Corbel Design [PCI 6th Edition]ACI 318

Project: SHY_230_132 kV GIS


Date:
Designer: kaosar alam

GIVEN (INPUTS)
Vu 9 kips
Nu 1.8 kips
Fy 60 ksi
fc' 3500 psi
f 0.75
b 20 in
lp 10 in
h 14 in
d 13 in
a 6 in
b 1 Uncoated
l 1 Normal Weight Concrete
m 1.4 Concrete to concrete, monolithically
poured

mmax 3.4
CALCULATIONS/CHECKS
Vumax 280 kips (1000 * l *Acr)
2

Vu < Vumax OK

As1 0.14 in2

As2 0.08 in2


me 3.4

As,min 0.61 in (0.04*b*d*(fc/Fy))


2

As,req 0.61 in2


An 0.04 in (Nu/f*Fy)
2

Ah 0.28 in (0.5*(As-An)
2

Chose Corbel Reinforcement Bar Size


Bar Size #5
Bar Dia 0.625 in.
ldh 12.68 in.(chk cover factor)