masonry

NBC 102-1994 UNIT WEIGHT OF MATERIALS

Specify the design unit weight of materials: Steel (in KN/m3) 78.5

Specify the design unit weight of materials: RCC (in KN/m3) 25

Specify the design unit weight of materials: Brick Masonry


19.2
(in KN/m3)

NBC 103-1994 OCCUPANCY LOAD (IMPOSED LOAD)

For Residential buildings

Occupancy Load (Uniformly Distributed load in kN/m2) for


2
Rooms and Kitchens

Occupancy Load (Uniformly Distributed load in kN/m2) for


3
Corridor, Staircase, Store

Occupancy Load (Uniformly Distributed load in kN/m2) for


3
Balcony

35
NBC 104-1994 WIND LOAD

Wind Zone 1 NOT APPLICABLE

Basic wind speed (in m/s) 47 NOT APPLICABLE

NBC 105-1994 SEISMIC DESIGN OF BUILDINGS IN NEPAL

☒Seismic Coefficient Approach


Method adopted for earthquake resistant design ☐Response Spectrum Method
☐Others

Adopted Code for Seismic Design NBC 105:2077 EBPS as per IS 1893:2016

☐Type I (Hard)
Subsoil category ☒Type II (Medium)
☐Type III (Soft)

3432.41
Seismic Weight (W) (in kN)

Fundamental Time Period of the building along X (Tx) (in


0.549
Seconds)

Fundamental Time Period of the building along Y(Ty) (in


0.549
Seconds)

Seismic zoning factor (Z) 0.36

Importance Factor (I) 1

Response reduction factor (R) 5

Spectral acceleration coefficient (Sa/g) along X 2.5

Spectral acceleration coefficient (Sa/g) along Y 2.5

Design Horizontal Seismic Coefficient Along X (Ah) 0.09

Design Horizontal Seismic Coefficient Along Y (Ah) 0.09

Base Shear(VB) for Seismic Coefficient Along X 308.92

Base Shear(VB) for Seismic Coefficient Along Y 308.92

Maximum Inter-storey Drift (mm) 4.263

Corresponding Storey height for Maximum Inter- Storey


2540
Drift (h)(mm)

Maximum Inter-storey Drift Ratio 0.001501

NBC 106-1994 SNOW LOAD

36
☐Perennial
Snowfall type or condition ☐Occasional
☒No snowfall

NBC 107-1994 PROVISIONAL RECOMMENDATION ON FIRE SAFETY

☒Yes
Have you considered fire safety requirement?
☐No

NBC 108-1994 SITE CONSIDERATION FOR SEISMIC HAZARDS

Whether Distance of construction site from toe/beginning of ☐Yes


downward slope is within 50m? ☒No

Whether Distance of construction site from river bank is ☐Yes


within 50m? ☒No

☐Yes
Availability of soil test report
☒No

NBC 114-1994 CONSTRUCTION SAFETY

Are you sure that all safety measures will be fulfilled in the ☒Yes
construction site as per this code? ☐No

☒Safety hard hat


☒Safety goggles
Safety wares used ☒Safety boots
☒Safety belts
☒First aid facility

STRUCTURAL DATA FOR FRAMED RCC STRUCTURE

NBC 110-1994 PLAIN AND REINFORCED CONCRETE

☒M20
☐M25
Concrete grade in structure
☐M30
☐M35

☐Fe-415
Reinforcement Steel Grade ☒Fe-500
☐Fe-550

SLAB DESIGN

Boundary condition of slab ☐4 side continuous


☐1 short side discontinuous
☐1 long side discontinuous
☒2 adjacent side continuous
☐2 long side continuous

37
☐2 short side continuous
☐1 long side continuous
☐1 short side continuous
☐4 side discontinuous

Effective Thickness of slab (d) (in mm) 107

Short span of Critical slab panel (L) (in mm) 3300

Calculated short span to effective depth ratio (L/d) for the


30.84
corresponding slab

Basic (L/d) ratio 23

Required modification factor for tension reinforcement 1.34

Required Tension reinforcement(Ast) for short span bottom


362.92 mm2
reinforcement

Provided Tension reinforcement(Ast) for short span bottom


515.35 mm2
reinforcement

Actual Modification factor for tension reinforcement 1.45

CHECK FOR CRITICAL BEAM

Effective depth of beam (d) (in mm) 314.6

Critical span (L) (in mm) 4876.8

☐Cantilever
☐Simply supported
Support condition
☒One side continuous
☐Both side continuous

Basic (L/d) ratio 23

Calculated critical span to effective depth ratio (L/d) 15.5

CHECK FOR CRITICAL COLUMN

Critical column height (mm) 2840

Minimum size of column (mm x mm) 350x350

☒Yes
Short column effect considered or not
☐No

Minimum area of longitudinal reinforcement provided (%) 1.27

Design Philosophy Limit State method

LOAD COMBINATIONS

38
1: DL 1.5

1: LL 1.5

2: DL 1.2

2: LL 1.2

2: EQ 1.2

3: DL 1.5

3: EQ 1.5

4: DL 0.9

4: EQ 1.5

Whether sample design calculations of foundations, columns, ☒Yes


beams and slabs are submitted
☐No

☐PILE
☒Strap
Type of Foundations ☒Isolated
☒Combined
☐Raft

Depth of foundation from ground level to the bottom of


1.82
footing (in m)

39