You are on page 1of 2

DIMENSIONAL PLUMBNESS

BEFORE WELDING

CLIENT : PT. Agincourt Resources REPORT. NO. : 003-PLB/QC-EMK/VII/20


PROJECT : Martabe Recyn Plant DATE : 10 - 07 - 20
ITEM : Cyanide Adsorption Tank ( TK-012 )

0o
330o 30o

300o 60o

270o 90o

240o
120
o
210o
150o
180 o

TOP STRAKE 3
PLUMBNESS
Measurement Result
No Angle Deviasi Deviasi Tolerance Remark
Design R Actual R Top ST-3 Acc Reject
Desain Actual
1 0o 3350 3335 3303 -47 -32 ±31,75 √
2 30o 3350 3338 3317 -33 -21 ±31,75 √
3 60o
3350 3339 3335 -15 -4 ±31,75 √
4 90o
3350 3344 3347 -3 ⁺3 ±31,75 √
5 120 o
3350 3353 3368 ⁺ 18 ⁺ 15 ±31,75 √
6 150o 3350 3352 3351 ⁺1 -1 ±31,75 √
7 180o 3350 3350 3329 -21 -21 ±31,75 √
8 210 o
3350 3351 3343 -7 -8 ±31,75 √
9 240 o
3350 3349 3338 -12 -11 ±31,75 √
10 270 o
3350 3344 3363 ⁺ 13 ⁺ 19 ±31,75 √
11 300o 3350 3343 3360 ⁺ 10 -17 ±31,75 √
12 330o 3350 0 3326 0 0 ±31,75 √

NOTE :
this plumbness point to be measured Checked By, Approved By, Acknowledge By,
from 8 point of circum
Geoindo PT. EMK/IMN PT. Agincourt Resources
at each strake (at imaginary line).
each strake will have imaginary
line offset 80-150 from welding line Name : Name : Yuwantoni Name :
DIMENSIONAL PLUMBNESS
BEFORE WELDING

CLIENT : PT. Agincourt Resources REPORT. NO. : 003-PLB/QC-EMK/VII/20


PROJECT : Martabe Recyn Plant DATE : 10 - 07 - 20
ITEM : Cyanide Adsorption Tank ( TK-012 )

0o
330o 30o
API-650 7.5.2.a Date : Date : Date :

You might also like